FOXBORO FBM227 P0927AC Module
OVERVIEW
The FBM227 module provides signal conversion
required to interface analog and digital electrical
input/output signals from field sensors/actuators. It
has four 0 to 10 V DC analog input channels and two
0 to 10 V DC analog output channels, all of which are
individually isolated. For the digital I/O signals (on/off
state), it has four digital input channels, isolated in
two groups of two channels each, and four digital,
pair isolated, output channels.
It executes either the Analog I/O or Digital I/O
application program, and has support for MDACT or
DPIDA control.
The configurable options for each analog program
are Input Resolution, Fail-safe Configuration
(Hold/Fallback) and Output Fail-safe Fallback Data.
The configurable options for each digital program are
Input Filter Time, Fail-safe Configuration, Fail-safe Fall
Back and Sustained or Momentary Outputs.
If the Momentary Output configuration is selected,
then Pulse Output Interval is also configurable.
Configurable options for inputs are exercised on a
per module basis; those for outputs are exercised on
a per channel basis.
FEATURES
Key features of the FBM227 module are:
Four 0-10 V analog input channels, used for
either DC voltage measuring, or slidewire
(position) sensing
Two 0-10 V analog output channels, used for
driving positioners, controllers or remote
indicators
Four 130 V DC digital input channels, used for
either contact sensing, or DC voltage monitoring
Four digital output channels, used for either
60 V DC output switching with an external source
(e.g. to control powering of various external
loads), or a 3-wire DC output switching with an
internal 11 V DC source (e.g. to power external
solid state relays or other similar devices)
Support for DPIDA and MDACT control blocks
Each pair of analog input or output channels is
individually isolated from other channels and
earth (ground). Its digital channels have paired
isolation from all other channels and earth
(ground)
Rugged design suitable for enclosure in Class G3
(harsh) environments.
STANDARD DESIGN
The FBM227 module has a rugged extruded
aluminum exterior for physical protection of the
circuits. Enclosures specially designed for mounting
the FBMs provide various levels of environmental
protection, up to harsh environments per ISA
Standard S71.04.
EASY REMOVAL/REPLACEMENT
The modules can be removed/replaced without
removing field device termination cabling, power or
communications cabling.
VISUAL INDICATORS
Light-emitting diodes (LEDs) incorporated into the
front of the modules provide visual status indications
of Fieldbus Module (FBM) functions.
MODULAR BASEPLATE MOUNTING
The modules mount on a modular baseplate or
conversion mounting structure which accommodates
up to four or eight FBMs. The modular baseplate is
either DIN rail mounted or rack mounted, and
includes signal connectors for redundant fieldbus,
redundant independent DC power, and termination
cables.
FIELDBUS COMMUNICATION
A Fieldbus Communication Module or a Control
Processor communications with the FBM227 over
the redundant 2 Mbps module Fieldbus used by the
FBMs. The FBM227 module accepts communication
from either path (A or B) of the redundant 2 Mbps
fieldbus – should one path fail or be switched off at
the system level, the module continues
communication over the active path.
TERMINATION ASSEMBLIES
Field I/O signals connect to the FBM subsystem via
DIN rail mounted TAs. The TAs used with the
FBM227 modules are described in “TERMINATION
ASSEMBLIES AND CABLES” on page 8.

| User name | Member Level | Quantity | Specification | Purchase Date |
|---|