DCS; Industrial control system
NameDescriptionContent
NEW CENTER
Current Location:

DOOSANDOOSAN AC SERVO MOTOR/DRIVE VISION DVSC - TM Series

From:DOOSAN | Author:LIAO | Time :2025-08-15 | 571 Browse: | Share:

Installation and wiring 

1.1. Designations 

Designations of DOOSAN AC Servo Motor and Drive are as follows.

Please refer to this section for system installation and after service.

1)Encoder Connector 2)Power Connector 3)Name Plate 4)Shaft 5 )Flange 6 )Frame 7 )Encoder

1.2. Environmental conditions 

This product was designed for indoor usage.

Caution : If used in different circumstances and environment other than stated below, damages 

may occur.

Please use under the following conditions.

1.3. Installation method 

1.3.1. Assembling of the servo motor

▷ Warning: While assembling the servo motor, avoid dropping it.

▷ Caution: While mounting the servo motor horizontally, the connector should be assembled

facing downward.

▷ The servo motor can be mounted horizontally or vertically.

▷ To prevent vibrations and extend the life of coupling and bearing, the motor shaft and the loading

shaft should be precisely aligned. Use flexible coupling when connecting directly to the load.

① The outer part of the coupling should be measured at four equidistant points each 90˚ apart,

and the gap between the maximum and the minimum readings should not exceed 0.03㎜.

② The center point of the motor and the loading shaft should be precisely aligned.

▷ Avoid excessive radial and thrust load to the motor shaft and also avoid impact that is more

than 10G when mounting the gear, coupling, pulley and etc. at the same time.

▷ A minus load means continuous operation in the regenerative braking state, when the motor is

rotated by load. The regenerative braking capacity of the servo drive is short term rated

specification equivalent to stop time of the motor. Thus, it should not be used in minus load that

generates continuous regenerative braking.

ex) Servo system for descending objects(without counterweight)

▷ The admissible load inertia into the motor shaft is within 5 times than the inertia of applied servo

motor. If it exceeds this, during deceleration it may cause regenerative malfunction.

The following steps should be taken if the load inertia exceeds more than 5 times the inertia of

the servo motor.

- Reduce the current limit. – Decelerate slowly.(Slow Down)

- Lower the maximum speed in use.

1.3.2. Mounting of the servo drive

▷ Warning: To prevent electric shock, turn off the power while mounting or uninstalling.

▷ While installing the panel, the size of the panel, cooling and wiring should be considered in

order to maintain a difference of temperature below 5℃ between the panel temperature and the

surrounding temperature in accordance with heat value of the equipment and box size.

▷ If a heating element is placed nearby, the surrounding temperature of the servo drive should be

maintained below 55℃ at all cases despite temperature rise by convection and radiation. Use a

fan to ventilate sealed inner air, and proper ventilation should be used for convection of the air.

▷ If a vibrating element is placed nearby, the drive should be mounted on shock absorbing surface.

▷ If the servo drive be exposed to corrosive gas for a long time, may cause damages to connecting

devices such as relay and circuit breaker, thus it should be avoided.

▷ Environmental conditions such as high temperature, high humidity, excessive dust and metal

particles should be avoided.

◆ Mounting method

▷ There should be a space wider than 100㎜ below and above the servo drive.

▷ There should be a space wider than 30㎜ on both sides of the servo drive.

▷ Mount the servo drive vertically. Do not use if it is mounted horizontally.

1.4. Wiring 

▶ For signal lines and encoder lines, use twisted lines or multi-core shielded twisted-pair lines.

The length for command input lines should be maximum 3m, and the encoder line should be

maximum 10m or less.

Wiring must be done in shortest distance and the remaining length should be cut.

▶ The ground circuit should be a thick line. Usage of third-class grounding or above (ground

resistance 100Ω or less) is recommended. Also, make sure to ground at one-point grounding.

▶ The following precautions should be taken to avoid malfunction due to noise.

- The noise filter should be placed as near as possible.

- Mount a surge absorber to the coil of the relay, electromagnetic contacts, solenoids and etc.

