SEL SEL-735 Power Quality and Revenue Meter
SEL-735
Power Quality and Revenue Meter
The SEL-735 offers high-accuracy metering combined with detailed power quality analysis. With data available at their fingertips, operators can easily identify power system anomalies and mitigate their impact.
For high-accuracy revenue metering applications, the SEL-735 exceeds ANSI C12.20 0.1 and IEC 62053-22 0.1 S accuracy class requirements over a wide current range.
The SEL-735 maintains this accuracy through its entire service life, eliminating costs associated with field calibration.
This makes the SEL-735 the premier choice for points of common coupling, interchanges, and critical loads.With optional continuous waveform streaming,
the SEL-735 precisely samples and sends waveform data from the power system at 3 kilosamples per second (ksps).
Accurate Metering
The SEL-735 exceeds the requirements of ANSI and IEC accuracy standards over a wide current range.
Capable of reliable and precise metering even in the presence of harmonics, the SEL-735 exceeds the Accuracy Class 0.1 requirements of ANSI C12.20 and 0.1 S accuracy class for IEC 62053-22.
Quality-focused manufacturing ensures that the meter will meet these accuracy requirements throughout its service life.Load Profile Data Collection
You can collect billing data with a simple-to-use load profile recorder that captures years of data.Advanced Integration
The SEL-735 integrates seamlessly into Itron MV-90 billing software, IEC 61850. DNP3. IEEE C37.
118. Modbus, or SEL communications architectures. Multiple communications ports and protocols enable the SEL-735 to simultaneously communicate with up to ten devices.IEEE C37.118.1a-2014 Synchrophasors
SEL-734 and SEL-735 Product Feature ComparisonThe SEL-734 Revenue Meter is no longer in production. SEL recommends selecting the SEL-735 in place of the SEL-734.SEL-735 Power Quality and Recording OptionsChoose from three power quality options to fit any application and budget.
| Feature | Basic | Intermediate | Advanced |
|---|---|---|---|
| General | |||
| Display | Customizable three-line or single-line display | Customizable three-line or single-line display | Customizable three-line or single-line display; 5-inch 800 × 480 color touchscreen display* |
| Front Port | ANSI Type II optical port or EIA-232 port | ANSI Type II optical port or EIA-232 port | ANSI Type II optical port or EIA-232 port; Type-C USB* |
| Memory | 128 MB | 256 MB | 1 GB |
| Max Harmonic Order | 15th | 63rd | 63rd |
| Interharmonic Quantities | No | No | Yes |
| Harmonic Angles | No | No | Yes |
| Power Harmonics | No | No | Yes |
| Waveform Capture | |||
| Samples Per Cycle | 16 | 16, 128 | 16, 128, 512 |
| Duration (cycles) | 15 | 15–600 | 15–600 |
| Number of Events | 256 | 33–6,200 | 101–10,000 |
| COMTRADE Reports | Yes | Yes | Yes |
| Wave View Oscillography | No | No | Yes |
| Continuous Waveform Streaming to Synchrowave | Upgradable | Yes | Yes |
| Load Profile Data | |||
| Recorders × Channels | 1 × 16 | 12 × 16 | 32 × 16 |
| Acquisition Rates | 1–120 min | 3–59 s, 1–120 min | 3–59 s, 1–120 min |
| Storage Duration | 0–10 years, varies with acquisition rate and number of channels used | 0–20 years, varies with acquisition rate and number of channels used | 0–20 years, varies with acquisition rate and number of channels used |
| Example Duration | 10 years for 16 channels logged every 10 min | 20 years for 16 channels logged every 10 min | 20 years for 16 channels logged every 10 min |
| Voltage Sag, Swell, Interruption (VSSI) Recorder | |||
| Typical Number of Summary Events | 270 | 270 | 600 |
| Number of Detailed Rows | 60,000 | 60,000 | >130,000 |
| Minimum Disturbance Duration | 1/4 cycle | 1/4 cycle | 1/4 cycle |
| Sampling Rate | 4 samples/cycle–1 sample/day, adaptive | 4 samples/cycle–1 sample/day, adaptive | 4 samples/cycle–1 sample/day, adaptive |
| Sequential Events Recorder (SER) | |||
| Number of Events | >80,000 | >80,000 | >80,000 |
| Number of Channels Monitored | ≤72 | ≤72 | ≤72 |
| IEC 61000-4-30 PQ Compliance | |||
| 150/180-Cycle, 10-Minute, 2-Hour | - | Class A | Class A |
| Flicker | - | Class A (10-min, 2-hr updates) | Class A (1-min, 10-min, 2-hr updates) |
| Voltage Harmonics | - | - | Class A |
| Current Harmonics | - | - | Class A |
| User name | Member Level | Quantity | Specification | Purchase Date |
|---|