CTI 2591-A 16-Point Isolated 11-146 VDC Output Module
2591-A 16-Point Isolated 11-146 VDC Output Module
The 2591-A 16-point discrete output module provides sixteen isolated outputs from the CTI 2500 Series® or Simatic® 505 I/O base.
The 2591-A is designed to switch externally supplied 11 to 146 VDC.
Features
Supports sourcing and sinking applications
1.5 Amps per output with no derating
1500V channel-to-channel isolation
Outputs individually fused
Blown fuse indicator
Blown fuse reporting to the PLC
Description
2500 Series® PLC System
Product Bulletin
The 2591-A 16-point Isolated Discrete Output Module
provides sixteen discrete isolated outputs from the CTI
2500 Series® or Simatic® 505 I/O base. The module
uses solid- state output circuits to switch on or off exter
nal devices such as pilot lamps, motor starters, or sole
noids. The 2591-A is designed to switch externally sup
plied 11 to 146 VDC. The internal logic signals are iso
lated from the external outputs to 1500 VDC.
Features
• CTI 2500 Series® or Simatic® 505 I/O base format
• 1.5 Amps per output (no derating)
• Isolated 1500 VDC channel-to-channel
• Blown fuse reporting (per channel) to the PLC
• Blown fuse indicator
• Logs in as a 16Y or 16X/16Y (jumper selectable)
• Individual fuse for each output channel
• Single-wide module
The 2591-A is capable of logging in as a 16Y or a 16X/16y.
Changing the addressing of the module is done by moving a
jumper located near the rear backplane connector as shown in
Figure 2 below. In Figure 2. the 2591-A module is inserted in slot
1 in the I/O base 0. Data appears as 16 "Y" locations starting at
"Y1". The 2591-A ships with a login of 16Y. In this configura
tion blown fuse reporting is disabled. By moving the jumper to
the REPORTS 16X INPUTS the module logs in as a 16X/16Y.
The X addresses are used to report the Blown Fuse Indication
and the 16Y addresses are used as any other normal output
would be used.