- The power line (AC input, motor input line) and the signal line should be placed 30㎝ apart

or more. Do not put them into the same duct or tie them in a bundle.

- If the power source of the servo drive is used in common with an electric welder or electrical

discharge machine, or a high-frequency noise source is present, attach noise filter to the

power or the input circuits.

- Since the core wire of the signal line cable is as thin as only 0.2 ~ 0.3㎟, excessive force to the

line should be avoided to prevent damages.

1.5. Noise treatment 

For wiring and grounding of the servo drive, the effect of switching noise which is generated by the

built-in IPM should be reduced as much as possible. Unexpected effect by outside noise should be

reduced as much as possible.

▶ Grounding method

The servo drive supplies power to the motor according to the switching of the IPM device.

Thus the Cf dv/dt current flows from the power component to the floating capacity of the motor.

To prevent the effect of the switching noise, the motor frame terminal should be connected to

the PE terminal of the servo drive terminal block and the PE terminal of the servo drive should be

directly grounded to standard ground panel.

▶ Noise filter

Noise filter is used in order to prevent noise from the power line. Please refer to the following

conditions while installing.

(a) Separate the input and output wiring and do not tie them together or put them into the same

duct.

(b) Do not put the ground wire into the same duct with the filter output line or other signal lines.

And do not tie them together.

(c) The ground wire should be wired singly to the ground panel.

(d) If the unit contains the filter, connect the filter and the equipment ground to the base of the

unit.

2. Operation 

2.1. Automatic operation 

① If the drive maintains a normal state (takes 5 sec) after the POWER turns on, it outputs the initial

position data and the positioning completion signal(VPF) after it detects the initial position by the 

absolute encoder.

② When the SVON signal is ON, the SVRDY signal turns ON after the inner GATE turns ON.

③ When the START signal is ON, the servo motor will rotate according to the position data.

(Maintain ON state of the START signal for about 100 ~ 200 msec.)

④ When the position movement starts, the position data 0 will be outputted with turning OFF the

VPF(Positioning Completion) signal.

⑤ When the position movement is complete, the VPF signal turns ON after the position input data is 

outputted.

⑥ The host controller must turn OFF the SVON signal only after the VPF signal turns ON.

(Move to the next position after the SVRDY signal turns OFF.)

⑦ After the SVRDY and the SVON signals are turned OFF, the current position data is outputted.

2.2. Jog operation and Usage of BRAKE Signal(Magazine Port move by the jog signal)

① Turn ON the Jog Switch.

② The PLC outputs the SERVO ON signal to the servo drive.

③ When the SERVO ON signal turns ON, the BRAKE release signal is outputted after the time value in

the parameter 14.

④ After the time value in the parameter 13, the SERVO READY signal is outputted.

⑤ After the SERVO READY signal is outputted, the PLC must input the JOG+ signal to the servo drive.

⑥ When the position movement is complete, the positioning completion signal(VPF) turns ON after 

the position data that is increased by more than one from the previous position is outputted.

⑦ When the positioning completion signal(VPF) turns ON, the PLC turns OFF the SERVO ON signal.

Then, the servo drive turns ON the BRAKE signal and turns OFF the SERVO READY signal after the 

time value in the parameter 15.

The servo drive outputs the current position data after the SERVO ON signal turns OFF. 

※ In the jog mode, the motor cannot rotate over 4,000 revolutions continuously. If there is an input 

over 4,000 revolutions, the motor will stop and it will not rotate. In this case, turn off the JOG+ or 

JOG- signal and then turn it on again. 


2.3. Parameter and Machine Origin setting method after replacement of the servo drive 

At the time of the first machine assembly, it should be set the absolute encoder zero-point to the 

Machine Origin. The setting method is as follows.

(These steps should be done when the external SERVO ON signal is OFF.)

2.3.1. Parameter and Machine Origin setting method of Turret/Magazine

1) Turn on the drive power.

2) Clamp the Turret.

3) Set value of the parameter 45, servo drive function selection parameter, as 0.

