Critical mode operation
GCB and MCB synchronization (slipping / phase matching)
Interchange (import / export control)
Load-dependent start/stop
n/f, V, P, Q, and PF remote control via analog input or interface
Load/var sharing for up to 32 gensets
Freely configurable PID controllers - 3 - 3
HMI
Soft keys (advanced LC display) DynamicsLCDTM - -
Start/stop logic for diesel / gas engines
Counters for operating hours / starts / maintenance / active/reactive energy
Configuration via PC #3
Event recorder entries with real time clock (battery backup) 300 300 300 300
Protection ANSI#
Generator: voltage / frequency 59 / 27 / 81O / 81U
Generator: overload, reverse/reduced power 32 / 32R / 32F
Generator: unbalanced load 46
Generator: instantaneous overcurrent 50
Generator: time-overcurrent (IEC 255 compliant) 51
Generator: ground fault #4
50G
Generator: power factor 55
Generator: rotation field
Engine: overspeed / underspeed 12 / 14
Engine: speed / frequency mismatch
Engine: D+ auxiliary excitation failure
Mains: voltage / frequency 59 / 27 / 81O / 81U
Mains: phase shift / rotation field 78 /
I/Os
Speed input (magnetic / switching; Pickup)
Discrete alarm inputs (configurable) 10 10 10 10
Discrete outputs (configurable) LogicsManagerTM max. 12 max. 12 max. 12 max. 12
External discrete inputs / outputs via CANopen (maximum) 16 / 16 32 / 32 16 / 16 32 / 32
Analog inputs #5 (configurable) FlexInTM 3 3 3 3
Analog outputs (+/- 10V, +/- 20mA, PWM; configurable) 2 2 2 2
External analog inputs / outputs via CANopen (maximum) - 16 / 4 - 16 / 4
Display of J1939 analog values (number of SPNs) 16 - 16 -
Display and evaluation of J1939 analog values (supported SPNs) - 100 - 100
CAN bus communication interfaces #6 FlexCANTM 2 2 2 2
RS-232/485 Modbus RTU Slave interface(s) 1 / 1 1 / 1 1 / 1 1 / 1
Listings/Approvals
UL Listing
cUL Listing
LR & ABS Marine Approval
CE Marked
Part Numbers
1A CT inputs / front panel mounting with display #7 P/N 8440- - - 1816 1842
5A CT inputs / front panel mounting with display #7 P/N 8440- - - 1831 1843
1A CT inputs / cabinet back mounting w/o display P/N 8440- 1818 1844 - -
5A CT inputs / cabinet back mounting w/o display P/N 8440- 1817 1845 - -
Spare connector kit P/N 8923- 1314 1314 1314 1314