Basler Electric BE1-87G Variable Percentage Differential Relay
. Basler Electric BE1-87G Variable Percentage Differential Relay
selective, high-speed, differential protection for generators, motors, and shunt reactors.
Differential relaying selectivity is based on the ability of a relay to distinguish between an internal fault
(within the protected zone) and an external fault. Under normal operating conditions, the current flowing
into the protected zone equals the current flowing output of the protected zone with a net operating
current equal to zero. Internal faults upset this balance and result in a difference between the input and
output currents. External faults have relatively little effect on the balance because the protected zone
input current still equals the output current. Therefore, by comparing the currents on both sides of the
protected element or zone and detecting when these currents are not equal, a differential relay acts to
isolate the element or zone from the system with unsurpassed effectiveness.
BE1-87G relays typically trip a lockout (86) relay which in turn trips the generator breaker and, when
present, the field and/or neutral breakers.
are recommended for the following specific applications:
• Generators:
o Any terminal voltage and a rating of 1.000 kVA and above
o Any kVA rating and a terminal voltage of 5 kV and above
o A terminal voltage of 2.200 V or higher and a rating of more than 500 kVA
• Motors rated at 1.500 horsepower and above
• As primary protection on shunt reactors for transmission lines
• Generator ground differential
Differential relaying is the most selective form of fault protection which may be applied to the individual
elements or zones of ac power systems. Various types of differential relays and relaying systems have
evolved to take advantage of the differential principle.
Variable Restraint Characteristic
At high current levels, the inevitable difference in the saturation characteristics between current
transformers indicates a need for a compensating decrease in relay sensitivity. The design of the
BE1-87G provides a restraint factor that is proportional to input current when the restraining current (IR) is
greater than nominal (5 Aac for sensing input range 1 or 1 Aac for sensing input range 2). The BE1-87G
compares the protected zone sensed input and output currents. The lesser of the two sensed current
levels becomes the restraining current. The difference between the two sensed currents (the operating
current) is compared to a reference established by the sensitivity setting, and adjusted by an amount
proportional to the restraining current. This makes the BE1-87G more sensitive to low current internal
faults, and less sensitive to external faults with high levels of through current.
When the restraining current is at nominal (5 Aac for sensing input range 1 or 1 Aac for sensing input
range 2) or less, the relay trips if the differential current exceeds the relay setting (IS). But when the
restraining current is greater than nominal, the overall sensitivity is a combination of the front panel
setting and the restraint factor.
Design Highlights
Some of the many advantages of the BE1-87G relay are summarized below:
• Seven sensitivity levels on each of the two sensing input ranges. The seven levels allow
compensation for CT mismatch and provide the flexibility and adaptability necessary for many special
applications such as split-winding generator protection.
• Stabilizing reactor. Minimizes dissimilar performance of system CTs. Reactor can be located on the
back of the relay or remotely from the BE1-87G for flexibility of system installation.
• Variable restraint. The variable restraint characteristic allows increased sensitivity to low-current,
internal faults while providing increased security against high levels of through-current caused by
external faults.
• Single- or three-phase availability. Either configuration is available in the Basler Electric S1 draw-out
case.
• High-speed operation. The BE1-87G operates in 30 milliseconds for fault levels of 10 times the
sensitivity setting. This high-speed operation minimizes potential damage to the protected equipment.
Response characteristics for sensing input ranges 1 and 2 are shown in the Testing section.
Model and Style Number
The model number BE1-87G designates the relay as a Basler Electric, Class 100. Variable Percentage
Differential Relay.
The electrical characteristics and operational features of the BE1-87G relay are defined by a combination
of letters and numbers which constitutes the relay style number. The style number describes the features
and options of the BE1-87G relay and appears on the front panel, draw-out cradle, and inside the case
assembly.
Style Number Chart
The BE1-87G style number chart is illustrated in Figure 1-3.
Style Number Example
As an example, if the style number of a BE1-87G were G1EA1JA0C0F, the relay would have the
following characteristics and features:

| User name | Member Level | Quantity | Specification | Purchase Date |
|---|