Please change the parameter 45 as 1 only when it needs to set as ATC because default value is 0, 

Turret/Magazine. Turn the drive power OFF and then turn ON again after setting the value.

4) Initialize the parameter value. 

Press the MODE key to change the display to diagnosis mode, and then press the DOWN key

three times to change the display to parameter initialize mode.

Even if an alarm occurs, it’s possible to change the display as state display mode, diagnosis display

mode, parameter setting mode, origin setting mode and alarm history display mode since version

DVSC-TM-14D-02. Also, even at alarm state, parameter or offset value setting is possible since that

version.

▶ Method of releasing the alarm state

 : Once the cause of the alarm is resolved, it is possible to operate the drive by turning the power 

OFF and ON again.

▶ Detection time of over load

 : The operation time of the over load alarm detect circuit is as listed below.

300% ~ ; 5.5sec

275% ~ ; 6.5sec

225% ~ ; 8sec

200% ~ ; 10sec

170% ~ ; 14sec

150% ~ ; 17.5sec

140% ~ ; 20sec

130% ~ ; 25sec

120% ~ ; 30sec

3.6.3. Detailed explanation of user parameter 

□0 Motor output capacity 

As selection parameter of the applied motor capacity, it’s possible to select 0.8, 1.5, 1.7, 2.0, 2.3,

3.0 and 4.0kW.

0 : 1.5kW 8 : 0.8kW 17 : 1.7kW 20 : 2.0kW 23 : 2.3kW 30 : 3.0kW 40 : 4.0kW

※ Use 14A drive for motors under 3.0kW and 28A drive for motors more than 3.0kW. If not applied

properly, it may cause malfunction of the motor. 

□1 Motor rotation direction 

This parameter sets the rotation direction of the motor. Please select according to the structure

of the equipment.

0 : Selects when the rotation direction of the motor and the equipment is the same.

1 : Selects when the rotation direction of the motor and the equipment is different.

□2 Option function 

This parameter is used when the NC uses the drive itself JOG mode or sets the origin position.

For use this function, OVR0 and OVR1 contact points must be connected between the drive and

the NC, and the NC program should support this feature.

0 : Option disable 1 : Option enable

OVR0 OVR1 function

OFF ON The operation mode will be changed as the drive itself JOG, and the motor

rotates by JOG+, JOG- signals.

ON ON Machine origin setting will be executed.

□3 Direction fixing, JOG function selection 

This parameter defines the function of JOG+(no.20) and JOG-(no.23) signals of CN1 connector.

0 : Defined as direction fixing signal.

JOG+ JOG- Rotation direction

OFF OFF Detects the shortest distance and rotates.

OFF ON The motor always rotates in clockwise.

ON OFF The motor always rotates in counterclockwise.

ON ON The motor always rotates in counterclockwise.

* The above statement is applicable if the parameter 1 is set as 0. If the parameter is set as

1, the motor rotates the opposite way.

1 : Magazine JOG operation signal (This is used when it need to move the tool post by the

JOG signal at the Magazine.)

JOG+ JOG- Contents

OFF OFF Only operates by position data input.

OFF ON Step JOG operates towards the direction the POST number decreases.

ON OFF Step JOG operates towards the direction the POST number increases.

ON ON Cannot be defined.

* The above statement is applicable if the parameter 1 is set as 0. If the parameter is set as

1, the motor rotates the opposite way. And, the position data input will be ignored if JOG+

and JOG- signals are ON.

※ For more detailed explanation, refer to ‘JOG operation’ section.


□4 Encoder pulse per 1 rotation

This parameter displays 1/4 value of encoder pulse count per rotation.

□5 Maximum POST number 

This parameter sets the maximum POST number. If parameter 46 is set as 3, it’s possible to set as

maximum 255. At the Teaching mode, it’s available up to 99. The position data input exceeding the

setting number will be ignored.

 

Setting range : 2 ~ 127 or 255 Teaching function : 2 ~ 99 

 

□6 Gear ratio of motor side 

This parameter sets the motor rotation counts until the machine moves up to the POST set in the

parameter 7.

