DCS; Industrial control system
NameDescriptionContent
NEW CENTER
Current Location:

ABBAutomatic Transfer Switch

From:ABB | Author:LIAO | Time :2025-07-28 | 229 Browse: | Share:

1. Symbols & Terms

1.1 Use of symbols

Risk of Electric shock: warns about a situation where a hazardous voltage may cause physical injury to a person or damage to equipment. General warning: warns about a situation where something other than electrical equipment may cause physical injury to a person or damage to equipment. Caution: provides important information or warns about a situation that may have a detrimental effect on equipment. Information: provides important information about the equipment


1.2 Explanations of abreviations and terms


OTM_C21D           Automatic transfer switch, the type name


LN1-Switch           I Power supply line, e.g. the primary line


LN2-Switch           II Power supply line, e.g. the secondary line used in emergency cases


EMRG OFF            Used to drive the automatic transfer switch transfers to the “O” position when receiving EMRG OFF signal


AUTO                   Automatic mode


Remote test          A sequence to test the functionality of the automatic transfer switch


Ts                        Transfer delay


TB                       s Return delay


OV                       Adjustable overvoltage threshold


UV                       Adjustable undervoltage threshold


2. Product overview

2.1 Product overview and packing

The OTM_C21D automatic transfer switch can be

 used as a source transfer switch in a three-phase

 or single-phase networks. Monitored conditions are,

 no-voltage, phase-loss, overvoltage and undervoltage 

detection, transfer delays, generator start and stop, and 

remote test function. Source transfer can be performed

using a manually

operated handle, locally using push buttons or fully automatically. The automatic mode includes several operating methods: Line 1 priority, no line priority and manual back switching mode. OTM_ C21D can achieve communication function by using the optional external Modbus RTU module.



1. Handle for manual operation 

2. Place for auxiliary contact blocks 

3. Push button 

4. Mimic panel 

5. Voltage sensing connections 

6. Locking clip for padlock 

7. Locking latch for releasing the handle and locking electrical control 

8. Locking clip for locking manual operation 

9. Dip switches 

10. Rotary switches 

11. Connecting terminal 

12. Modbus RTU acces


2.2 OTM_C21D switching sequence

2.2.1 Line 1 Priority (default mode)

The transfer sequence of OTM_C21D can be summarized in following steps: 

• An anomaly occurs on the Line 1 (LN1) 

• Generator start, immediately start generator in case of black-out, phase-loss, overvoltage or undervoltage (If Generator mode is selected) 

• The Line 2 start the normal functioning, transfer delay Ts 

• Change-over switch (Switch I) to the position 0 

• Change-over switch (Switch II) to the position II

And the return sequence can be summarized in the following steps: 

• The Line 1 will start the normal functioning 

• Return delay TBs 

• Change-over switch (Switch II) to the position 0 

• Change-over switch (Switch I) to the position I 

• Generator stop delay Gs 

• Generator stop


2.2.2 No line priority

The transfer sequence of OTM_C21D can be summarized in following steps: 

• An anomaly occurs on the Line 1 (LN1) 

• Transfer delay Ts, in case of black-out, phaseloss, overvoltage and undervoltage conditions 

• Change-over switch (Switch I) to the position 0 

• Change-over switch (Switch II) to the position II

And the return sequence can be summarized in the following steps: 

• The Line 1 will start the normal functioning 

• Change-over switch stays in position II • An anomaly occurs on the Line 2 (LN2) 

• Return delay TBs 

• Change-over switch (Switch II) to the position 0 

• Change-over switch (Switch I) to the position I

2.2.3 Manual return mode

The transfer sequence of OTM_C21D can be summarized in following steps:

An anomaly occurs on the Line 1 (LN1) 

• Generator start, immediately start generator in case of black-out, phase-loss, overvoltage or undervoltage (If Generator mode is selected) 

• The Line 2 start the normal functioning, transfer delay Ts 

• Change-over switch (Switch I) to the position 0 

• Change-over switch (Switch II) to the position II

And the return sequence can be summarized in the following steps: 

• The Line 1 will start t

• Change-over switch stays in position II

• An anomaly occurs on the Line 2 (LN2) 

• Change-over switch stays in position II 

• Change-over switch can be transferred manually back to position I


3. Quick start

3.1 Operating the switch manually (local operation)

To operate the switch manually:

 1.Attach the handle to the switch panel. You can attach the handle in any position. 

