Basler Electric DECS-250-CN2CN 1N Digital Excitation Control System Unit
Basler Electric DECS-250 - CN2CN 1N Digital Excitation Control System Unit
output contact including OUTA. Over 20 alarm conditions are available to be monitored including user
definable logic conditions using BESTlogic.
Active alarms can be read and reset from the front panel HMI or from the communication ports. A
historical sequence of events report with time stamps lists when each alarm occurred and cleared. These
reports are available through the communication ports.
Version Report
The version of the embedded software (firmware) is available from the front panel HMI or the
communication ports. The unit serial number and style number is also available through the
communication port.
BESTlogic™ Programmable Logic
Each BE1-GPS100 protection and control function is implemented in an independent function element.
Every function block is equivalent to its single function, discrete device counterpart so it is immediately
familiar to the protection engineer. Each independent function block has all of the inputs and outputs that
the discrete component counterpart might have. Programming with BESTlogic is equivalent to choosing
the devices required by your protection and control scheme and then drawing schematic diagrams to
connect the inputs and outputs to obtain the desired operating logic.
Several preprogrammed logic schemes and a set of custom logic settings are provided. A
preprogrammed scheme can be activated by merely selecting it. Custom logic settings allow you to tailor
the relay functionality to match the needs of your operation's practices and power system requirements.
Write Access Security
Security can be defined for three distinct functional access areas: Settings, Reports, and Control. Each
access area can be assigned its own password. A global password provides access to all three functional
areas. Each of the four passwords can be unique or multiple access areas can share the same password.
A second dimension of security is provided by allowing the user to restrict access for any of the access
areas to only specific communication ports. For example, you could set up security to deny access to
control commands from the rear RS-232 port that is connected through a modem to a telephone line.
Security settings only affect write access. Read access is always available in any area through any port.
Human-Machine Interface (HMI)
Each BE1-GPS100 comes with a front panel display with five LED indicators for Power Supply Status,
Relay Trouble Alarm, Minor Alarm, Major Alarm, and Trip. The lighted, liquid crystal display (LCD) allows
the relay to replace local indication and control functions such as panel metering, alarm annunciation, and
control switches. Four scrolling pushbuttons on the front panel provide a means to navigate through the
menu tree. Edit and Reset pushbuttons provide access to change parameters and reset targets, alarms
and other registers. In Edit mode, the scrolling pushbuttons provide data entry selections. Edit mode is
indicated by an LED on the Edit pushbutton.
The LCD has automatic priority logic to govern what is being displayed on the screen so that when an
operator approaches, the information of most interest is automatically displayed without having to
navigate the menu structure. The order of priorities is:
1. Targets
2. Alarms
3. Programmable automatic scrolling list
Up to 16 screens can be defined in the programmable, automatic scroll list.
Communication
Three independent, isolated communication ports provide access to all functions in the relay. COM 0 is a
9-pin RS-232 port located on the front of the case. COM 1 is a 9-pin RS-232 port located on the back of
the case. COM 2 is a two wire RS-485 port located on the back of the case.
An ASCII command interface allows easy interaction with the relay, using standard, off the shelf
communication software. The ASCII command interface is optimized to allow automation of the relay
setting process. Settings files can be captured from the relay and edited using any software that supports
the *.txt file format. These ASCII text files can then be used to set the relay using the send text file
function of your communication software.
ASCII, Modbus™, DNP3. and Basler TNP protocols are optionally available for the RS-485
communication port. A separate instruction manual is available for each available protocol. Consult the
product bulletin or the factory for availability of these options and instruction manuals.
Primary Applications
The BE1-GPS100 Generator Protection System provides three-phase, ground, negative sequence
overcurrent, voltage, reverse power, loss of excitation, volts per hertz, and sync-check protection. It is
intended for use in any generator protection application. Its unique capabilities make it ideally suited for
applications where:
• Wide setting range, multiple setting groups, multiple coordination curves, and versatile
programmable logic is desired in one unit.
• One economical, space-saving unit provides all protection, control, metering, and local and
remote indication functions.
• Applications where a small-size relay with limited behind-panel projection facilitates modernizing
protection, metering, and control systems in existing substations is desired.
• Protection redundancy is desired by having differential relaying in an independent, protective
relaying package.
• Communication and protocol support is required.
• Drawout construction is desired.
• High accuracy across a wide frequency range is required.
• The capabilities of intelligent electronic devices (IEDs) are used to decrease relay and equipment
maintenance costs.
Model and Style Number Description
General
The BE1-GPS100 Relay electrical characteristics and operational features are defined by a combination
of letters and numbers that make up the style number. The model number, together with the style
number, describe the options included in a specific device and appear in the clear window on the front
panel and on a sticker located inside the case. Upon receipt of a relay, be sure to check the style number
against the requisition and the packing list to ensure that they agree.
Sample Style Number
Style number identification chart, Figure 1-1. defines the electrical characteristics and operational features
included in BE1-GPS100 Relays. For example, if the style number were E3N1R0U, the device would
have the following characteristics and features:
BE1-GPS100 —
(E) - 5 ampere nominal system with 5 ampere independent ground input
(U) - Three-phase voltage sensing - Not applicable - 48/125 Vac/Vdc power supply - Single ended case, normally open alarm output - ASCII communication - Battery backup for real time clock