The analog output ports of the RELIANCE Ryan 0-57413-3B DCS universal memory module: The module panel contains four analog output ports on a connector marked with instrument ports. A 5-point plug-in connector with screw-type terminal points is used to connect the instrument or data recording device to the UDC module. All connections are made with 14-22 AWG wires. Terminals 1 to 4 can be respectively connected to individual analog devices. All devices share a common connector terminal marked as COM. These outputs are not isolated from each other. Please note that these terminals (1-4 and COM) must not be grounded. Data mapping: Any register or local variable in the UDC dual-port memory (common) can be mapped to these ports for output to the instrument or chart recorder
1. Output range: Each port provides an 8-bit internal data resolution within the range of -10VDC to + 10VDC (78.125mV per bit). At +10 VDC, the output current is 20 mA. Output update: If CCLK is enabled and the UDC task is running, the value will be updated each time the UDC is scanned. If CCLK is not enabled, the value 1 will be updated every 0.20 milliseconds. Default output: The analog output port is set to output 0 VDC by default until it is configured in the application task or online. Advantageous supply: Sufficient inventory, advantageous supply 1. Advantageous supply = Function: Store PLC programs and data 12 Application: Widely used in industrial control, process control, building automation and other fields. 12 Features: Large capacity: 256MB, High Speed: 100MHz, Low Power Consumption: 2W, Stable and reliable 123. Product Description: Memory Requirements: 64K memory, suitable for multi-processor applications 123. Arbitration function: Arbitration processor's access to the bus 123. Modular design: Easy to install, equipped with LED indicator lights that can indicate the working status of the module. Parameter capacity: 256MB Speed: 100MHz Power Consumption: 2W Operating Temperature: -25℃ to 85℃123 Specification Dimensions: 100 x 60 x 20mm Weight: 100G 12 Application fields: Industrial control, process control, Building automation
Address:Xiamen City, Fujian Province, China
TELL:
E-MAIL:yang@kongjiangauto.com
E-MAIL:gedcs868@gmail.com