2.When the handle is attached, the automatic transfer switch will automatically be in 

Manual mode and won’t operate automatically in case of line failure. The AUTO LED on the mimic panel is OFF.


When the handle is inserted into the switch, the switch will enter “manual mode” with the automatic operation disabled.


Do not adjust wires when the transfer switch is being energized.


Before the power-on operation of the transfer switch, please operate the switch manually to confirm it is in normal function.


With the power supply function in “normal” and without the handle inserted and EMRG OFF signals, the initially energized switch will enter automatic mode and transfer to the main line. Keep the handle inserted if you do not want the switch to be in automatic mode upon initial energization


— 3.2 Automatic operation

OTM_C21D must be in automatic mode and the “AUTO” LED is on 

in order that the switch can perform automatic transfer cycles according

 to the pre-set operating mode.

To operate the switch electrically: • If the handle inserted 

1. Press handle locking clip and remove the handle from the switch. 

2. Press “AUTO” button and the “AUTO” LED will be ON, indicating automatic mode.

• If handle is not inserted 

1. If “AUTO” LED blinks, press “AUTO” button and the “AUTO” LED will be ON, indicating automatic mode. 

2. Automatic operation includes three operating modes: Line 1 priority (factory default setting), No line priority, and manual return mode.


3.3 System testing

3.3.1 Local test

In automatic mode, “AUTO” LED is ON and you can transfer the switch using 

I, O, and II push buttons on the front panel of the switch. Press “AUTO” button 

to return the automatic operation.

3.3.2 Remote test

The procedure of the remote test is as follows: 

1. Connect to the remote test signal according to Figure 7. 

2. Ensure that the OTM_C21D is in automatic mode (“AUTO” LED is on). 

3. Short circuit the remote test signal for at least 100 ms until the “AUTO” LED blinks to enter the test mode. Under test mode, the automatic transfer switch will simulate switching cycle and finally return to its original position prior to the activation of the test mode. e.g., when the switch is in Position I: Enter test signals; the switch transfers to Position O → to Position II → to Position O → to Position I. Entering test signals is invalid before the automatic transfer switch returns to its original position. Under test mode, press the “AUTO” button to cancel test mode and return to automatic mode. The “Auto” LED will be “ON” as normal. 

4. After the remote test finishes, the OTM_C21D automatically returns to the automatic mode (“AUTO” LED is on).


3.4 Locking

3.4.1 Locking the electrical operation

The switch can be padlocked in any position, causing that all operating modes and test operations are disabled, and handle cannot be inserted. See below for operation:

Figure 8. Locking the electrical operation

3.4.2. Locking the manual operation

By default, the manual operation can only be locked in position 0. The handle can be padlocked by pulling out the clip from the handle and place the padlock on the handle see Figure 9


3.5 Modbus communication function

OTM_C21D can achieve communication function by using the optional external Modbus RTU module.


3.5.4 Cyber security


Disclaime 

t is the sole responsibility of the customer to provide and continuously ensure a secure connection between the product and the customer network or any other network. The customer is required to establish and maintain any appropriate measures (including but not limited to the installation of firewalls, application of authentication measures, encryption of data, installation of anti- virus programs, etc.) to protect the product, the network, its system and the interface against any kind of security breach, unauthorized access, interference, intrusion, leakage and/ or theft of data or information. ABB and its affiliates are not liable for damage and/or losses related to such security breaches, unauthorized access, interference, intrusion, leakage and/or theft of data or information.


Secure Deployment

The user of the product should be aware that the unsecure nature of the serial Modbus protocol exposes the communication between the product and the control system. Encryption, authentication or integrity of transmitted data are not provided by the protocol. To prevent equipment to operate in an unsafe or undesirable manner due to malicious activities the product must be positioned in a trusted network, strictly limited and in a hosted portion of a network or control system. The recommendation is also to restrict physical access to the product/ system to only allow authorized people to make changes to the system. Besides, the user can setup system to trigger alarm when communication is interrupted (device stops responding) and check if there are any unsafe condition


4. Interface and Settings

4.1 Buttons

Figure 11. Buttons


Button                                Function                                         Remarks


I ON                                  Transfer to LN1                                Only available in automatic mode and remote test mode


O OFF                                Transfer to 0 position


II ON                                 Transfer to LN2


Auto                                  Select autiomatic mode, fault clearance and reset


Table 5. Buttons


4.3 Rotary switch settings


Transfer delay Ts The delay of transferring from the LN1 to the LN2 in automatic mode. 

