Woodward MFR300-11M 8444-1071 8440-1089
MFR300-11M 8444-1071 8440-1089
Overfrequency (Level 1 & 2) ANSI# 81O
General notes
This controller provides the user with two alarm levels for overfrequency. Both alarms are
definite time alarms.
Monitoring for overfrequency faults is performed in two steps.
The diagram listed below shows a frequency trend and the associated pickup times and
length of the alarms.
Underfrequency (Level 1 & 2) ANSI# 81U
General notes
This controller provides the user with two alarm levels for underfrequency. Both alarms
are definite time alarms.
Monitoring for underfrequency faults is performed in two steps
Positive Load (Level 1 & 2) ANSI# 32
General notes
The power is monitored depending on parameter "Voltage measuring" (parameter ╚═▷
1851) and parameter "Current measuring" (parameter ╚═▷ 1850)
If the single- or three-phase measured real power exceeds the configured limit, the alarm
will be issued.
Both alarm limits may either be positive or negative
ID Parameter CLSetting range
[Default]
Description
2304
2310
Limit 4-300.0 to 300.0
| HIMA | F6217 |
| HIMA | F8628X |
| HIMA | F7126 |
| HIMA | F7553 |
| HIMA | F3 AIO 8/4 01 |
| HIMA | F3 DIO 8/8 01 |
| HIMA | Z7116 |
| HIMA | Z7128 |
| HIMA | Z7138 |
| HIMA | F8652E |
| HIMA | Z7306 |
| HIMA | BV7046-4 |
| HIMA | K9202B |
| HIMA | X-FAN 18 03 |
| HIMA | F8620/11 |
| HIMA | ELOPII |
2304: [110.0 %]
2310: [120.0 %]
The percentage values that are to be
monitored for each threshold limit are defined
here.
If this value is reached or exceeded for at least
the delay time without interruption, the
specified relay will be energized.
Notes
This value refers to the "Rated active power"
(parameter ╚═▷ 1752).
2305
2311
Delay 4 0.02 to 300.00 s
2305: [11.00 s]
2311: [0.10 s]
If the monitored load exceeds the threshold
value for the delay time configured here, an
alarm will be issued.
Notes
If the monitored load falls below the threshold
(minus the hysteresis) before the delay expires
the time will be reset.
2301
2307
Relay 4 None / Relay 1 /
Relay 2 / Relay
3 / Relay 4
2301: [Relay 1]
2307: [Relay 2]
The relay configured here is activated if the
respective monitoring functions triggers. If
"None" is configured here, no relay is activated
in this case.
Notes
Whether the relay is energized or de-energized
depends on the configuration of the relay
function (parameter ╚═▷ 6920 , ╚═▷ 6921. ╚═▷
6922 and ╚═▷ 6923).
Negative Load (Level 1 & 2) ANSI# 32R/F
General notes
The power is monitored depending on parameter "Voltage measuring" (parameter ╚═▷
1851) and parameter "Current measuring" (parameter ╚═▷ 1850).
If the single- or three-phase measured real power is below the configured limit, the alarm
will be issued.
Both alarm limits may either be positive or negative