Stop mode: Resets alarm
Lamp test (press at least 3 seconds)
Notes
During stopping process, press this button again to stop generator
immediately.
I (START) MANual mode: Start genset
MAN (Manual Mode) Press this key and the controller enters into MAN mode
AUTO (Automatic Mode) Press this key and the controller enters into AUTO mode
Open/Close breaker Release breaker control in MAN mode.
The navigation button "Up/Increase" is used to close the GCB
3.2.1

3.3
Alarm Acknowledgment
General notes
The alarm acknowledge handling is valid for following alarm classes
•
• Shutdown
•
• Trip/Stop
•
• Trip
Mute Horn
Any new active alarm activates the horn and is made visible by the flashing Alarm LED.
After pressing the "Down/Decrease" button, the horn is deactivated and the Alarm LED
changes from flashing to constantly active and stays active as long as any alarm is
present. An additional active alarm reactivates the horn and the Alarm LED starts flashing
again.
Stop by alarm
The operation mode automatically changes to STOP if a stopping alarm is active
(»Shutdown« or »Trip/Stop«).
Acknowledge alarm
In case of alarm condition, pressing the STOP button will reset the alarm.
Operation Modes
General notes
The easYgen offers three operation modes:
•
• AUTO
•
• MANUAL (MAN)
•
• STOP
•
• ... and an internal (non) operating phase during the start of the device itself
The operation mode can be initiated – provided the current settings allow for this
function:
•
• directly by pressing the respective button on the front panel
•
• directly by click on the respective button on the ToolKit-SC remote screen
•
• via discrete inputs
•
• via interface
3.3.1
General notes
In operation mode AUTO, both genset and breaker are under easYgen control. The start
and stopping of the engine is managed automatically, along with opening/closing the
breaker.
•
• supply load by generator
•
• start the engine
•
• stop the engine
3.3.2
Operation Mode MANual
General notes
In operation mode MANual, both genset and breakers are independent of each other
under easYgen control.
The starting and stopping of the engine are managed using the same procedure as in
AUTO mode but without breaker control. Breakers can be opened and closed without
taking care of load or genset state!
3.3.3
Operation Mode STOP
General notes
In operation mode STOP, the breaker is open and the engine is not running.
3.4
3.4.1

START/STOP Operation
Start engine to supply load
The AUTO Start procedure is going through sub procedures with own timers
3.5
Pressing
can stop the running generator as described above.
Transition Procedures
3.5.1
Disconnect during cranking
There are three conditions under control to abort the starting of the engine:
•
• speed sensor
•
• generator frequency
•
• engine oil pressure
They can be used separately or in combinations.
We recommend selecting all three at the same time: engine oil pressure together with
speed sensor, and generator frequency. This allows for an immediate separation of the
starter motor from the engine. Additionally, crank disconnect can be checked exactly.
When set to speed sensor, ensure that the number of flywheel teeth is the same as
setting.
5 Glossary and List of Abbreviations
CB Circuit Breaker
CT Current Transformer
DI Discrete Input
DO Discrete (Relay) Output
ECU Engine Control Unit
FMI Failure Mode Indicator
GCB Generator Circuit Breaker
GOV (speed) Governor; rpm regulator
HMI Human Machine Interface e.g., a front panel with display and
buttons for interaction
I Current
MCB Mains Circuit Breaker
MPU Magnetic Pickup Unit
N.C. Normally Closed (break) contact
N.O. Normally Open (make) contact
NC Neutral Contactor
OC Occurrence Count
Operation In (general) operation.
State when the genset is running according to the selected
mode, all parameters are in allowed values and ranges, and
without OPEN requests or alarms. Somehow "waiting for next
occurrence".
P Real power
P/N Part Number
PF Power Factor
PT Potential (Voltage) Transformer
Q Reactive power
S Apparent power
S/N Serial Number
SPN Suspect Parameter Number
V Voltage
Index
A
Alarms
Classes . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 25█
Shutdown Alarms . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 26█
C
Contact person . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 9█
Customer Service . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 9█
F
Functions . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 12█
I
Intended use . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 9█