Honeywell TDC‑3000 BASIC,CG Computer Gateway,80360206‑001
TDC‑3000 BASIC,CG Computer Gateway,80360206‑001
International models (240 Vac) of the Enhanced Micro TDC3000 Control System are
equipped with 1.8 meter (6foot) power cords having CEE-7 standard VII dual earthing
plugs. Likewise, there must be four (or more) CEE-7 standard VII dual earthing electrical
outlets provided, all tied to the same ground.
2.2.1 Dimensions and Weight
These are the approximate dimensions and weight for each electronics tower, color
monitor, UCN cabinet (APM) and printer:
Electronics Tower (each) Advanced Process Manager
(Dual-Access)
Height 72 cm (28.3") Height 210 cm (81.5”)
Width 32 cm (12.6") Width 80 cm (31.5”)
Depth 58 cm (22.8") Depth 80 cm (31.5)”
Weight 45 kg (99.2 lb) Weight 200kg (440 lb)
Printer (ASPI-41) Color Monitor (20”)
Height 17 cm (6.7") Height 44.9 cm (17.7")
Width 62 cm (24.4") Width 49.8 cm (19.6")
Depth 31 cm (12.2") Depth 53.4 cm (21.0")
Weight 14 kg (30.8 lb) Weight 29 kg (63.9 lb)
IDEK Color Monitor (21”) HITACHI Color Monitor (21”)
Height 47.1 cm (18.5") Height 47 cm (19.7")
Width 49.2 cm (19.4") Width 50 cm (18.5")
Depth 53.6 cm (21.1") Depth 51 cm (20.1")
Weight 33 kg (72.7 lb) Weight 34 kg (74.9 lb)
For Advanced Process Manager dimensions and weight, consult Process Manager
/Advanced Process Manager Planning, part of the System Site Planning - 1 binder.
2.3 ELECTRICAL REQUIREMENTS
The customer selected ac power option is installed in the Enhanced Micro TDC3000
Control System before shipment.
The inrush current to each electronics module is limited to 15 A @ 120 V.
2.3.1 AC Voltage Options
120. 240 Vac +10%, -15%
2.3.2 Frequency
47 Hz to 63 Hz
| ABB | REF542PLUS 1VCF752000 |
| ABB | REF542PLUS 1VCF750168R801 |
| ABB | REF542PLUS 1VCF751021R802 |
| ABB | REF542PLUS 1VCF750170R819 |
| ABB | REF542PLUS 1VCF750090802 |
| Alstom | LC105A-1 |
| Alstom | LC106-1 |
| ABB | 23AE23 |
| BIFFI | ICON-010/90-36 |
| BIFFI | ICON-020/180-72 |
| AB | 1336-BDB-SP42D |
| GE | IC698CRE030 |
| GE | IC200MDL740 |
| GE | IC698CRE030 |
| GE | IC200MDL740 |
| GE | IC200MDL740 |
| GE | IC698CRE030 |
| GE | IC200MDL740 |
| ABB | REF542PLUS 1VCF752000 |
| UNITEC | UN/PRF100 |
| Rolls-Royce | RRWRC01;000218080 |
| ABB | 5SDF0860H0003 |
| ABB | 0746919G |
| ABB | 3HAC026271-001 |
| Siemens | 6AV2124-0QC02-0AX1 |
The dual access Advanced Process Manager cabinet is included with the Enhanced Micro
TDC3000 System and is shown for reference in Figure 2-1. Complete planning and
installation instructions for the Advanced Process Manager are given in the Process
Manager/Advanced Process Manager Planning, part of the System Site Planning - 1 binder
and Process Manager/Advanced Process Manager Installation manual, part of the
Implementation/PM/APM binder.
In the following steps, you will move relatively heavy and bulky units containing sensitive
electronic equipment. When moving a tower, we recommend you use two people to place
the tower on a low, flat, roller dolly for transfer within the building. If a hand-truck is
used, it must be well-padded and you must use care not to put excessive stress on the short
feet under the tower.

| User name | Member Level | Quantity | Specification | Purchase Date |
|---|