Line Redundancy
The CI854/CI854A supports line redundancy for PROFIBUS DP. Therefore the two
interfaces "PROFIBUS A" and "PROFIBUS B" are available on the baseplates
TP854 of the modules. There is a Redundancy Link Module functionality
implemented on the CI854/CI854A that handles the sending and receiving of data
on the PROFIBUS. Independent of any configuration the RLM sends data on both
lines and receives data only via one line. Regarding the receiving of data the RLM
checks if the slave sent data on both lines and if the data is valid. The first received
valid data on line A or B will be picked up and operated. It is possible that the slave
sends data on both lines in parallel or only on one line.
The monitoring of the line redundancy can be enabled or disabled. The default is
disabled. The enabling is done via the parameter "Line redundancy" in the settings
If the non-redundant slave gets disturbed the CI854/CI854A waits for watchdog
time before connection down will be indicated for the slave
for CI854/CI854A. If the line redundancy is enabled the warning "No activity on
PROFIBUS" will be indicated for the specific line in the case of a failure, for
example if there is a fault on the PROFIBUS cable.
Please enable the monitoring of line redundancy, if
– redundant slaves according to the PNO redundancy specification are used
and/or
– non-redundant slaves provide a line redundant interface and/or
– non-redundant slaves with only one PROFIBUS interface are connected to
the CI854/CI854A with a RLM01.
Status Handling
Status Handling for DP-V1 Master Unit
Every status information for CI854/CI854A in terms of hardware and software
errors is indicated via the unit status. The unit status is used to present the status of
the HW unit in Control Builder M while CBM is in online mode. In addition
alarms/events are generated based on the unit status (please refer also to Alarms and
Events on page 36). For special reasons also the access to the unit status via the
controller application is supported.