The options are 0, 1, 2, 3, 5, 10, 15, 20, 25, and 30 seconds.

Return delay TBs The delay of transferring from the LN2 to the LN1 in automatic mode.

 The options are 0, 5, 10, 20, 30, 60, 120, 300, 600, and 900 seconds.

Overvoltage threshold OV (%) and undervoltage threshold UV (%) The benchmarks of the OV

 and UV are the rated voltage of the switch. When the voltage is higher than the pre-set OV value

 or lower than the preset UV value, the switch performs automatic transfer.

The value of OV can be 5%, 10%, 15%, 20%, 25%, and 30%. The

 value of UV can be 5%, 10%, 15%, 20%, 25%, and 30%.


4.4 Dip switch setting

The 9-bit dip switch is used to set the working modes of transfer switch.


4.5 Terminal outputs and inputs

The switch has 11 bits of signal terminals for users to input and output signals

Figure 16. Terminals


Terminal

No.             Function


1, 2            Remote test: connection for at least 100 ms for the switch to enter the remote test mode


3, 4            EMRG OFF: Input the 24VDC EMRG OFF signals for at least 1s until the switch transfers to the EMRG OFF 

                 position and the EMRG OFF LED is on. At this time, the switch cannot enter the automatic or test mode                       and only handle operation is allowed. After the signal is canceled, press "AUTO" to quit EMRG OFF


5, 6           Generator start: generator start signal output. When the backup power is a generator, it is used to start                      (close signal) and stop (open signal) the generator. After the switch transfers to the normal power, the                        generator stop signal is sent after the preset delay for generator stop (see the ninth bit in section 4.4 for                    the  generator stop delay setting).


7,8,9         Switch status feedback signal output.


10, 11       Alarm: The switch outputs consecutive alarm signals in EMRG OFF mode or refuses to perform operations.                  The alarm signals are cleared after quitting the EMRG OFF mode, fault recovered, or handle inserted.


Output      Output contact relays are dry contactz and therefore external voltage supply is required.

contacts    24VDC or up to 250VAC max. 3A AC1


6. Installation

6.1 Installation method

The switch can be installed using screws or a DIN rail. The fixed installation mode on the base board is as follows:

The DIN rail installation mode is as follows: First pry out the latch with an appropriate tool, as shown in Fig. 13

After attaching the switch to the DIN-rail, push the latch back to lock it

6.2 Installation dimensions


7. Optional accessories

7.1 Bridging bars


7.2 Terminal shrouds

7.3 Auxiliary contact blocks


7.4 Modbus communication module


8. Maintenance and common troubleshooting

8.1 Maintenance

To ensure the operation reliability of switches, regular switching tests should be performed (once every 3 months) to confirm normal function.


9. Appendix9.1 Wiring diagram


• Read through this instruction book carefully before working on the switch, and keep this instruction book safe for later reference 

• The images provided in this instruction book are for illustration only and may not match the actual product exactly 

• This instruction book is subject to change for product updates without prior notice