 

Setting range : 1 ~ 9999 

□7 Gear ratio of machine side 

This parameter sets the POST number variation until the motor rotates up to the setting data in

the parameter 6. 

 

Setting range : 1 ~ 9999

 

Example)

1. At the TC model, the turret has 10 POST(10 angle) and makes 1 revolutions until the motor 

makes 30.75 revolutions. In case the reduction gear ratio is determined like this, the parameter 

will be set as follow, because 1 revolution of turret corresponds with 10 POST move.

Maximum POST number : 10

Gear ratio of motor side : 3075

Gear ratio of machine side : 1000

2. At the MC model, the Magazine has 41 POST(41 POT) and moves 9 POSTs until the motor 

makes 101 revolutions. In case the reduction gear ratio is determined like this, the parameter will 

be set as follows.

Maximum POST number : 41

Gear ratio of motor side : 101

Gear ratio of machine side : 9

□8 POST number of origin 

When setting the origin of machine, input the POST number that will be set as origin into this

parameter. If parameter 46 is set as 3, it’s possible to set as maximum 255.

Please refer to ‘Machine origin setting’ for more detailed explanation.

 

Setting range : 1 ~ 127 or 255 

 

□9 24 angle alternate angle function selection 

This parameter sets the 24 angle alternate angle function of the Turret.

0 : Alternate angle function disable

1 : Alternate angle function enable

10 Position loop proportional gain 

The proportional gain of the position loop is the parameter which determines the response of

position control loop. If the value increases, the mechanical response gets better. However,

mechanical impact on the machine may occur when the motor starts or stops. If the value

decreases, the mechanical response will get worse and position error increases by remaining pulse.

This also relates with the speed loop gain. 

 

Setting range : 0 ~ 9999 

□11 Speed loop proportional gain 

The proportional gain of speed loop is the parameter which determines the response of the speed

control loop. As external characteristics, it determines the degree of rigidity. If the value of the

proportional gain increases, the rigidity becomes better. Thus the larger the setting value is the

better, but too large setting may cause oscillations and hunting. The value should be set as large

as possible under a stable condition.

Setting range : 0 ~ 9999 

□12 Speed loop integral gain 

The integral gain of the speed loop is a compensatory factor which reduces normal state error and

increases rigidity. If the value of integral gain is increased, the rigidity will get better. But too large

setting may cause oscillations and the system may become unstable.

 

Setting range : 0 ~ 9999 

□13 SERVO READY ON delay time 

This parameter sets the Servo Ready signal delay time to change as ON. 

 

Setting range : 0 ~ 1000 [x 10msec] 

□14 Brake OFF control delay time 

In case the motor has an inner brake, this parameter sets brake release delay time.

Setting range : 0 ~ 1000 [x 10msec]

□15 Brake ON delay time 

In case the motor has an inner brake, this parameter sets the time it takes for braking. 

Set the value higher than actual time it takes for braking. 

 

Setting range : 0 ~ 1000 [x 10msec] 

□16 ~ □17 Reserved 

 

□18 Positioning complete range 

At position control, this parameter sets the positioning completion range. If the deviation between

the targeted position and the current position is within the setting range, the VPF terminal (no. 16 

of the CN1 connector) will be turned ON. The numerical value unit means the encoder pulse and it

is 8192 pulse per rotation of the motor.

19 Remaining pulse allowable range 

In position control, in each position control loop the difference between position command 

and position feedback is accumulated. If this difference value exceeds the setting value, the

position deviation excess alarm will be occurred. The numerical value unit means the encoder

pulse and presently it is 8192 pulse per 1 rotation.

Setting range : 1 ~ 6000 [x 100pulse] 

□20 Deceleration time after stop signal 

This parameter sets the deceleration time from rotation state until the motor stops. When the

setting value is 0 as default, the motor under 3kW capacity will be stopped as 100 msec

deceleration time. And the motor more than 3kW will be stopped as 340 msec. 

