SAUTER Linear valve actuator AVM 234S series AVM234SF132-6
Connection with 230 V or 100…110 V as 2-point/3-point or with continuous activation of valve
actuator (accessory 0372332)
The built-in positioner controls the actuator depending on controller’s output signal y.
A voltage signal (0...10 V–) at terminal 3u or a current signal at terminal 3i serves as the control
signal. If there is a control signal on both terminals (3u (0...10 V) and 3i (4...20 mA)) at the same time,
the input with the higher value has priority.
Direction of operation 1 (mains power supply on internal connection 2a):
When the positioning signal is increasing, the actuator spindle extends.
Direction of operation 2 (mains power supply on internal connection 2b):
When the positioning signal is increasing, the actuator spindle retracts.
The starting point and control span are fixed. A split-range unit (only for voltage input 3u) designed for
installation in the actuator is available as an accessory for adjusting partial ranges (see split-range
unit function).
After the connection of the power supply and the initialisation, the actuator moves to every valve
stroke between 0% and 100%, depending on the control signal. Thanks to the electronics and the
travel measurement system, no stroke is lost, and the actuator does not require periodic re
initialisation. When the end positions are reached, this position is checked, corrected if necessary,
and saved again. It is thus possible to operate multiple actuators of the SUT type in parallel. The
feedback signal y0 = 0...10 V corresponds to the effective valve stroke of 0...100 %.
If the control signal 0...10 V or 4...20 mA is interrupted with direction of operation 1. the actuator
spindle moves in completely, or moves out completely with direction of operation 2.
The coding switch can be used to set the characteristic of the valve. An equal-percentage or
quadratic characteristic can only be generated when the actuator is used as a continuous actuator.
Additional switches can be used to select the running times (with the 2-point, 3-point or continuous
functions).
Continuous actuation can also be used with a power supply of 230 V or 110 V (accessory required).
You must ensure that the neutral wire of the controller is connected to the control voltage. The neutral
wire of the power supply may only be used for the module.
LED indicator: The indicator consists of bi-colour LEDs (red/green).
Both LEDs flash red
Top LED lights up red
Bottom LED lights up red
Top LED flashes green
Top LED lights up green
Initialisation
Top limit stop or “CLOSED” position reached
Bottom limit stop or “OPEN” position reached
Actuator is running, moving to “CLOSED” position
Actuator is stopped, last direction of travel “CLOSED”
Bottom LED flashes green
Bottom LED lights up green
No LED lights up
Both LEDs flash red and green
Actuator is running, moving to “OPEN” position
Actuator is stopped, last direction of travel “OPEN”
No power supply (terminal 2a or 2b)
Actuator is in manual mode
Additional technical information
The yellow housing, consisting of the front part, rear part and connecting lid, only serves as a cover.
The DC motor, electronic control unit, load-bearing section and maintenance-free gear unit are
located in the housing. The actuator spindle and the column are made of rust-proof material. The
inner printed circuit boards and the gear unit are made of steel. The valve spindle guide and the valve
neck coupling are made of die-cast aluminium.
Note on ambient temperatures: With a media temperature of up to 110 °C in the valve, the ambient
temperature is allowed to reach 60 °C. With a media temperature above 110 °C, the ambient
temperature must not exceed 55 °C. Otherwise, the intermediate piece accessory 0372336180 must
be fitted.
Abbreviations used
Abbreviation Directive
LV-D Low-Voltage Directive 2014/35/EU
EESR-2016 Electrical Equipment (Safety) Regulations 2016
EMC-D Electromagnetic Compatibility Directive 2014/30/EU
EMC-2016 Electromagnetic Compatibility Regulations 2016
RoHS-D RoHS Directives 2011/65/EU and 2015/863/EU
RoHS-2012 Restriction of Hazardous Substances (RoHS) Regulations 2012
Auxiliary change-over contacts
0372333
001
Switch rating max. 250 VAC, current min. 250 mA at 12 V (or 20 mA at 20 V)
Switch rating max. 12...30 VDC, current max. 100 mA
0372333
002
Switch rating max. 250 VAC, current min. 1 mA at 5 V
Switch rating max. 0.1...30 VDC, current 1...100 mA
If it is used once in the range up to 10 mA or up to 50 V, the gold plating is eliminated. The switch
can then only be used for a higher switch rating.
| BRAD COMMUNICATIONS | PC104-DPIO DRL-DPM-BKF |
| ABB | GJR2392700R1210 83SR07 |
| ABB | GJR2391500R1210 81EU01-1210 |
| ABB | 07AC91 GJR5252300R0101 |
| Woodward | 2301D 8273-140 |
| WOODWARD | 67DR 8440-2088 |
| AREVA | 49.102.110-20/30 |
| ABB | AWT420 A1.D1.C2.C2.A1.E5.A2.U1.D1.T1.M5 |
| ABB | REU615 HBUAEAADABCCANN1XD |
| Honeywell | TC847A1004 |
| ABB | PCD235A PEC80-CIO FU 3BHE032025R0101 |
| ABB | 3ADT218437R0001 D1 UNS4908a V5004 |
| GE | IS2020JPDBG01 |
| GE | IS420UCSBS1A |
| GE | IS215UCVFH2AB |
| ABB | REC670 1MRK004814-AG 1PCS |
| ABB | 3BDH000741R1 CTI 21-P Ex |
| ABB | TPC1582H43A1401E-T 3BHB040969R0001 |
| ABB | PSE105-600-70 |
| User name | Member Level | Quantity | Specification | Purchase Date |
|---|