Jaquet FT3000 Speed measurement system
System documentation FT 3000 :
• Operating instructions FT 3000
• Operating instructions sensor
• Rack 19 ¨ description
• Bloc function description
• System configuration
• Connection diagram
Applications
FT 3000 tachometers are used to monitor and measure frequencies in the range 0 to 30000Hz eg from frequency proportional
sources such as rotational speed.
The FT 3000 family comprises of the following modules:
• Monitoring module (Motherboard) FTFU 3024
with input card -E01 FTFU 3024- E01 Art. Nr. 377Z-03981
with input card -E02 FTFU 3024- E02 Art. Nr. 377Z-03982
with input card -E03 FTFU 3024- E03 Art. Nr. 377Z-03983
with input card -E04 FTFU 3024 -E04 Art.-Nr. 377Z-05855
• Trip Chain Control card FTBU 3034 Art. Nr. 377Z-05030
• Frequency to current converter FTW 3013 Art.Nr.377Z-03984
(Auxiliary module)
• Relay card (Auxiliary module) FTV 3090 Art. Nr. 377Z-03985
• Comms module FTK 3072 Art. Nr. 377Z-03986
• PSU 116/230Vac FTZ 3061 Art. Nr. 377Z-04065
• PSU 24/48Vac FTZ 3062 Art. Nr. 377Z-04073
• PSU 14...70Vdc FTZ 3064 Art. Nr. 377Z-04074
• PSU 75...372Vdc FTZ 3065 Art. Nr. 377Z-04075
• Mains filter (2 wire) FTZ 3069 Art. Nr. 804D-35886
FT 3000 3 channel speed monitoring and over speed protection systems comprise of 3 independent channels, from speed pick
ups through to limit signalling. High integrity operation is provided for in the rack through the use of 2 redundant power
supplies to each module via diode decoupling. Rack module supply requirements are matched to the incoming supply by the 2
redundant power supplies.
4 Construction
The modules are plug in units in a 19" rack, with height 3 HE and with 4. 12 or 20 TE in accordance with DIN 41494.
Compatible card frames with up to 21 locations at 4 TE are used for mounting and wiring the modules.
The card frames are
built by JAQUET to customer requirements. Connections for speed sensors, control and output signals along with power
supplies are normally provided at the back via screw terminals or Termi-Point connections.
The setting of measuring range,
monitoring and relay parameters is via front panel RS 232 interface on the FTK 3072 comms module to a PC.
This module
controls the data flow between the PC and individual modules in the rack (RS 485 rack bus). The parameters are stored in
EEPROM’s and protected against mains failure.
Statistics
Mean Time Between Failure for each channel (without voting)
Mean Time Between Failure for each OSP channel (FTFU 3024)
Mean Time Between Failure for each signal monitoring channel (FTBU 3x34)
PFHg according to IEC 61508-2
DC % according to IEC 61508-2
: 2.69e-8 fits
: 94.23%
: 188683 hours # 21.5 years
: 230700 hours # 26.0 years
: 1036000 hours # 118 years
Life duration for the system is 20 years. During this period the data integrity of the programable devices are garanted, this time
is equivalent to the MTBF of the channel. After this period the overspeed protection system must be replaced.
6.2 Special specifications :
6.2.1 CSA specifications
• Pollution Degree 2 environment
• Installation Category II
• Altitude : sea level
• Humidity : 0%...90% condensation to be avoided
• Electrical supply 24 Vdc, max. 8A, Double or Reinforced insulated from mains
• The Ft3000 rack system must be installed in a indoor environment.
• Operating temp -5...+40ºC