e300 32 Bit RISC based PowerPC Architecture. The
controller operates out of a battery-backed DDR2 64MB
memory for C30 and C50 modules, 128MB for C70 and
C75 modules. DDR2 memory on all modules is
supported with ECC circuitry to enhance reliability and
error detection.
Program execution environment is protected using an
independent watchdog timer.
• All ControlEdge HC900 CPU modules offer open Ethernet
communications for access by a variety of HMI and
SCADA software applications and peer to peer
communications for control data exchanges between
controllers. The C70 and C75 provide dual Ethernet ports
for high network availability installations.
• ControlEdge HC900 CPU modules use a dual scan
method to handle fast digital scanning and normal analog
input scanning in the same integrated control
environment. Both scans support a wide range of
computational function block algorithms and a user
adjustable execution sequence order.
ControlEdge HC900 CPUs use Flash memory for
permanent user configuration program storage
and battery-backed memory for dynamic data
storage allowing for graceful recovery following a
power interruption or other discontinuous
operations. Using proven TL5903 primary
batteries to support up to 24 days of continuous
power outages
• 5000 SOE event buffering capability
I/O Scanners
ControlEdge HC900 Remote I/O is processed and
communicated to the main CPU module through a
remote I/O Scanner module. Two I/O scanner modules
are available: a single port model for non-redundant
CPU systems and a dual port model for redundant
CPU systems. Scanner addressing in multi-rack
systems is selectable via DIP switch setting.
Program execution environment is protected using an
independent watchdog timer.
Inputs and Outputs - A variety of I/O modules are
available for selection in creating a custom control
solution. These include:
• 8-point universal analog input modules: Inputs
may be mixed on a module and may include
multiple thermocouple types, RTDs, ohms,
voltage, current or millivoltage types – all easily
assigned using the Designer configuration tool.
High point-to-point isolation simplifies installation
and saves the expense of external isolation
hardware.
• 16-point high level analog input module: each
point is configurable for V or mA. Point-to-point
isolation.
• 4-point galvanically isolated analog output
module: Supports from 0 to 20mA each.
• 8-point analog output module. Galvanically
isolated in two groups of 4. Supports 0 to 20mA.
• 16-point (14-point for redundant configuration)
Universal I/O module galvanically isolated Input/
Output to chassis. Each point can configured as
DI, DO, AI or AO.
• 16-point digital galvanically isolated AC/DC input
module.
• 16-point analog output module. Galvanically isolated in
four groups of 4. Supports 0 to 20mA.
• 16-point digital galvanically isolated input modules:
Contact closure type, DC voltage and AC voltage types.
• 32-point galvanically isolated digital input (sink) module:
DC voltage
• 8-point AC or 16 point galvanically isolated DC digital
output (sink) modules
• 32-point galvanically isolated digital output (source): DC
voltage
• 8-point galvanically isolated high voltage
• 8-point galvanically isolated relay output module: four
form C type and four forms A type relays.
• 4 channel Pulse/ Frequency/Quadrature I/O module
See Module Specifucation sheet 51-52-03-41 for details.
Insert & removal of I/O under power - For ease of
maintenance, the ControlEdge HC900 controller supports
removing and inserting modules from the card rack without
removing power from the controller. Each card is sensed for
validity by the controller and auto-configured on insertion.
Hardware can be replaced without shutting down operations
for replacement of CPU or Scanner modules thus reducing
downtime and total cost of ownership.
I/O Terminal Blocks – 20-screw Terminal Blocks
are available with either barrier style or Euro style screw
connections. A module label area is provided for field wiring
identification. An available 36-screw Euro Terminal block is
required for certain high capacity modules.
Remote I/O - I/O racks may be remotely mounted
from the controller via a dedicated Ethernet 10/100Base-T
connection at up to 300 meters (984 feet) between the
controller and the most remote rack using two Ethernet
switches. Use of fiber optic cable extends distance to 40
Kilometers.
Remote Terminal Panels - Optional DIN rail mounted
Remote Terminal Panels (RTPs) are available for use
with pre-wired cables to reduce installation time and
labor expense. RTP types available: analog input,
relay output, discrete input, discrete output, analog
output.
Three cable lengths are also available to match
hardware to installation variations. See Module
Specification sheet 51-52-03-41 for more details.