Setting range : 0 ~ 5000 [msec]

 

□21 S-shaped acceleration/deceleration time constant 

This parameter sets the time constant to reduce the impact at the time of acceleration or

deceleration.

Total acceleration time : acceleration time(parameter 29) + S-shaped acceleration/deceleration

time constant

Total deceleration time : deceleration time(parameter 30) + S-shaped acceleration/deceleration

time constant

Setting range : 0 ~ 400 [msec]

□22 Positive torque limit 1 

This parameter limits the torque output of the positive (+) polarity in areas except of positioning

complete range. If the value is set at 0%, positive torque will not occur. If the value is set too low,

hunting may occur when the motor starts or stops.

 

Setting range : 0 ~ 300 [%] 

□23 Negative torque limit 1 

This parameter limits the torque output of the negative (-) polarity in areas except of positioning 

complete range. If the value is set at 0%, negative torque will not occur. If the value is set too low,

hunting may occur when the motor starts or stops.

 

Setting range : 0 ~ 300 [%]

 

□24 Positive torque limit 2 

This parameter limits the torque output of the positive (+) polarity in areas within positioning

complete range. In purpose of applying continuous load with ON state of SVON signal after

positioning completion, the overstrain on the equipment or the motor can be avoided by setting a

low value.

25 Negative torque limit 2 

This parameter limits the torque output of the negative (-) polarity in areas within positioning

complete range. In purpose of applying continuous load with ON state of SVON signal after

positioning completion, the overstrain on the equipment or the motor can be avoided by setting a

low value.

Setting range : 0 ~ 300 [%] 

□26 Speed limit 

This parameter limits the maximum rotation speed. Even when overshooting and such cases occur

while accelerating, the rotation speed will be limited within the setting value. Set the value at least 

50rpm more than the setting value of parameter 28(rotation speed).

 

Setting range : 0 ~ 3000 [rpm] 

□27 Jog speed at origin setting 

This parameter sets the motor speed of the internal jog operation.(At Magazine, the speed of the

jog operation will be applied as the setting speed of parameter 28.) 

Setting range : 1 ~ 3000 [rpm]

□28 Operation speed

This parameter sets the motor rotation speed for automatic operation or jog operation speed of the

Magazine.

Setting range : 10 ~ 3000 [rpm]

□29 Acceleration time

This parameter sets the time that takes to get to the setting speed of parameter 28 from 0 speed.

If the value is set too low, speed overshooting may occur when accelerating.

Setting range : 0 ~ 9999 [msec]

□30 Deceleration time

This parameter sets the time that takes to get to 0 speed from the setting speed of parameter 28.

If the value is set too low, positioning completion time may be delayed due to hunting when the

motor stops.

Setting range : 0 ~ 9999 [msec]

□31 Teaching function 

To use the Teaching function, set this parameter as 1. It’s possible to set the movement distance

unequally unlike existing gear ratio setting method.

3000 : gear ratio setting method

1 : Teaching function enabled

□32 High torque IPM motor selection 

If the high torque IPM motor is applied, set the value of this parameter as 1. 

 

1500 : Normal SPM motor 

1 : High torque IPM motor

 

□33 Initial state display 

This parameter sets the initial display mode just after the power is ON. 

Set value Initial display contents Set value Initial display contents

00 Motor rotation speed 06 Accumulated value of remaining pulse

01 Current POST number 07 Reserved

02 Absolute encoder rotation count 08 Reserved

03 Absolute encoder-one rotation 09 Alarm display

04 Effective load factor 10 Motor rotation speed

05 Maximum load factor

□34 ~ □44 Automatic setting parameters or maker parameters for management 

These parameters are maker parameters for management or will be set automatically while setting

the machine origin-point.

Please do not set according to the user’s purpose. It may cause malfunction of the servo drive.

□45 Servo drive function selection

Please set this parameter first before parameter initialization or parameter setting, because this

parameter sets the servo drive function as Turret/Magazine or ATC.

Set value Function

0 Turret/Magazine

1 ATC

※ For normal operation of the servo drive, the drive power must be turned OFF and ON again,

after setting parameter 45.

