Woodward easY-I-3400XT-P1 8440-2293
Woodward easY-I-3400XT-P1 8440-2293
Output Type/Preset Description
Relay output [R 10] Programmable
Fixed to"Command: close GGB" if GGB is
activated otherwise preconfigured to "Aux
iliary services"
Only applicable for application mode , and .
The discrete output "Command: close GGB" is an impulse output
signal.
This discrete output is enabled for the time configured in param
eter 5726 Ä p. 223.
An external holding coil and sealing contacts must be utilized with
the GGB closing circuit.
Preconfiguration "Auxiliary services":
The auxiliary services output (LogicsManager 03.01) will be ena
bled with the start command (prior to the engine start because of
the prerun time) and remains enabled as long as the engine is
running.
It will be disabled after the engine has stopped and the postrun
time has expired(i.e. for operating a cooling pump). Ä “Auxiliary
operations” on page 165 for this behavior.
The auxiliary services output (LogicsManager 03.01) is always
enabled in MANUAL operation mode.
Relay output [R 11] Programmable
Fixed to"Command: open GGB" if GGB is
activated otherwise preconfigured to
"Alarm class A and B"
Only applicable for application mode , and .
The controller enables this discrete output when the GGB is to be
opened for switching operations.
If the discrete input "Reply GGB" is energized, the discrete output
"Command: open GGB" is disabled.
Preconfiguration "Alarm class A and B":
This discrete output is enabled when a warning alarm (class A or
B alarm) is issued ( Ä Chapter 9.5.1 “Alarm Classes”
on page 944).
After all warning alarms have been acknowledged, this discrete
output will disable.
Relay output [R 12] Programmable
Preconfigured to "Shutdown alarm"
This discrete output is enabled when a shutdown alarm (class C
or higher alarm; refer to Ä Chapter 9.5.1 “Alarm Classes”
on page 944 for more information) is issued.
After all shutdown alarms have been acknowledged, this discrete
output will disable.
LogicsManager
Relay
All discrete outputs not assigned to a defined function, may be
freely configured via the LogicsManager.
Discrete Inputs
Discrete inputs may be configured to normally open (N.O.) or nor
mally closed (N.C.) states.
Fig. 150: Discrete inputs - alarm/control inputs - operation logic
(state N.O.)
In the state N.O.:
n No potential is present during normal operation.
n If an alarm is issued or control operati888on is performed, the
input is energized.
Fig. 151: Discrete inputs - alarm/control inputs - operation logic
(state N.C.
In the state N.C.:
n A potential is continuously present during normal operation
n If an alarm is issued or control operation is performed, the input
is de-energized.
ID Parameter CL Setting range
[Default]
| GE | DS200FGPAG1AHD |
| GE | PCH1026 |
| GE | IS200PMCIH1ABA |
| GE | DS200SIOBH1ABA |
| GE | DS200SIOBH1AAA |
| GE | DS200SIOBH1ACA |
| GE | IS215UCVEH2AB |
| GE | IS215UCVEH2AF |
| GE | HE700GEN200C |
| GE | IS215UCVGM06A IS215UCVGH1A VMIVME-7666-111000 |
| GE | 7750 |
| GE | IC660BBA104 6231BP10910 |
| GE | IS215UCVFH2BB VMIVME-7650-83H 350-007650-83H C |
| GE | HR911103A VMIVME-7750 |
| GE | SR750-P5-G1-S1-HI-A20-R |
| GE | IS215VCMIH2CA IS200VCMIH2CAA |
Description
1200 DI {x} Delay 2 0.08 to 650.00 s
[0.20 s]
A delay time in seconds can be assigned to each alarm or control input.
The discrete input must be enabled without interruption for the delay time
before the unit reacts.
If the discrete input is used within the LogicsManager this delay is taken into
account as well.
1201 DI {x} Opera
tion
2 The discrete inputs may be operated by an normally open (N.O.) or normally
closed (N.C.) contact.
The idle circuit current input can be used to monitor for a wire break.
A positive or negative voltage polarity referred to the reference point of the DI
may be applied.
[N.O.] The discrete input is analyzed as "enabled" by energizing the input (normally
open).
N.C. The discrete input is analyzed as "enabled" by de-energizing the input (nor
mally closed).
1202 DI {x} Alarm
class
2 An alarm class may be assigned to the discrete input.
The alarm class is executed when the discrete input is enabled.
A/[B] Warning alarm classes
C/D/E/F Shutdown alarm classes
Control Signal to issue a control command only.
If "control" has been configured, there will be no entry in the event history and
a function out of the LogicsManager ( Ä Chapter 9.3.1 “LogicsManager Over
view” on page 860) can be assigned to the discrete input.
1204 DI {x} Self
acknowledge
2 Yes The control automatically clears the alarm if the fault condition is no longer
detected.
[No] The control does not automatically reset the alarm when the fault condition is
no longer detected.
The alarm must be acknowledged and reset by manually pressing the appro
priate buttons or by activating the LogicsManager output "External acknowl
edgment" (via a discrete input or via an interface).
Notes
If the DI is configured with the alarm class "Control", self acknowledgment is
always active.
1203 DI {x} Enabled 2 87.70 LM:
Eng.mon
Monitoring for fault conditions is not performed until engine delayed moni
toring is enabled. The engine monitoring delay time (param
eter 3315 Ä p. 167) must expire prior to fault monitoring being enabled for
parameters assigned this delay.
[Always] Monitoring for this fault condition is continuously enabled regardless of engine
speed