A configurable low-pass filter was added to the acceleration signal.
Front Panel Display changes:
Speed display: The precision of the speed value on the front panel provides one decimal
precision when below 100 rpm. Configurable filtering added to the displayed speed value.
Improved front panel performance, providing faster response to a key press.
Analog Input display: Expanded the front panel display of the analog input to show the level
setpoints (e.g. Hi, Lo) as well as all the level status indications.
Trip button (front panel): Toggles display between the Trip Log and the Trip Latch.
Alarm button (front panel): Toggles display between the Alarm Log and the Alarm Latch.
Added Shared Reset, Shared Start, and Shared Speed Fail Override display screens.
Trip Latch inputs were rearranged to display more practical faults first (e.g. overspeed).
Modbus: A) Included the outputs of all analog logic blocks as Modbus analog/register reads.
B) The address numbering (Boolean and register) changed to be consecutive, removing
huge gaps in numbering. C) Added Spare Boolean read registers to prevent errors
experienced by devices that queried in increments of 16. D) Added 20 scalable analog reads,
allowing the user to select the source and set the signal scaling (for very large or very small
analog signals).
Expanded the configurable logic Boolean connections to include both the local and shared
signals for start, reset, and speed fail override.
New logic connections added:
Local and Shared Start
Local and Shared ResetLocal and Shared Speed Fail Override
ARM block Difference Detected
Outputs from the new analog blocks
Configuration Checking enhancements implemented:
Power-up trip (trip relay must be set for de-energize for trip)
configuration mismatch (function must be enabled)
Speed fail alarm (function must be enabled and local speed must enabled)
Speed Fail Trip and Speed Fail Timer (function must be enabled and speed must be
enabled)
GAP Programming Environment Updated
Updated the MSM GAP/simulation tool to include the firmware updates in this release. This tool
allows users to program the MSM using graphical function block code. 9927-2151 Revision B or
newer is required. Refer to manual 26712 for details on this tool.
This tool provides the following:
Graphical view of entire application
Completeness check to ensure the program will be accepted by the device
Documented feedback of the ProTech CRC codes to ensure program ‘fingerprint’ verifying laptop
GAP program & installed ProTech settings
GAP Block help clarifying the function and input/output fields of each block
Built-in simulation on the user PC to allow testing/debugging of logic
Simulation that allows manual entry (control) of Input signals
Compatibility Notes and Table
Field Software Conversion kit 8929-038 is compatible with and can be used to convert most older
MSM models to the newer models listed below. See table below for compatibility information.
Description
Part Numbers that Can Be Converted
MSM – Bulkhead Mount, HV/LV, Ind. Relays
8237‐1252 Rev D or Newer or 8237-1492
MSM – Bulkhead Mount, HV/HV, Ind. Relays
8237‐1253 Rev D or Newer or 8237-1493
MSM – Bulkhead Mount, HV/LV, Voted Relays
8237‐1254 Rev D or Newer or 8237-1494
MSM – Bulkhead Mount, HV/HV, Voted Relays
8237‐1255 Rev D or Newer or 8237-1495
MSM – Panel Mount, HV/LV, Ind. Relays
8237‐1375 Rev D or Newer or 8237-1496
MSM – Panel Mount, HV/HV, Ind. Relays
8237‐1376 Rev D or Newer or 8237-1497
MSM – Panel Mount, HV/LV, Voted Relays
8237‐1377 Rev D or Newer or 8237-1498
MSM – Panel Mount, HV/HV, Voted Relays
8237‐1378 Rev D or Newer or 8237-1499
MSM – Field Software Conversion Kit
8929-038
Only MSM Service Tool (9927-1684 Rev. F or newer) is compatible with both new and old MSM
models. Note that the latest revision of this service tool can be obtained/ downloaded from
Woodward’s website
Configuration files from older MSM models can be loaded into new MSM models using the MSM
service tool. However, configuration files from new MSM models cannot be loaded into older MSM
models.
Preferred Model Numbers
The following table shows the new/improved “preferred” MSM part numbers:
Description
Non-Preferred
Part Number
Preferred Part
Number
MSM – Bulkhead Mount, HV/LV, Ind. Relays
8237-1492
8237-2492
MSM – Bulkhead Mount, HV/HV, Ind. Relays
8237-1493
8237-2493
MSM – Bulkhead Mount, HV/LV, Voted Relays
8237-1494
8237-2494
MSM – Bulkhead Mount, HV/HV, Voted Relays
8237-1495
8237-2495
MSM – Panel Mount, HV/LV, Ind. Relays
8237-1496
8237-2496
MSM – Panel Mount, HV/HV, Ind. Relays
8237-1497
8237-2497
MSM – Panel Mount, HV/LV, Voted Relays
8237-1498
8237-2498
MSM – Panel Mount, HV/HV, Voted Relays
Customer Action
8237-1499
8237-2499
Customers who are currently using any MSM model and do not require any of the above listed
changes/improvements should take no action. Woodward is committed to supporting the listed “non
preferred” models for a period of 20 years after inactivation. Refer to the related product support plan
for these models.
After January 30. 2018. Woodward recommends that customers who are purchasing MSM units for use
in new applications order part numbers from the “preferred” part number list only.
After January 30. 2018. customers who currently own an older MSM model and wish to have/utilize one