SHINKAWA MODEL VM-5G SINGLE UNIT INSTRUMENT RACK
MODEL VM-5G SINGLE UNIT
INSTRUMENT RACK
BEZEL
(OPTION)
Required(couple)
Not required
POWER OUTPUT FOR
TRANSDUCER
+24VDC, 4mA (input code:1) -24VDC,20mA (input code:2)
1CH : -24VDC, 40mA 2CH : -24VDC, 20mA (input code:3)
1CH : -24VDC, 20mA 2CH : +24VDC, 4mA (input code:4)
OTHERS
Power supply voltage specification 0 and 2:Does not conform to CE.
Conform to RoHS directive.
Power supply voltage specification 1 :Conform to CE.
ote) This code is applicable only to Model VM-5G.
Note) *1 2-wire transducer requiring a constant current power supply
(+24VDC, 4mA).
*2 3-wire transducer requiring a -24VDC power supply,
or any other transducer that does not cause power to be
supplied from the monitor to the transducer.
*3 The product that the power supply voltage specification
is 0 or 2 does not conform to CE.
EXTERNAL CONTACT
INPUT
(FROM REAR PANEL)
Contact for alarm reset (normally open)
Contact for sequence (normally open)
Contact type : Dry contact
INSULATION
RESISTANCE
Between power supply and GND : 100M or more at 500VDC
Between GND and alarm contact : 100M or more at 500VDC
DIELECTRIC STRENGTH Between power supply and GND : 1500VAC, one minute
POWER
CONSUMPTION
VM-5G0 : 40VA or less
VM-5G1 : 30W or less
VM-5G2 : 40W or less
TEMPERATURE
RANGE
Operating temperature : 0 to 65°C (32 to 149°F)
Storage temperature : -30 to +85°C (-22 to +185°F)
Relative humidity : 20 to 95% (noncondensing)
RELAY POINTS 5 points(DANGER1,ALERT1,DANGER2,ALERT2,OK)
CONTACT RATING
(LOAD RESISTANCE)
250VAC,0.2A 30VDC,2A
MATERIAL AND FINISH Rack : SPCC Munsell N-2.0 (equiv.)
Rear plate : SPCC Unichromate plating finish (black)
Bezel : Aluminum Munsell N-1.0 (equiv.)
CONTACT LIFE 100,000 times or more(rated load)
CONTACT METHOD SPDT(DAN.1,DAN.2,ALE.1,ALE.2,OK)5 points relay
PROTECTIVE
CONSTRUCTION
Plastic sealed
MASS Rack : max.1.8kg
Bezel : max.0.2kg
Alarm contact operation
Monitor alarm relay mode Monitor power OFF Monitor power ON
Normal state Alarm state
NO contact NORMALLY DE-ENERGIZED OPEN OPEN CLOSE
NO contact NORMALLY ENERGIZED OPEN CLOSE OPEN
NC contact NORMALLY DE-ENERGIZED CLOSE CLOSE OPEN
NC contact NORMALLY ENERGIZED CLOSE OPEN CLOSE
Note) ・Ventilation holes are drilled through the top, bottom and side faces of the instrument rack for natural
cooling. When mounting the instrument rack within the panel, do not close these ventilation holes. If closed,
the temperature in the rack may rise to shorten the service life of electronic parts used.
・Do not place anything which interrupts ventilation within 200 mm from top and bottom faces of the instrument
rack.
・When multiple VM-5G racks are installed in a row, the temperature of them may increase considerably.
It is recommended to use intermediate bezels (VZ-56-2) to keep them 10mm or more apart from each other.
・Do not place the apparatus which generates heat under the instrument rack.
・Be careful when installing the instrument rack in a bad-ventilated closed box (instrument panel).
・It may cause shortening the life time of electronic parts because of marked rising in temperature of the
instrument rack in a bad-ventilated closed box which keeps the heat in.
Cool down inside the box with a cooling fan or the like.
Especially when installing in a small closed box, use the forced-air cooling apparatus like an electronic air
conditioner.
・CE means conformity with EC directive for only the rack, but not for all the units which are
installed in the rack, nor for the whole system.