SAUTER AVM322S-R Linear valve actuator AVM 234S series
The cross-section of the power cable must be selected based on the cable length and the number of
actuators. With five parallel actuators and a cable length of 50 m, a cable cross-section of 1.5 mm2
and a line resistance of > 1.5 Ω must be used (power consumption of the actuator × 5).
According to building installation regulations, the lines must be protected from overload or short cir
cuit
Specific standards such as IEC/EN 61508. IEC/EN 61511. EN ISO13849 and the like have not been
taken into account.
Local requirements regarding installation, usage, access, access rights, accident prevention, safety,
dismantling and disposal must be taken into account.
Place of installation
The devices may only be used indoors.
It is not admissible to use them in the following locations:
• in outdoor areas
• in potentially explosive atmospheres
• on ships or in vehicles
• in plants or machines with required functional safety.
Additional information
Fitting instructions
Declaration on materials and the environment
Declaration of incorporation
Power consumption at nominal voltage
Type
Running time (s/mm)
P100011900
MD 51.375
P100012470
Status
AVM321S
12 / (4)
Active power P (W) Apparent power S (VA)
Operation < 1.7
Standstill < 0.45
< 3.5
−
Sizing
AVM322S
6 / (4)
−
Operation < 1.7
Standstill < 0.45
Sizing
Max. power consumption with accessory 0500570001
for all types
Connection as 2-point valve actuator (24 V)
24 V=
24 V~
−
5.2
6.2
≥ 4.5
< 3.5
−
≥ 4.5
−
11
The OPEN/CLOSE activation is via two wires.
The actuator is connected to a permanent voltage via terminal MM and terminal 01.
When voltage (24 V) is applied to terminal 02. the actuator spindle extends into the end position.
After the voltage is switched off at terminal 02. the actuator automatically retracts into the base posi
tion.
Terminal 03 must not be connected or touch other contacts. We recommend that you insulate these.
Connection as 3-point valve actuator (24 V)
If voltage is applied to terminals MM and 01 (or 02), the valve can be moved to any position.
If voltage is applied to terminals MM and 01. the actuator spindle retracts.
If the electrical circuit is closed on terminal MM and 02. the actuator spindle extends.
If there is no voltage on terminals 01 and 02. the actuator remains in the respective position until volt
age is applied again.
| ABB | REX615 |
| ABB | 3BHS036290R0001 PA110358 |
| WESTERMO | TD-36 (485) 3618-0001 |
| ABB | MRW-6420P |
| Honeywell | CC-PWRR01 |
| GE | 345-E-P5-G5-H-E-M-N-N-1E-D-H |
| GE | SSF16Y216 |
| GE | VMIVME-7807 |
| GE | ACC-5595-208 |
| Honeywell | FC-PSU-UNI2450U |
| ABB | PP846 3BSE042238R1 |
| ALSTOM | AL129A |
| ALSTOM | LC105A-2 |
| ALSTOM | LC106-1 |
| CONVERTEAM | P111-6052 |
| Metso, | ND9106FN |
| GE | IS230JPDGH1B |
| Meggit | 200-510-071-113 |
Terminal 03 must not be connected or touch other contacts. We recommend that you insulate these.
Connection to a control voltage (0...10 V or 4...20 mA)
The built-in positioner controls the actuator depending on controller’s output signal y. A voltage signal
(0...10 V) at terminal 03 serves as the control signal. Coding switch S4 can be used to switch to a
current input (4...20 mA). If there is voltage on terminals MM/01 and a rising positioning signal, the
actuator spindle extends. The direction of operation can be reversed with coding switch S2.
The starting point and control span are fixed. For setting partial ranges (only for voltage input), a split
range unit is available as an accessory (see split-range unit function).
After the connection of the power supply and the initialisation, the actuator moves to every valve
stroke between 0% and 100%, depending on the control signal. Thanks to the electronics and the ab
solute distance measurement system, no stroke is lost, and the actuator does not require periodic re
initialisation.
If the control signal 0...10 V is interrupted in the direction of operation 1. the actuator spindle retracts
completely.
If the control signal 0...10 V is interrupted in the direction of operation 2. the actuator spindle extends
completely.
With coding switch S3. the characteristic of the valve/actuator combination can be adjusted. An
equal-percentage characteristic can only be generated when the actuator is used as a continuous ac
tuator.
Initialisation and feedback signal
The actuator initialises itself automatically when it is connected as a continuous actuator (not in 2-/3
point mode). With the first application of voltage the actuator moves until it reaches the mechanical
stop and connects to the valve.
For 8 mm travel range of AVM321SF132
After the actuator has stopped moving to connect to the valve, it moves to the upper first stop and
then to the 8 mm travel range in the opposite direction. If the valve travel range is greater than 8 mm,
the initialisation stops after 8 mm. The two values are recorded and stored by the absolute distance
measurement system. The control signal and the feedback are adapted to this effective stroke. If it
cannot move the 8 mm travel range, the initialisation is cancelled and the actuator indicates “Under
range”. After initialisation, the actuator goes to every valve stroke between 0% and 100%, depending
on the control voltage.
For 20 mm travel range of AVM322SF132
After the actuator has stopped moving to connect to the valve, it moves to the upper and lower stop.
The travel range thus achieved is recorded by the measurement system and apportioned as 0 to
100% travel range. The control signal and the feedback are adapted to this effective stroke.
In case of a power failure or the removal of the power supply, no re-initialisation needs to be carried
out. The values remain saved.
If the initialisation is interrupted, the initialisation restarts when the voltage is reapplied.
You trigger a re-initialisation by moving coding switch S8 from OFF to ON or vice versa.
When the process is triggered, the LED flashes green.
During initialisation, the feedback signal is inactive or equal to the value “0”. The initialisation is car
ried out with the shortest running time. The re-initialisation is only valid when the whole process is
complete.
If a stroke change is carried out, a re-initialisation must be triggered so that the new stroke can be
adapted.
If the valve actuator detects jamming, it will report this by setting the feedback signal to 0 V after
about 90 s. During this time, the actuator continues to try to overcome the jamming. If the jamming
can be overcome, the normal control function is activated again and the feedback signal is restored.
With 2-point or 3-point control without a feedback signal, no initialisation is performed.
Continuous control can also be implemented with a 230 V power supply with the external accessory
0500570003 “230 V module”. You must ensure that the neutral wire of the controller is connected to
the control voltage. The neutral wire of the power supply may only be used for the 230 V module