  • ALSTOM COP232.2 VME A32/D32, 029.232 446 controller unit
  • GE 151X1235DB15SA01 Gas turbine controller
  • Abaco VP869 FPGA Card
  • Abaco VP868 FPGA Card
  • Abaco VP780 FPGA Card
  • Abaco VP680 FPGA Card
  • PC821 PCIe FPGA Card
  • Abaco PC820 FPGA Card
  • Abaco PC720 FPGA Card
  • Abaco FlexVPX Backplane
  • Abaco VP880 / VP881
  • Abaco VP889 FPGA Board
  • Abaco VP430 RFSoC Board
  • Abaco VP460 Direct RF Processing System
  • Abaco VP431 RFSoC Board
  • Abaco VP461 6U VPX Xilinx UltraScale
  • Abaco VP891 3U VPX FPGA Processing Card
  • Abaco TM-683 2 PMC rear panel I/O transition module for 6U CPCI
  • Abaco CPCI-100A-FP 2-slot IndustryPack carrier for 3U CPCI systems
  • Abaco BIO-4 Rear transition card for the CPCI-200A IP carrier
  • Abaco VME-4116 VME Analog I/O Output Boards
  • Abaco VME-4140 VME Analog I/O Output Boards
  • Abaco VME-3122B VME Analog I/O Input Boards
  • Abaco VME-3113B Scanning 12-bit Analog-to-Digital Converter with Built-in-Test
  • Abaco Vme-4132 VME Analog I/O Output board
  • N-Tron® NT24K-14FXE6-SC-80 Managed 14-Port Gigabit Industrial Ethernet Switch
  • N-Tron® 7012FXE2-SC-40 Managed 12-port Industrial Ethernet Switch
  • N-Tron® NT24K-11GX3-SC-PT Managed 11-Port Gigabit Industrial Ethernet Switch
  • N-Tron® NT24K-14FXE6-SC-15 Managed 14-Port Gigabit Industrial Ethernet Switch
  • N-Tron® 7018FXE2-SC-15 Managed 18-port Industrial Ethernet Switch
  • N-Tron® NT24k 24-Port Rackmount Gigabit Managed Industrial Ethernet Switch
  • N-Tron® NT24k 24-Port, Dual Redundant VDC Power Input, Rackmount Gigabit Managed Industrial Ethernet Switc
  • N-Tron® NT24K-10FX2-SC Managed 10-Port Industrial Ethernet
  • N-Tron® NT24K-12SFP-DM4 Managed 12-Port Gigabit Industrial Ethernet Switch
  • N-Tron® NT24k 16-Port, Single Redundant VDC Power Input
  • N-tron SLX-6ES-5SC Unmanaged 6-port industrial Ethernet switch
  • NT24k® 10FX2-POE Managed PoE+ Gigabit Ethernet Switch
  • N-Tron® 105FXE-SC-15-POE-MDR Unmanaged 5-port PoE Switch
  • Sixnet® SL-8ES-1 Unmanaged 8-port Industrial Ethernet Switch
  • N-Tron® 106FX2-SC-MDR Unmanaged 6-port Industrial Ethernet Switch
  • Sixnet® SLX-9ES-3SC Unmanaged 9-port Industrial Ethernet Switch
  • N -Tron® 710FXE2-ST-80 Managed 10-port Industrial Ethernet Switch
  • N -Tron® 712FXE4-SC-15-HV Managed 12-port Industrial Ethernet Switch
  • N -Tron® 712FXE4-ST-15-HV Managed 12-port Industrial Ethernet Switch
  • N -Tron® 709FXE-SC-40 Managed 9-port Industrial Ethernet Switch
  • ABB IEMMU21 Module Mounting Unit
  • ABB CMA120 3DDE300400 Basic Controller Panel Unit
  • Bently Nevada 2300/20-RU 2300/20-CN Monitoring controller
  • A-B 4100-234-R IMC™ S Class Compact Motion Controllers
  • B&R Power Panel 300/400
  • ADLINK cPCI-3840 Processor module
  • ACQUISITIONLOGICAL81G -2
  • HIMA K1412B PLC Module
  • IS200VTCCH1CBD GE Speedtronic Turbine Control PCB board
  • TRICONEX 4200 Digital Output Module
  • DEIF SCM-1 PCB CARD Module
  • HIMA F3DIO20802 controller plc F3DIO20802
  • HIMA B5233 PLC Module
  • HIMA B5322 PLC Module
  • HIMA F7105A PLC Module
  • HIMA F7150 PLC Module
  • HIMA Z7308 PLC Module
  • HIMA F60 PS01
  • TRICONEX 4409 PLC Module
  • F8651X HIMA Central module F8651X
  • HIMA-6E-B HIMA-6E-B Large System Controller
  • HIMA P8403 PLC Module
