SAUTER AVM115F122 Linear Valve Actuator
AVM 105. 115: Valve actuator
How energy efficiency is improved
Torque-dependent cut-off facility for efficient usage of energy
Features
• Activation of 2-way and 3-way valves of the VUN/BUN, VUD/BUD and VUE/BUE series
• For controllers with a switching (2-/3-point) output
• Synchronous motor with electronic control unit and time-dependent cut-off
• Direction of operation can be selected directly on the cable
•Maintenance-free gearbox with magnetic coupling
• Gear unit can be disengaged in order to position the valve by hand (hexagon key provided)
• Connection with valve spindle performed automatically
• Cap nut for valve fitting made of brass
• Fitting vertically upright to horizontal, not suspended
necting the voltage to terminals MM/N and 01. When dismantling, first the actuator and valve spindles
are released, then the cap nut. The device is delivered ex works in the middle position.
The concept of synchronous motor and magnetic coupling enables parallel operation of multiple valve
actuators of the same type.
The maximum accessory equipment for an actuator is 1 auxiliary change-over contact or 1 potentiom
eter.
The auxiliary contact accessory is screwed onto the top cover of the actuator. To be able to make the
mechanical connection, you first have to remove the indicator knob. A new indicator can be seen on
the cover of the accessory.
Additional technical data
The upper section of the housing with the cover and indicator knob contains the synchronous motor
with capacitor.
The lower section of the housing contains the maintenance-free gear unit and the gear-release knob.
Auxiliary change-over contacts:
• Switch rating max. 230 V VAC, current min. 20 mA at 20 V
• Switch rating max. 4...30 V VDC, current 1...100 mA
Power consumption
Type
Running time [s]
Status
AVM105F100
30
Operation
AVM105F120
120
Operation
AVM105F122
120
AVM115F120
120
AVM115F122
120
Outdoor installation
Operation
Active power P [W]
Apparent power S [VA]
2.4
5.4
2.0
5.0
1.6
1.7
Operation
2.0
5.0
Operation
1.6
1.7
The actuators must also be protected from the weather if they are installed outside the building.
Disposal
When disposing of the product, observe the currently applicable local laws.
More information on materials can be found in the Declaration on materials and the environment for
this product.
| GE | MMLG02 |
| GE | MMLB01 |
| GE | MVAJ105RA0802A |
| GE | IS200TRPGH1B |
| ABB | PCD231 3BHE025541R0101 |
| ABB | PCD235 3BHE032025R0101 |
| AMC | P111-6052 |
| MOOG | D635-706 |
| ABB | SCA022657R8790 CU2A01V2 |
| CTI | 2500-C200 |
| GE | IS200ESYSH1AAA |
| GE | IS200EDISG1AAA |
| SAUTER | AVM234SF132-5 |
| ABB | SCC-C 23070-0-10311111 |
| METSO | PDP401 |
| Brad Communications | DRL-DPM-BKF |
| ABB | 3BSE027062R50 PFCL 201CE-50kN |
| User name | Member Level | Quantity | Specification | Purchase Date |
|---|