DCS Industrial control system
NameDescriptionContent
NEW CENTER
Current Location:

ABBDCS800 Quick guide DCS800 Drives (20 A to 5200 A)

From:ABB | Author:LIAO | Time :2025-08-27 | 1808 Browse: | 🔊 Click to read aloud ❚❚ ▶ | Share:

E-STOP button without any time delay. In case of ramp stop 

selection the, K 15 timer relay must be set longer than the 

EStopRamp (22.04). For COAST selection, the drive opens 

the main contactor immediately.

OFF2 switches off DC current as fast as possible and prepares the drive for opening main contactor or drop down 

mains supply. For a normal DC motor load the time to switch 

OFF the DC current is below 20 ms. This function should be 

connected to all signals and safety functions opening the main 

contactor. This function is important for 4-quadrant drives. 

Do not open main contactor during regenerative current.

The correct sequence is 

1. switch off regenerative current

 2. then open the main contactor

In case of the E-STOP is hit, the information is transferred 

to the converter via digital input 5. In case of rampstop, or 

max torque selection the converter will decelerate the motor 

and then open main contactor.

If the drive has not finished the function within the K15 timer 

setting, the drive must get the command to switch OFF the 

current via K16. After K16 timer set has elapsed the main 

contactor is opened independent of the drives status.

Notes For North American Installations

1. EMC conformity is not usually required in North America. In most cases, the section “Notes on EMC” can be 

bypassed. In this manual, you will see references to DIN, EN 

and VDE standards. These are European standards and, 

generally, do not apply to North America. It is, however, 

the responsibility of the user to determine which standards 

need to be followed.

2. If using a DC contactor, you must connect an auxiliary

contact to a digital input of your choice and set para. MainContAck accordingly. Set the following parameters:

MainContAck (10.21) = DI-1 (or any input you

choose for the DC cont.

auxiliary contact)

DO8BitNo (14.16) = 10

MainContCtrlMode (21.16) = DCcontact (3)

Set these parameters AFTER macros are loaded but BEFORE 

the drive is commissioned.

Digital output 8 (DO-8) must be used to turn the DC

contactor on and off.

3. If using Dynamic Braking, the drive allows you to select the stopping method under three different situations. 

Parameters 21.02, 21.03 and 21.04 select the stopping 

method for loss of 

the OnOff, run command (StartStop, Jog1, Jog2, etc.), and 

E-Stop input, respectively. 

Each can be set to:

• RampStop • TorqueLimit

• CoastStop • DynBraking

In order to command the drive to perform a DB stop, one 

or more of these parameters must be set to DynBraking. 

Most users will want the drive to ramp stop when OnOff or a 

run command (StartStop, Jog1, Jog2, etc.) input is cleared, 

and dynamically brake when the E-Stop input is cleared. In 

that case, use the following settings:

• Off1Mode (21.02) = RampStop

• StopMode (21.03) = RampStop

• E StopMode (21.04) = DynBraking

However, any case is allowed and the final decision is left 

to the user.

Other parameters control stops during faults. 

See:

LocalLossCtrl (30.27) ComLossCtrl (30.28)

FaultStopMode (30.30) SpeedFbFltMode (30.36)

If using EMF feedback with dynamic braking, set:

• DynBrakeDly (50.11) = t

Where: t = the time (sec) it normally takes the motor 

to stop during dynamic braking

DC contactor US:

DC contactor US K1.1 is a special designed contactor with 2x 

NO contacts for C1 and D1 connection and 1x NC contact for 

connection of Dynamic Brake resistor RB.

The contactor should be controlled by signal 6.03 Bit 10.

The acknowledge can be connected to parameter:

10.21 MainContAck

10.23 DCBreakAck

Overview of the Installation and Commissioning Process

This is to protect the motor and converter if a commutation 

fault should occur. NOTE: DC output fuses are the same 

type and size as AC line fuses.

Line reactor:

All thyristor-based dc converters cause notching in the AC 

line due to motor commutation. A properly sized line reactor 

will mitigate the effect on the line. Unless the converter uses 

a dedicated isolation transformer, each converter requires 

its own line reactor. 

AC or DC contactor:

A contactor is required to safely disconnect the motor from 

the incoming power when the converter is off. The contactor 

can be installed between the line and the converter (an AC 

contactor) or between the converter and the motor (a DC 

contactor). Do not use both.

IMPORTANT: Other equipment may be necessary depending on application and local codes.

Step 1:

Check converter for damage. Contact ABB Technical Support 

if damage is found. In North America, call 1-800-435-7365

(1-800-HELP-365)

Step 2:

Select supporting hardware for the converter:

For specific recommendations for fuses, reactors, and 

contactors, see the DCS800 hardware manual or technical 

catalog.