□46 Option function 

This parameter sets up OVERRIDE, selective application of offset and 255 TOOL function. 

For use the OVERRIDE function OVR0, OVR1, OVR2 and OVR3 contact points must be connected

between the drive and the NC, and the NC program should support this feature.

For use the function of selective application of offset value, OVR0 and AUX_OUT0 contact points

must be connected between the drive and the NC, and the NC program should support this feature.

For use of 255 TOOL function, OVR0 and AUX_OUT0 contact points must be connected between

the drive and the NC, and the NC program should support this feature.

0 : Option function disabled

1 : OVERRIDE function enabled

2 : Selective application of offset value

3 : 255 TOOL function enabled

51 Tool number decrease direction Backlash

This parameter sets the Backlash compensation value for tool number decrease direction. If this

parameter is set as 0, Backlash compensation value is not applied. The numerical value unit means

the encoder pulse and presently it is 8192 pulse per 1 rotation.

Please refer to ‘Example of tool number increase direction Backlash compensation value setting’

for more detailed setting method.

Setting range : 0 ~ 9999[PULSE]

□52 Speed Command Filter

This parameter sets Speed Command Filter value. If this parameter is set as 0, Speed Command

Filter value is not applied.

Setting range : 0 ~ 9999[Hz]

□53 Speed Feedback Filter

This parameter sets Speed Feedback Filter value. If this parameter is set as 0, Speed Feedback

Filter value is not applied.

Setting range : 0 ~ 9999[Hz]

□54 Current Command Filter

This parameter sets Current Command Filter value. If this parameter is set as 0, Current Command

Filter value is not applied.

Setting range : 0 ~ 9999[Hz]

□55 Current Feedback Filter

This parameter sets Current Feedback Filter value. If this parameter is set as 0, Current Feedback

Filter value is not applied.

Setting range : 0 ~ 9999[Hz]

□56 Position Signal Output Function

Set this parameter as 1 to use position signal output function. Use this function when it needs to

output the position signal using the existing tool number output contact point at the specific

position(angle) that is set by user. And this function is available only if the NC is ready for this

feature.

