ATEX Directive 94/9 EC – Special conditions for safe use
Relevant for RS20 Basic family devices when operating in explosive gas
atmospheres according to ATEX Directive 94/9 EC, the following applies:
List of Standards:
EN 60079-0:2009
EN 60079-15:2010
Certificate No.: DEKRA 11ATEX0139 X.
Make sure that the device has the following label:
II 3G
Ex nA IIC T4 Gc
Dekra 11ATEX0139 X
Ambient rating and temperature code:
T4: 0 °C ≤ Ta ≤ +60 °C for “B” types (item 17 of nomenclature
breakdown).
The modules shall be installed in a suitable enclosure in accordance
with EN 60079-15 providing a degree of protection of at least IP54
according to EN 60529. taking into account the environmental
conditions under which the equipment will be used.
When the temperature under rated conditions exceeds 70 °C at the
cable or conduit entry point, or 80 °C at the branching point of the
conductors, the temperature specification of the selected cable and
cable entries shall be in compliance with the actual measured
temperature values.
Provisions shall be made to prevent the rated voltage from being
exceeded by transient disturbances of more than 40 %.
Connectors shall be connected or disconnected exclusively in dead
voltage state.
DIP switches shall be switched exclusively in dead-voltage state
For the ground conductor, use a cable with a cross section of at least
1.0 mm².
The clearance between the ventilation slots of the housing and other
objects must be at least 10 cm (3.94 in).
The device must be installed in the vertical position.
If installed in a living area or office environment, the device must be
operated exclusively in switch cabinets with fire protection
characteristics in accordance with EN 60950-1.
Environment
The device may only be operated at the specified surrounding air
temperature (temperature of the surrounding air at a distance of up to
5 cm (1.97 in) from the device) and relative air humidity specified in the
technical data.
Install the device in a location where the climatic threshold values
specified in the technical data will be observed.
Use the device only in an environment within the pollution degree
specified in the technical data.
Qualification requirements for personnel
Qualified personnel as understood in this manual and the warning signs,
are persons who are familiar with the setup, assembly, startup, and
operation of this product and are appropriately qualified for their job. This
includes, for example, those persons who have been:
trained or directed or authorized to switch on and off, to ground and to
label power circuits and devices or systems in accordance with current
safety engineering standards;
trained or directed in the care and use of appropriate safety equipment
in accordance with the current standards of safety engineering;
trained in providing first aid.