  • F8621A HIMA communication module
  • IS200VRTDH1D GE Mark VI Printed Circuit Board
  • ABB NIACO2 PLC Module
  • ABB NIAMO1 PLC Module
  • HIMA F8652 98465266 PLC Module
  • F8652X HIMA Central module
  • HIMA 62100
  • HIMA 99-7105233 B5233-1 NSMP
  • ABBSPAD 346 C3-AA
  • ABBREF543KM127BABB
  • ABB 0-63007 M003742626
  • Abb FET3251A0P1B3C0H2M
  • ABB 3HAB8800-1
  • ABB 3AUA266001B166
  • ABB3HNM07686-1
  • ABB PQF4-3 TAS
  • Honeywell 30735863-502 - SWITCH
  • Honeywell TK-CCR014 - REDUNDANT NET INTERFACE NEW ORIGINAL FREE EXPEDITED SHIPPING/
  • Honeywell 51403165-400 - new 51403165400/
  • Honeywell318-049-001 quot100 Batteries(Japan Liion2Ah14.8Wh)INTERMEC/ PR2,PR3 P/N
  • Honeywell FC-PSU-UNI2450U - Power Supply
  • Honeywell 965-0676-010 - WARNING COMPUTER SV
  • Honeywell 51403519-160 - Module
  • Honeywell 107843 - HOUSING CARBON FILE P/N NE COND # 11438 (4)
  • Honeywell VR434VA5009-1000 - Brand new in box Condensing boiler valve DHL fast shipping
  • Honeywell SPXCDALMFX - plc new FREE EXPEDITED SHIPPING/
  • Honeywell BCM-PWS - BCM-ETH BCM-MS/TP BCM-MS/TP Network controller setFedEx or DHL
  • Honeywell YSTR12D-22/C/-2J0DFA/BE/400/T/-CM.HO.TG.SB.SM,ZS,F1,LP,/FX/,1C-BT - UNMP
  • Honeywell IWS-1603-HW - 90-250VAC 1.0A UNMP
  • Honeywell 51304386-150 - MEASUREX Factory Packed
  • Honeywell CC-PFB401 - / CCPFB401 (NEW IN BOX)
  • Honeywell 50071726 - St 800 Series Pressure Transmitter Remote Diaphragm 11-42VDC
  • Honeywell 621-2150 - / 6212150 (NEW NO BOX)
  • Honeywell 80360206-001 - USED YAMATAKE CLI BOARD
  • Honeywell BMDX001A-001 - ACCURAY / BOARD BMDX001A001
  • Honeywell XCL8010A - New CPU Controller.
  • Honeywell PGM-7320 - 1PCS NEW Rae Systems MiniRAE 3000 Portable VOC Monitor#XR
  • Honeywell BK-G40 - U65 *FULL INSTALLATION* Gas Meter 3?± Inlet/Outlet Spool NEW UNUSED
  • Honeywell DM106-0-B-00-0-R-1-00000-000-E0 - DPR100 250V NSNP
  • Honeywell KFD840 - PRIMARY FLIGHT DISPLAY CORE PN: 066-01206-0104
  • Honeywell 51401914-100 - 51400996-100
  • Honeywell C7012A1145 - 1PC New UV Flame Detector Expedited Shipping
  • Honeywell OV210 - Baxter Bakery Oven Igition Control. For DRO. 00-616973 NEW
  • Honeywell 51304431-125 - 1PC New /51304431125 1 year warranty#XR
  • Honeywell QPP-0002 - Quad Processor Module / 5 Vdc / Massima 1.2A/24Vdc/max.25mA
  • Honeywell QPP-0002 - Quad Processor Module / 5Vdc / Max. 1.2A/24Vdc/max.25mA
  • Honeywell 8C-PCNT02 - 514543363-275 module
  • Honeywell DPCB21010002 - Tata Printed Circuit Board
  • Honeywell DPCB21010002 - Tata Printed Circuit Board Rev: 0
  • Honeywell 001649-M5T028 - Tata Printed Circuit Board Rev: 0
  • Honeywell YSTD924-(J2A)-00000-FF,W3,TP,TG,SS - NSFS
  • Honeywell XF523-A - / XF523A (NEW IN BOX)
  • Honeywell TK-PRS021 - NEW IN STOCK ship by UPS
  • Honeywell 2MLR-AC22 - " 2mlr-dbsf,2mlf-ad4s,2mlf-dc4s,2mlr-ac22 Rack"
  • Honeywell 9436610 - MEASUREX NSMP
  • Honeywell RT10A-L0N-18C12S0E - RT10A.WLAN.IN.6803.CAM.STD.GMS
  • Honeywell 51305896-200 - P:C1 Rev D Nim Modem - FAST SHIP BY Fedex
  • Honeywell TK-FTEB01 - PCL module Brand New Fast Shipping By DHL
  • Honeywell 8694500 - Measurex Control Processor Module
  • Honeywell DR4500 - Truline and DR4300 Circular Chart Recorder
  • Honeywell EC-7850-A-1122 - / EC7850A1122 (NEW IN BOX)