SAUTER ASM 134 series - ASM134SF132 Damper actuator
ASM 134: Damper actuator
How energy efficiency is improved
Torque-dependent cut-off facility for efficient usage of energy
Features
• For operating air dampers, shut-off dampers, butterfly valves and multi-leaf dampers
• For controllers with a switching (3-point) output
• Self-centring spindle adapter
• Gear unit can be disengaged to position the damper and for manual adjustment
• Stepping motor with electronic activation and cut-out
• Direction of rotation changed by transposing the connections
• Suitable for all fitting positions
•Maintenance-free
• Version with halogen-free cable on demand

Technical data
Power supply
Power supply 230 V~, ±15%, 50 Hz
Power consumption 3.7 W, 4.7 VA
Parameters
Torque and holding torque 30 Nm
Running time for 90° 120/240 s
Angle of rotation Max. 95°
Admissible damper shaft Ø12...20 mm, □ 10...16 mm
Admissible damper shaft (hardness) Max. 300 HV
Operating noise < 30 dB (A)
Response time 200 ms
Ambient conditions
Admissible ambient temperature–20...55 °C
Admissible ambient humidity < 95% rh, no condensation
Construction
Weight 1.8 kg
Housing Lower section black, upper section
yellow
Housing material Fire-retardant plastic
Power cable 1.2 m long, 3 × 0.75 mm²
Standards and directives
Type of protection IP40 (EN 60529)
IP54 (EN 60529)
IP55 (EN 60529)
Protection class II (IEC 60730)
EMC Directive 2014/30/EU EN 61000-6-1. EN 61000-6-2
EN 61000-6-3. EN 61000-6-4
Low-Voltage Directive 2014/35/EU EN 60730-1. EN 60730-2-14
Over-voltage categories III
Degree of contamination III
Mode of operation Type 2 B (EN 60730)
Software A (EN 60730)
Overview of types
Type Power consumption during operation Power consumption when idle
ASM134F130 3.7 W, 4.7 VA 1.1 W, 2.7 VA
Accessories
Type Description
0361977001 Assembly materials for M3R/M4R, MH32F/MH42F with ASM 124
0370990001 Auxiliary change-over contacts, single
Description of operation
When voltage is applied to the cable (2a or 2b), the control unit to be activated is moved to any de
sired position.
Direction of rotation (viewing the spindle adaptor from the actuator):
• The coupling piece turns in the clockwise direction, with the voltage on the brown cable (2a).
• The coupling piece turns in the anti-clockwise direction, with the voltage on the black cable (2b).
In the end positions (limit stop of damper, limit stop due to angle-of-rotation limit, max. angle of rota
tion of 92° reached) or in the case of an overload, the electronic motor cut-off is activated (no limit
switches). The running time can be set with switches S1 and S2 according to requirements. The man
ual adjustment is performed by turning the spindle adaptor after releasing the gear unit (button on
housing cover).
Direction of rotation changed by transposing the connections.
Additional technical data
The upper section of the housing with the cover, manual adjustment knob and cover knob contains
the stepping motor and the SUT electronics. The lower section of the housing contains the mainte
nance-free gear unit and the spindle adaptor. To reverse the direction of rotation, the brown and black
cables must be swapped.
Auxiliary change-over contacts
Switch rating max. 250 V~, current min. 20 mA at 20 V
Switch rating max. 4...30 V=, current min. 1...100 mA
Intended use
This product is only suitable for the purpose intended by the manufacturer, as described in the “De
scription of operation” section.
All related product regulations must also be adhered to. Changing or converting the product is not ad
missible.
Engineering and fitting notes
The concept of stepping motor and electronics enables the parallel operation of multiple air dampers
with different torques. The actuator can be fitted in any position and can be plugged directly onto the
damper spindle and fixed by means of the self-centring clamping lever.
| User name | Member Level | Quantity | Specification | Purchase Date |
|---|