Honeywell TDC‑3000 BASIC,XLCNE2 LCN Extender,51305508‑100.Coaxial LCN
TDC‑3000 BASIC,XLCNE2 LCN Extender,51305508‑100.Coaxial LCN
EPDGP I/O boards (see Figures 2-10 and 2-11) interface nearly all the peripherals of the
Enhanced Micro TDC3000 Control System. You are now going to connect those cables
which could not be installed at the factory
The EPDGC I/O is the EMC Directive board version used to interface with the monitor,
keyboard, touchscreen, SCSI cartridge drives and printers. The EMC Directive version is
shown in Figures 2-12 and 2-13. All the connectors have been converted to D-type
connectors with full 360 degree shielding. The connectors are bulkhead mounted into the
board face plate which provides a contiguous shield from module to cable. The cabling of
peripheral devices are connected at this face plate. The Touchscreen and Trackball cables
are connected to the cabinet bulkhead shown in Figure 2-7.

The background color of the monitor can be selected as one of four colors as shown in
Figure 2-13. The pinning shown is for the default background color. Pin the board for
desired background color. The pinned background color selection is only in force until the
station is loaded with software.
The sync pulse requirements of the monitor used is pinned at J6 (factory set) as shown in
Figure 2-13. The pinning of J6 will determine the tab number of the board and is factory
set. The monitor sync pulse source will either be direct (Tab 100) or inverted (Tab 200)
Operator Keyboard Cabling
Connect the keyboard cable to the connector on the face plate of the EPDGC I/O board (see
Figure 2-11). Use a small screwdriver to tighten the screws (2) on the connector.
2.7.6 Printer Cabling
The printer cable (51303631-003) has similar connectors on each end.
1. Connect the end of the cable marked PIC to the connector on the face plate of the
EPDGC I/O board marked PRINTER in Figure 2-11. Use a small screwdriver to tighten
the screws (2) on the connector.
2. Connect the other end of the printer cable (marked PRINTER) to the back of the printer.
Using a small screwdriver, tighten the screws (2) on the connector.
2.7.7 Color Monitor Cabling
Connect the cable from the color monitor to the EPDGC I/O face plate connector marked
VIDEO in Figure 2-11. on the upper transition panel. Using a small screwdriver, tighten
the screws (2) on the connector. Finally, attach the power cord to the monitor and plug it
in.
| ABB | REF601CE446BB1NH 24-240V 50/60Hz |
| ABB | UFC765AE102 3BHE00364R0102 |
| bently | 3500/60 |
| PROCONTROL P | GJR2395500R1210 83SR50 |
| PROCONTROL P | 5102-MCM4-DFCM4 |
| ABB | 81943A059-1 |
| ABB | 81943A059-2 |
| ABB | A419471 |
| ABB | AINT-14C |
| bently | 3500/92-02-01-01 |
| bently | 3500/32-01-01 |
| bently | 3500/33-01-01 |
| bently | 3500/25-01-01-00 |
| bently | 3500/40M-01-01 |
| bently | 3500/22M-01-02-01 |
| Meggitt | CA202 – 144-202-000-203 |
| Meggitt | TQ402 – 111-402-000-012 |
| bently | 3500/92-02-01-01 |
| bently | 3500/32-01-01 |
| bently | 3500/33-01-01 |
| bently | 3500/25-01-01-00 |
| bently | 3500/40M-01-01 |
| bently | 3500/22M-01-02-01 |
| bently | 26530-12-10-02-018-038-22-04-00 |
| bently | 3500/15-05-05-01 106M1079-01 +106M1081-01 |
2.7.8 Engineer’s Keyboard Cabling
Insert the plug on the cable from the engineer’s keyboard into the small connector located
on the right of the operator keyboard. Note the plug will only fit one way.
2.7.9 TPLCN Cabling
The two (2) TPLCN cables (51304505-100) have similar connectors on each end. The
standard cable length is 5 feet (1.5 meters). The optional cable (Option number
MX-MTLC11) is 33 feet (10 meters) long, allowing a maximum distance between towers
of 10 meters. The cable set connects directly to the TP-485 board face plates in the towers.
1. Attach one cable plug to the TP-485 face plate connector marked BUS A and the other
cable plug to BUS B at the rear of Tower #1. Using a small screwdriver, tighten the
screws (2) on the connectors.
2. Attach the other end of the cable to the TP-485 face plate connector marked BUS A and
the other cable plug to BUS B at the rear of Tower #2. Use a small screwdriver to
tighten the screws (2) on the connectors.
3. Attach the ground wires to the small screws, if they are on your cable
| User name | Member Level | Quantity | Specification | Purchase Date |
|---|