BASLER ELECTRIC BE1-25M1EA6PN5R1F / BE125M1EA6PN5R1F
BASLER ELECTRIC BE1-25M1EA6PN5R1F / BE125M1EA6PN5R1F
Surge Withstand Capability
Oscillatory
Qualified to IEEE C37.90.1-1989 Standard Surge Withstand Capability (SWC) Tests for Protective Relays
and Relay Systems (excluding communication ports).
Fast Transient
Qualified to IEEE C37.90.1-1989 Standard Surge Withstand Capability (SWC) Tests for Protective Relays
and Relay Systems (excluding communication ports). (Excluding across open output contacts due to
installed surge suppression components)
Radio Frequency Interference (RFI)
Qualified to IEEE C37.90.2-1995 Standard for Withstand Capability of Relays Systems to Radiated
Electromagnetic Interference from Transceivers.
Electrostatic Discharge (ESD)
Four kilovolts contact discharges and 8 kilovolts air discharges applied in accordance with Qualification
EN61000-4-2.
Shock
Qualification .................................................................... IEC 255-21-2. Class 1
Vibration
Qualification .................................................................... IEC 255-21-1. Class 1
Environment
Temperature
Operating Range ............................................................ –40°C to 70°C (–40°F to 158°F)
Storage Range................................................................ –40°C to 70°C (–40°F to 158°F)
∗ Display is inoperative below –20°C (–4°F)
Humidity
Qualified to IEC 68-2-38. 1st Edition 1974. Basic Environmental Test Procedures, Part 2: Test Z/AD:
Composite Temperature Humidity Cyclic Test.
CE Qualified
This product meets or exceeds the standards required for distribution in the European Community.
UL Recognition
UL recognized per Standard 508. UL File Number E97033. Note: Output contacts are not UL recognized
for voltages greater than 250 V.
CSA Certification
CSA certified per Standard CAN/CSA-C22.2 Number 14-M91. CSA File Number LR23131-140s. Note:
Output contacts are not CSA certified for voltages greater than 250 V.
DNP Certification
DNP3 IED certified, Subset Level 2. by SUBNET Solutions, Inc.
This section provides an overview of the BE1-GPS100 Generator Protection System. You should be
familiar with the concepts behind the user interfaces and BESTlogic™ before you begin reading about the
detailed BE1-GPS100 functions. Sections 3 through 6 in the instruction manual describe each function of
the BE1-GPS100 in detail.
The following information is intended to provide the reader with a basic understanding of the user
interfaces and the security features provided in the BE1-GPS100 relay. Detailed information on the
operation of the human-machine interface (HMI) can be found in Section 10. Human-Machine Interface,
and the ASCII command communications in Section 11. ASCII Command Interface. BESTCOMS™ is a
Windows® based software application that enhances communication between the PC user and the BE1
GPS100 relay. BESTCOMS for the BE1-GPS100 is provided free of charge with the BE1-GPS100.
BESTCOMS operation is very transparent, and does contain a Windows type help file for additional
operational details.
Also covered in this section is an overview of BESTlogic, which is fundamental to how each of the
protection and control functions is set-up and used in the BE1-GPS100 relay. Detailed information on
using BESTlogic to design complete protection and control schemes for the protected circuit can be found
in Section 7. BESTlogic Programmable Logic, and Section 8. Application.
Sections 3 through 6 describe each function provided in the BE1-GPS100 relay and include references to
the following items. Note that not all items are appropriate for each function.
• Human-machine interface (HMI) screens for setting the operational parameters.
• BESTCOMS for setting the operational parameters.
• BESTCOMS for setting up the BESTlogic required for functions in your protection and control
scheme.
• Outputs from the function such as alarm and BESTlogic variables or data reports.
• HMI screens for operation or interrogation of the outputs and reports provided by each function.
• ASCII commands for operation or interrogation of the outputs and reports provided by each
function.
About This Manual
The various application functions provided by this multifunction relay are divided into four categories:
input/output functions, protection and control functions, metering functions, and reporting and alarm
functions. Detailed descriptions of each individual function, setup, and use are covered in the sections as
shown in Table 2-1. Detailed information on using programmable logic to create your own protection and
control scheme is described in Section 7. BESTlogic Programmable Logic.
Table 2-1. Function Categories and Manual Sections Cross-Reference
Section Title
Input and Output Functions
Section
Protection and Control
Section 3
Metering
Section 4
Reporting and Alarms
Section 5
BESTlogic Programmable Logic
Section 6
Application
Section 7
Section 8