Circuit breaker or disconnect:

Current rating = Idc * 0.816 * 1.25 (min)

 = Idc * 0.816 * 2.50 (max)

Where: Idc = nominal DC motor current

Fuses:

AC Line Fuses: To properly protect the converter, semiconductor fuses on the incoming AC power line are required 

  • DEIF FAS-113DG Synchronisation & circuit breaker closing
  • DEIF FAS-115DG Synchronisation & circuit breaker closing
  • DEIF HAS-111DG Synchronisation & circuit breaker closing
  • DEIF LSU-122DG Load sharing, paralleling & operation
  • DEIF LSU-114DG Load sharing, paralleling & operation
  • DEIF LSU-113DG Load sharing, paralleling & operation
  • DEIF LSU-112DG Load sharing, paralleling & operation
  • DEIF RMF-112D Frequency relay
  • DEIF RMC-142D Current relay
  • DEIF RMC-132D Current relay
  • DEIF RMC-131D Current relay
  • DEIF RMC-122D Current relay
  • DEIF RMC-121D Current relay
  • DEIF RMC-111D Current relay
  • DEIF MVR-V211 Busbar Protection
  • DEIF MVR-T257 Transformer Differential Protection
  • DEIF MVR-T256 Transformer Differential Protection
  • DEIF MVR-T216 Transformer Differential Protection
  • DEIF MVR-T215 Transformer Protection
  • DEIF MVR-M257 Motor Differential Protection
  • DEIF MVR-M255 Motor Protection
  • DEIF MVR-M215 Motor Protection
  • DEIF MVR-M210 Motor Protection
  • DEIF MVR-G257 Generator Differential Protection
  • DEIF MVR-G215 Generator Protection
  • DEIF MVR-F255 Directional Feeder Protection
  • DEIF MVR-F215 Directional Feeder Protection
  • DEIF MVR-F210 Feeder Protection
  • DEIF MVR-F205 Directional Feeder Protection
  • DEIF MVR-F201 Basic Feeder Protection
  • DEIF MVR-200 series Medium Voltage Relay
  • DEIF MDR-2 Multi-differential relay
  • DEIF LMR-122D Loss of mains relay
  • DEIF LMR-111D Loss of mains relay
  • DEIF APU-4 Advanced G59 and G99 protection unit
  • DEIF iE 650 PLC - The most robust programmable automation controller available
  • DEIF iE 350 PLC - Programmable Automation PLC Controller
  • DEIF iE 250 PLC Versatile and modular intelligent energy PLC controller
  • DEIF PPM-3 EDG Protection and Power Management
  • DEIF AGC 3X 4198000234E AUTOMATIC GENSET CONTROLLER
  • SAUTER ASF123 Damper actuator with spring return
  • SAUTER ASF122 Damper actuator with spring return
  • SAUTER ASF113F122 Damper actuator with spring return
  • SAUTER ASF113F120 Damper actuator with spring return
  • SAUTER ASF112F122 Damper actuator with spring return
  • SAUTER ASF112F120 Damper actuator with spring return
  • SAUTER ASM 124/134 series - ASM134F130 Damper actuator
  • SAUTER ASM 134 series - ASM134SF132 Damper actuator
  • SAUTER ASM 124/134 series - ASM124SF132 Damper actuator
  • SAUTER ASM 124/134 series - ASM124F122 Damper actuator
  • SAUTER ASM 124/134 series - ASM124F120 Damper actuator
  • SAUTER Valve actuator ASM 105S/115S series ASM115SF152
  • SAUTER Valve actuator ASM 105S/115S series ASM105SF152
  • SAUTER Valve actuator ASM 105S/115S series ASM115SF132
  • SAUTER Valve actuator ASM 105/115 series ASM105SF132
  • SAUTER Valve actuator ASM 105/115 series ASM115F122
  • SAUTER Valve actuator ASM 105/115 series ASM115F120
  • SAUTER Valve actuator ASM 105/115 series ASM105F122
  • SAUTER Valve actuator ASM 105/115 series ASM105F120
  • SAUTER Valve actuator ASM 105/115 series ASM105F10
  • SAUTER AKF113S Rotating actuator AKF 112/113 series
  • SAUTER AKF113F122 Rotating actuator AKF 112/113 series
  • SAUTER AKF113F120 Rotating actuator AKF 112/113 series
  • SAUTER AKF112F122 Rotating actuator AKF 112/113 series
  • SAUTER AKF112F120 Rotating actuator AKF 112/113 series