0 : disabled 

1 : Position signal output function enabled


  • UniOP CP04F-04-0045 Human Machine Interface
  • UniOP eTOP308 ETOP308U301 HMI Panel
  • UniOP MD00R-02-0045 Ultra-Compact Industrial Operator Terminal
  • UniOP ePALM10-0061 Handheld Robot Trainer
  • ​UniOP CP05R-04-0045 High-Value Character Operator Terminal
  • UniOP CP01R-04. CP05R-04 and CP01F-02
  • Uniop MD02R-04 - MD02R-04-0045 Industrial PLC Workstation
  • Uniop Cp02r-04-0021 Operating Interface
  • UniOP CP04F-04-1945 Rugged VFD Operator Interface
  • UniOP ECT-16-0045 High-Performance Color Touchscreen HMI
  • UniOP ERT-16-0042 High-Durability Industrial Operator Interface
  • UniOP ePAD04-0046 Compact Industrial Interface
  • UniOP BKDR-16 High-Reliability Monochrome Operator Interface
  • UniOP MKDR-04-004 Control Unit Panel
  • UniOP eTOP515 Series 500 HMI
  • Woodward 8200-1300 High-Precision 505D Steam Turbine Controller
  • ABB PFSK138 3BSE016323R3 High-Performance Digital Board Connection Unit
  • ABB PFSK163 3BSE000435R1 High-Performance Interface Module
  • UniOP ETT-VGA Human-Machine Interface (HMI) terminal
  • ABB PFSK165 3BSE027778R1 VP74201-933CW07 Signal Processing and Communication Unit
  • ABB PFSK164 3BSE021180R1 Tension sensor module and processing board
  • ABB 3BSE006505R1 PFSK 142 Control board
  • ABB PFSK160A 3BSE009514R1 Regulated High-Capacity 24V DC
  • ABB PFSK162 3BSE015088R1 High-performance signal conditioning and processing board
  • ABB PFSK152 3BSE018877R1 Signal concentrator board
  • ALSTOM PIB1201A 3BEC0067 Power Interface Board (PIB)
  • ALSTOM PIB310 3BHB0190 Adapter Module / Printed Circuit Board (PCB)
  • ALSTOM PIB102A 3BEB0180 Communication Card / PCB Module
  • ALSTOM BGTR8HE 24491276A1004 High-Frequency Power Controller / Rack Module
  • ALSTOM AM164 Analog Output / Remote I/O
  • ALSTOM UT150-1 PID temperature controller / process control board
  • ALSTOM AL132 AL132A STO0982E01 Control Motherboard / CPU Card
  • ALSTOM AS111-1 Analog Output (AO) Module
  • ALSTOM AH116-2 Servo Drive / Control Module
  • ALSTOM V4555724-0100 Electromechanical Contactor /Power Switch
  • WATLOW 999D,999A Digital/Analog Dual-Channel Base Unit
  • WATLOW 998D 998A Digital/Analog Dual-Channel Base Unit
  • WATLOW 999D-11FF-AARG Dual-channel digital unit with universal process outputs
  • WATLOW Wattlo 998D-22KK-ARRG is a high-performance dual-channel digital controller.
  • WATLOW 996A Single-loop controller
  • WATLOW 996D-11CC-CUGR Single-loop digital controller
  • WATLOW 996D Single-Channel Digital Temperature/Process Controller
  • WATLOW 997D Digital Dual-Channel Base Unit
  • WATLOW 997A Analog Dual-Channel Variant
  • WATLOW DAC / SDAC,Digital-to-Analog / Serial-to-Analog Modules
  • WATLOW MLS300-OIT Operator Interface Terminal (Keypad/Display),Discontinued
  • WATLOW CIM300 Communication Interface Module (EIA-232/485),Discontinued
  • WATLOW MLS300-CIM Control Interface Module (Comm Bridge),Discontinued
  • WATLOW MLS300-AIM,Analog Input Module (16-channel expansion),Discontinued
  • WATLOW MLS300-PM Processor Module (Central CPU),Discontinued
  • Watlow MLS332 32-Loop Processor Base Unit,Discontinued
  • Watlow MLS316 Multi-loop thermal controller
  • Watlow CLS208 C10000CP high-performance, 8-loop PID temperature controller
  • Watlow CAS 16CLS/CAS Multi-loop temperature controller
  • HIMA K9212 Module Overview
  • ABB CP555 1SBP260179R1001 Product Overview
  • Watlow MLS300 Multi-Loop Control System
  • Watlow 997D-11CC-JURG SERIES 997 Vertical Limit Control
  • Watlow CLS216 | Multi-Loop PID Temperature Controller
  • Watlow NLS300-CIM316 Multi-Loop Control Interface Module
  • Watlow PPC-TB50 (30280-00) Precision Power Controller
  • ABB PPD113-B03-23-111615 high-performance Processor / Controller Module
