CTI 2582 16-Point Isolated 125 VDC Input Module
2582 16-Point Isolated 125 VDC Input Module
The 2582 16-point discrete input module accepts sixteen 125 VDC discrete isolated inputs to the CTI 2500 Series® or Simatic® 505 I/O base.
Features
1500V channel-to-channel isolation
1500V channel-to-backplane isolation
Sourcing and sinking applications
Indicator LEDs for each channel
Features
1500V channel-to-channel isolation
1500V channel-to-backplane isolation
Sourcing and sinking applications
Indicator LEDs for each channel
2580. 2581 and 2582 16-Point
Isolated Discrete Input Modules
Specifications
Inputs Per Module: 16 Isolation:
1500 VDC channel-to-channel
1500 VDC channel-to-backplane
Input Voltage:
2580: 95-132 VAC
2581: 12-56 VDC, 7-42 VAC
2582: 90-146 VDC
Input Current: 7 mA nominal per circuit
Turn ON Time:
2580: 1 AC cycle
2581/2582: 1.7 mSec nominal Turn OFF Time:
2580: 1 AC cycle
2581/2582: 7.2 mSec nominal
Turn ON Time:
2580: 1 AC cycle
2581/2582: 1.7 mSec nominal
Turn OFF Time:
2580: 1 AC cycle
2581/2582: 7.2 mSec nominal
Operating Characteristics for Typical Input:
2580:
Turn ON 85 VAC 2.85 mA
Turn OFF 80 VAC 1.43 mA
Nominal 120 VAC 4.0 mA
2581:
Turn ON 8.76 VDC 1.65 mA
Turn OFF 7.76 VDC 1.43 mA
Nominal 24 VDC 4.90 mA
2582:
Turn ON 63 VDC 1.93 mA
Turn OFF 60 VDC 1.79 mA
Nominal 125 VDC 3.82 mA
Connector: 2500-40F Removable
Wire Gauge: 14-22 AWG
Backplane Power: 1 Watt (maximum)
Module Size: Single wide
Shipping Weight: 1.5 lb. (0.68 Kg)
Checking Module Operation
You must check to see that the module is configured in the
memory of the PLC. This is important because the module will
appear to be functioning regardless of whether it is communi
cating with the PLC. To view the PLC I/O configuration chart
listing all slots on the base and the inputs or outputs associat
ed with each slot, refer to your Programming Manual. An ex
ample chart is shown in the following figure.
I/O MODULE DEFINITION FOR CHANNEL . . . 1 BASE……….0
I/O
SLOT ADDRESS NUMBER OF BIT AND WORD I/O SPECIAL
X Y WX WY FUNCTION
01 ......... 0001 ........1 6 ..... 00 ....... 00 ...... 00…………….NO
02 ......... 0000 .........00 ...... 00 ....... 00 ...... 00…………….NO
15 ......... 0000 .........00 ...... 00 ....... 00 ...... 00…………….NO
16 ......... 0000 .........00 ...... 00 ....... 00 ...... 00…………….NO
I/O Configuration Chart
In this example, the 16-point discrete input module is inserted
in slot 1 in I/O base 0. Data appears as 16 "X" locations starting
at "X1". For your particular module, look in the chart for the
number corresponding to the slot occupied by the module. If bit
locations appear on this line, then the module is registered in
the PLC memory and the module is ready for operation.
If the line is blank or erroneous, re-check the module to ensure
that it is firmly seated in the slots. Generate the PLC I/O config
uration chart again. If the line is still incorrect, contact your local
distributor or CTI at 1-800-537-8398 for further assistance.