  • SAUTER AKM115SAF332: Smart Actuator for ball valve, BACnet/IP
  • SAUTER AKM115SAF232  Rotating Actuator  AKM 115SA Smart Actuator
  • SAUTER AKM115SF152  Rotating Actuator  AKM 105S/115S Series
  • SAUTER AKM115SF132  Rotating Actuator  AKM 105S/115S Series
  • SAUTER AKM105SF132  Rotating Actuator  AKM 105S/115S Series
  • SAUTER AKM115F122 Rotating actuator  AKM 105/115 series
  • SAUTER Rotating actuator  AKM 105/115 series AKM115F120
  • SAUTER Rotating actuator  AKM 105/115 series AKM105F122
  • SAUTER Rotating actuator  AKM 105/115 series  AKM105F120
  • SAUTER Continuous actuator for unit valves, with stroke AXS215S
  • SAUTER Linear valve actuator AXT/AXS series AXT211
  • SAUTER Linear valve actuator AXT/AXS series AXT201
  • SAUTER Linear valve actuator AXM/AXF series AXF217S
  • SAUTER Linear valve actuator AXM/AXF series AXM217S
  • SAUTER AXM217SF404 is an electric actuator for unit valves.
  • SAUTER AXM217SF402 is an electric actuator for unit valves.
  • SAUTER Linear valve actuator AXM/AXF series AXM217
  • SAUTER Linear valve actuator AVF 124/125 series AVF125S
  • SAUTER Linear valve actuator AVF 124/125 series AVF124S
  • SAUTER Linear valve actuator AVF 124/125 series AVF124S
  • SAUTER AVM322S-R Linear valve actuator AVM 234S series
  • SAUTER AVM322-R Linear valve actuator AVM 234S series
  • SAUTER AVM322SF132 Linear valve actuator AVM 234S series
  • SAUTER AVM321SF132    Linear Valve Actuator
  • GE Power Conversion P112-6053 Advanced Micro Controller (AMC2)
  • GE Power Conversion P111-6053 Advanced Micro Controller (AMC2)
  • GE Power Conversion P110-6053 Advanced Micro Controller (AMC2)
  • GE Power Conversion P122-6052 Advanced Micro Controller (AMC2)
  • GE Power Conversion P121-6052 Advanced Micro Controller (AMC2)
  • GE Power Conversion P112-6152 Advanced Micro Controller (AMC2)
  • GE Power Conversion P110-6152 Advanced Micro Controller (AMC2)
  • GE Power Conversion P112-6052 Advanced Micro Controller (AMC2)
  • GE P106-6052 AMC2 Advanced Micro Controller Unit
  • SAUTER AVF234SF232 Linear valve actuator AVM 234S series
  • SAUTER AVF234SF132 Linear valve actuator AVM 234S series
  • SAUTER Linear valve actuator AVM 234S series AVM234SF132-6
  • SAUTER Linear valve actuator AVM 234S series AVM234SF132-5
  • SAUTER Linear valve actuator AVM 234S series AVM234SF132
  • SAUTER Linear valve actuator AVM215SF132-7
  • SAUTER Linear valve actuator AVM215SF132R
  • Linear valve actuator AVM 115SA Smart Actuator AVM115SAF332
  • Linear valve actuator AVM 115SA Smart Actuator AVM115SAF232
  • SAUTER Linear valve actuator AVM 105S/115S series AVM115SF132
  • SAUTER Linear valve actuator AVM 105S/115S series AVM105SF132
  • SAUTER AVM115F901 Linear Valve Actuator
  • SAUTER AVM115F122 Linear Valve Actuator
  • SAUTER AVM115F120 Linear Valve Actuator
  • SAUTER AVM105F122 Linear Valve Actuator
  • SAUTER AVM105F120 Linear Valve Actuator
  • SAUTER AVM105F100 Linear Valve Actuator
  • AEROTECH SM Series High-Performance Stepper Motors
  • AEROTECH BLMSC Series Linear Motors
  • AEROTECH Custom Linear Motors
  • AEROTECH BMS Series Brushless, Slotless Rotary Motors
  • AEROTECH BM Series Brushless Rotary Motors
  • AEROTECH BLMX Series Linear Motors
  • AEROTECH BLMH Series Linear Motors
  • AEROTECH BLM Series Linear Motors
  • AEROTECH BLMC Series Linear Motors
  • AEROTECH BLMUC-143  Linear motor forcer with thermistor
  • AEROTECH BLMUC-111    Linear motor forcer with thermistor
  • AEROTECH BLMUC-95  Linear motor forcer with thermistor
  • AEROTECH BLMUC-79 Linear motor forcer with thermistor