Phoenix QUINT-PS/1AC/24DC/40 2866789 Power supply
Phoenix QUINT-PS/1AC/24DC/40 2866789 Power supply
QUINT-PS/1AC/24DC/40 - Power supply
2866789
Primary-switched power supply unit QUINT POWER, Screw connection, DIN rail mounting,
SFB Technology (Selective Fuse Breaking), input: 1-phase, output: 24 V DC / 40 A, adjustable from 18 V DC ... 29.5 V DC, 90 V DC ... 300 V DC
QUINT POWER power supplies with maximum functionality
QUINT POWER circuit breakers magnetically and therefore quickly trip at six times the nominal current, for selective and therefore cost-effective system protection.
The high level of system availability is additionally ensured, thanks to preventive function monitoring, as it reports critical operating states before errors occur.
Reliable starting of heavy loads takes place via the static power reserve POWER BOOST. Thanks to the adjustable voltage, all ranges between 5 V DC ... 56 V DC are covered.
Item number 2866789
Packing unit 1 pc
Minimum order quantity 1 pc
Sales key CM11
Product key CMPQ13
GTIN 4046356421720
Weight per piece (including packing) 3.820 g
Weight per piece (excluding packing) 3.439 g
Customs tariff number 85044095
Country of origin TH
Nominal input voltage range 100 V AC ... 240 V AC
Input voltage range 85 V AC ... 264 V AC
Derating < 100 V AC (1 %/V)
Input voltage range AC 85 V AC ... 264 V AC
Input voltage range DC 90 V DC ... 300 V DC (UL 508: ≤ 250 V DC)
Electric strength, max. 300 V AC
Voltage type of supply voltage AC
Inrush current < 15 A (typical)
Inrush current integral (I2t) < 1.7 A2s
AC frequency range 45 Hz ... 65 Hz
Frequency range DC 0 Hz
Mains buffering time > 35 ms (120 V AC)
> 35 ms (230 V AC)
Current consumption 8.8 A (120 V AC)
4.6 A (230 V AC)
9.5 A (110 V DC)
4.7 A (220 V DC)
Nominal power consumption 1157 VA
Protective circuit Transient surge protection; Varistor, gas-filled surge arrester
Power factor (cos phi) 0.88
Typical response time < 0.7 s
Input fuse 20 A (slow-blow, internal)
Permissible backup fuse B16 B25 AC:
Permissible DC backup fuse DC: Connect a suitable fuse upstream
Recommended breaker for input protection 16 A ... 20 A (AC: Characteristics B, C, D, K)
Discharge current to PE < 3.5 mA
Number of phases 1
Insulation voltage input/output 4 kV AC (type test)
2 kV AC (routine test)
Insulation voltage output / PE 500 V DC (routine test)
Insulation voltage input / PE 3.5 kV AC (type test)
2 kV AC (routine test)
Product family QUINT POWER
MTBF (IEC 61709. SN 29500) > 900000 h (25 °C)
> 530000 h (40 °C)
> 240000 h (60 °C)