can be mounted in a 1/16 DIN panel cutout.
The UDC1700 controller is housed in a 100 mm (3.94
inches) deep case and can be mounted in a 1/8 DIN
panel cutout. By using the pre-assembled mounting
fixture delivered with the unit, you can easily and
securely install the controller into the panel cutout.
Modular plug-in construction allows rapid access and
saves time. All inputs and outputs are connected on
the rear terminal block by screws.
Operator Interface
Four display combinations are offered to the operator.
The upper 4-digit 7-segment display is always
dedicated to monitor the PV. The lower display can
show:
SETPOINT (read only)
SETPOINT (adjustable)
RAMPING setpoint (ramp mode)
BLANK
Universal Inputs
All input types are available on any unit. Selection
among the various types of inputs is made by prompt
configuration. As soon as the Process Variable
reaches the value of the input range limit, the controller
displays a message. A sensor break indication is also
provided. A configurable digital filter is available from
0.5 seconds to 100.0 seconds.
Outputs
Three types of outputs (RELAY, SSR driver or DC linear)
are selectable for three outputs, through the model selection
guide or by adding a plug-in module for outputs 1, 2 and 3.
Outputs Algorithm
The UDC1200 and UDC1700 are available with the
following output algorithms:
Time proportional:
ON/OFF or time proportional with
electromechanical relay SPDT 2 A or SSR driver
(open collector).
Current proportional:
Supply directly proportional current or voltage
signal to the final control elements which require 0-
20 mA, 4 20 mA, 0-10 V or 0-5 V.
Time proportional duplex:
Three duplex modes can be selected, either
ON/OFF duplex, time proportional duplex
(heat/cool with two proportional bands, two cycle
times and deadband) or TPSC.
Current proportional duplex:
In addition to the first current/voltage output, a
second similar output with its own proportional
band is provided.
Current/Time or Time/Current duplex:
Provides a variation of traditional time or current
duplex mode by mixing current and time
proportioning together.
Control Algorithms
Four control algorithms can be set up through the
configuration menu:
On/Off PID
PD + MR TPSC
The TPSC (Three Position Step Control) control algorithm is
dedicated to control valve positioning without slidewire
feedback from the motor shaft.
Configuration
There are two levels of configuration. The SET-UP
mode allows modification of current parameters such
as tuning parameters, alarm values, setpoint limit,
ramp enable, auto-manual mode enable and autopretune enable.
The CONFIGURATION mode is more oriented to unit
personality: input selection, output 2 and 3 usage,
alarm type, communication address and lockout code.
The operator mode screens are only selectable via the
configuration software only. For instance, the alarm
value screen can be moved from setup mode to
normal operator mode if desired.
Control Mode
Manual or automatic mode with bumpless transfer is
standard feature. In manual mode, the operator can
directly control the output through the two front face
keys (raise and lower keys). The output value is
monitored on the lower display.
Alarms
Outputs 1, 2 and 3 can be used as alarms. Two
electromechanical single pole double throw relays can
activate external equipment when alarm setpoints are
reached. An LED is also activated on the front-face. A
direct or reverse acting alarm output can be
configured. A logical combination of the two alarms:
OR, AND or hysteresis (active when both alarms are
active and inactive when both alarms are inactive) can
be set which associates the two alarms status before
energizing the relay. In order to detect a defective
control loop, the controller can supply special loop
alarm control by continually monitoring the PV
response to output demand. A timer is automatically
set up when any output is on saturation mode. When
the timer reaches twice the reset time with no PV
response, the loop alarm is activated. With this soft
alarm there is no need for a heater circuit breaker,
saving wiring time and costs.
Display
Dual, four-digit LED display with decimal point location
configurable up to three places for linear ranges only.
Limit Controller
The UDC1200 1/16 DIN limit controller provides a latched
relay output which is activated when the process parameters
either exceed or fall bellow the desired value, providing a
failsafe cut-off which has to be manually reset before the
process can continue.
The UDC1200 limit controller can be configured to be either