  • ABB MB510 3BSE002540R1 Control System Accessory
  • ABB 3BSE000863R1 SR511 Power Supply
  • ABB 3BSE014227R1 RF533 Central Unit
  • ABB PDD500A101 high-performance Drive Board / Processor Module
  • ABB PPD512A10-150000 high-performance Controller/Processor Module
  • ABB 500BIO01 1MRB150005R0001 1MRB200060/E Binary Input/Output (Combined)
  • ABB 500BIM01-1MRB160024R0002 Binary (Digital) Input Module
  • ABB 500PSM03 1MRB150038R1 894-030375D 136-011100H Power Supply Module
  • ABB 500PSM02 1MRB150015R1 AD-272.100.20-01 AZ:C Power Supply Module
  • ABB 500AIM02 1MRB150022R001 1HDF 930412 X010 Analog Input Module (AIM)
  • ABB 500MTM02 1MRB150020R0712 1HDF 930512 X010 Multivariable Transmitter Module
  • ABB 500SCM01 1MRB150004R0001 1MRB200059/C Signal Regulation and Monitoring Module
  • ABB 500TRM02 1MRB150011R0001 Terminal/Input-Output Board
  • ABB 500CPU03 1HDF700003R5122 Central Processing Unit module
  • ABB 500PB101 1MRB178009R0001 1MRB200064/C Communication Module
  • ABB 500CSP04 HE401314/0002 1MRB150051R2 Control and System Processing Module
  • ABB 500CMP04 HE401314/0001 1MRB150051R1 Communication motherboard
  • ABB 500TTM02 1MB150021R01161HF930712X010 Temperature / Logic Interface Module
  • ABB DSAO110 57120001-AT/1 Analog Output 4 Channels
  • ABB UNS4684A-P,V.1 HIEE305114R00R0001 Overvoltage protection (OVP) and pulse coupling panel (PCP) module
  • ABB PVD164A2059 3BHE014340R2059 high-performance Excitation Processor Module
  • ABB PFCL201CE 10KN 3BSX105983-100 Pressductor® Curved Plate Force Sensor
  • ABB 500SCM01 1MRB200059/C 1MRB15004R0001 Control Module
  • ABB 500CPU05 1MRB150081R1/E Central Processing Unit module
  • ABB 500CIM05 1MRB150077R1/B Communication Interface Module
  • ABB 500BIO01 1MRB150005R1/J high-performance Binary Input/Output (BIO) module
  • Metso D201379L ACN RT Controller / Processor
  • Metso D201505 (ACN C20 Controller)
  • Metso D201463 high-performance Network Controller / Processor Module
  • Metso D201505R (ACN C20 Series)
  • Metso D201380 CPU / Processor Module
  • Metso D202275 ACN Communication / Gateway Node
  • Metso D201376 ACN RT (Real-Time) Controller Node
  • METSO D200175 Application Control Node (ACN) Proc
  • METSO D200137 high-performance controller module
  • METSO IOP111 Analog Input Module
  • METSO IOP353 Digital Output Module
  • METSO IOP304 high-performance Thermocouple (TC) / Millivolt (mV) Input Module
  • METSO PDP601 high-performance Distributed Processing Unit
  • METSO IOP345 Digital Input/Output Module
  • METSO DPU-MR high-performance Distributed Processing Unit
  • METSO IOP114 high-precision Analog Input Module
  • METSO IOT300A Terminal substrate / Interface module
  • Metso R/I-TB 9139041 nput/output (I/O) interface module
  • YOKOGAWA YS1700-100/A06/A31 Programmable Logic Controller
  • YOKOGAWA PW482-10 AC Input Power Module
  • YOKOGAWA SCP451-11 CPU
  • YOKOGAWA SR1030B62 high-precision Power Supply Unit (PSU)
  • YOKOGAWA AAI143-H50 high-density Analog Input Module
  • YOKOGAWA AMM42 high-density Analog Input/Output Module
  • YOKOGAWA SDV144-S63 Digital input module
  • YOKOGAWA AIP830-111 Operating keyboard
  • YOKOGAWA S9361DH-00 High-performance terminal board module
  • YOKOGAWA ATK4A-00 S1 Terminal block adapter
  • YOKOGAWA PW701 Power Supply Module
  • YOKOGAWA AVR10D-A22010 Bus Converter
  • YOKOGAWA PROFIBUS-DP communication module
  • YOKOGAWA AIP578 AIP591 Optical link transceiver module
  • YOKOGAWA PW501 Power module
  • YOKOGAWA YNT511D ER Bus Terminator
  • YOKOGAWA AIP171 Vnet/IP-V net Coupler Unit
  • YOKOGAWA VI702 high-speed Vnet/IP Interface Module
  • YOKOGAWA Models 4370 µR1800 Recorder
  • YOKOGAWA ANR10D communicates the analog I/O signals and contact I/O
  • YOKOGAWA SDV144-S13 Digital Input Module
  • YOKOGAWA NFAI143-H00 Simulation Input Module