Measurement made easy
Engineered solutions for all applications
Base accuracy
• from 0.06 % of calibrated span (optional 0.04 %)
Reliable sensing system coupled with very latest digital technologies
• provides large turn down ratio up to 100:1
Comprehensive sensor choice
• optimize in-use total performance and stability
10–year stability
• 0.15 % of URL
Flexible configuration facilities
• provided locally via local LCD keypad
TTG (Through-The-Glass) keypad technology
• allows quick and easy local configuration without opening the cover,
even in explosion proof environments
IEC 61508 certification
• version for SIL2 (1oo1) and SIL3 (1oo2) applications
PED compliance
• Category III for PS > 20 MPa, 200 bar
• Sound Engineering Practice (SEP) for PS ≤ 20 MPa, 200 bar
WirelessHART version
• the battery powered solution compliant to IEC 62591
Best-in-class battery life
• up to 10 years @ 32 s update time
• in-field replaceable
Product in compliance with Directive 2011/65/UE (RoHS II)
In-built advanced diagnostics
Specification – functional
Range and span limits
Sensor
code
Upper range limit
(URL)
Lower range limit
(LRL)
Minimum
measuring span
A 1 kPa
10 mbar
4 inH2O
–1 kPa
–10 mbar
–4 inH2O
0.05 kPa
0.5 mbar
0.2 inH2O
B 4 kPa
40 mbar
16 inH2O
–4 kPa
–40 mbar
–16 inH2O
0.2 kPa
2 mbar
0.8 inH2O
E 16 kPa
160 mbar
64 inH2O
–16 kPa
–160 mbar
–64 inH2O
0.54 kPa
5.4 mbar
2.16 inH2O
F 40 kPa
400 mbar
160 inH2O
–40 kPa
–400 mbar
–160 inH2O
0.4 kPa
4 mbar
1.6 inH2O
H* 160 kPa
1600 mbar
642 inH2O
–160 kPa
–1600 mbar
–642 inH2O
1.6 kPa
16 mbar
6.4 inH2O
M* 600 kPa
6 bar
87 psi
–600 kPa
–6 bar
–87 psi
6 kPa
0.06 bar
0.87 psi
P* 2400 kPa
24 bar
348 psi
–2400 kPa
–24 bar
–348 psi
24 kPa
0.24 bar
3.5 psi
Q* 8000 kPa
80 bar
1160 psi
–8000 kPa
–80 bar
–1160 psi
80 kPa
0.8 bar
11.6 psi
S* 16000 kPa
160 bar
2320 psi
–16000 kPa
–160 bar
–2320 psi
160 kPa
1.6 bar
23.2 psi
* For 266DSH gauge version the LRL for sensors H, M, P, Q, S is 1 kPa abs /
10 mbar abs / 0.15 psia
Span limit
Maximum span = URL
(can be further adjusted up to ± URL (TD = 0.5) for
differential models, within the range limits)
IT IS RECOMMENDED TO SELECT THE TRANSMITTER
SENSOR CODE PROVIDING THE TURNDOWN VALUE AS
LOWEST AS POSSIBLE TO OPTIMIZE PERFORMANCE
CHARACTERISTICS.
Zero suppression and elevation
Zero and span can be adjusted to any value within the
range limits detailed in the table as long as:
– calibrated span ≥ minimum span
Damping (feature not available for WirelessHART version)
Selectable time constant : between 0 and 60 s
This is in addition to sensor response time.
Turn on time
Operation within specification in less than 10 s with
minimum damping.
Insulation resistance
> 100 MΩ at 500 V DC (terminals to earth)
Specification – operative limits
Pressure limits
Overpressure limits
The differential pressure transmitters, models 266DSH,
work without damage within the following pressure limits:
Sensors Fill fluid Overpressure limits
Sensor F to S Silicone oil 0.07 kPa abs, 0.7 mbar abs, 0.5 mmHg
and 21 MPa, 210 bar, 3045 psi *, **
Sensor E Silicone oil 0.07 kPa abs, 0.7 mbar abs, 0.5 mmHg
and 16 MPa, 160 bar, 2320 psi *
Sensor B Silicone oil 0.07 kPa abs, 0.7 mbar abs, 0.5 mmHg
and 7 MPa, 70 bar, 1015 psi *
Sensor A Silicone oil 0.07 kPa abs, 0.7 mbar abs, 0.5 mmHg
and 2 MPa, 20 bar, 290 psi *
Sensor F to S Inert
(Galden)
0.135 kPa abs, 1.35 mbar abs, 1 mmHg
and 21 MPa, 210 bar, 3045 psi *, **
Sensor E Inert
(Galden)
0.135 kPa abs, 1.35 mbar abs, 1 mmHg
and 16 MPa, 160 bar, 2320 psi *
* 1 MPa, 10 bar, 145 psi for Kynar-PVDF
** 16 MPa, 160 bar, 2320 psi for AISI 316 ss NACE “exposed bolting“
For flange mounted version
Flange Fill fluid Overpressure limits
ASME B16.5
Class 150
Silicone oil 0.07 kPa abs, 0.7 mbar abs, 0.5 mmHg
and 230 psi
ASME B16.5
Class 300
Silicone oil 0.07 kPa abs, 0.7 mbar abs, 0.5 mmHg
and 600 psi
EN 1092-1 PN 16 Silicone oil 0.07 kPa abs, 0.7 mbar abs, 0.5 mmHg
and 13.5 bar
EN 1092-1 PN 40 Silicone oil 0.07 kPa abs, 0.7 mbar abs, 0.5 mmHg
and 33.8 bar
ASME B16.5
Class 150
Inert
(Galden)
0.135 kPa abs, 1.35 mbar abs, 1 mmHg
and 230 psi
ASME B16.5
Class 300
Inert
(Galden)
0.135 kPa abs, 1.35 mbar abs, 1 mmHg
and 600 psi
EN 1092-1 PN 16 Inert
(Galden)
0.135 kPa abs, 1.35 mbar abs, 1 mmHg
and 13.5 bar
EN 1092-1 PN 40 Inert
(Galden)
0.135 kPa abs, 1.35 mbar abs, 1 mmHg
and 33.8 bar
Static pressure limits
The differential pressure transmitters, models 266DSH
work within specifications between the following limits:
Sensors Static pressure limits
Sensor F to S 1.3 kPa abs, 13 mbar abs, 0.2 psia
and 21 MPa, 210 bar, 3045 psi *, **
Sensor E 1.3 kPa abs, 13 mbar abs, 0.2 psia
and 16 MPa, 160 bar, 2320 psi *
Sensor B 1.3 kPa abs, 13 mbar abs, 0.2 psia
and 7 MPa, 70 bar, 1015 psi *
Sensor A 1.3 kPa abs, 13 mbar abs, 0.2 psia
and 2 MPa, 20 bar, 290 psi *
* 1 MPa, 10 bar, 145 psi for Kynar-PVDF
** 16 MPa, 160 bar, 2320 psi for AISI 316 ss NACE “exposed bolting“
Flange Static pressure limits
ASME B16.5 Class 150 1.3 kPa abs, 13 mbar abs, 0.2 psia and 230 psi
ASME B16.5 Class 300 1.3 kPa abs, 13 mbar abs, 0.2 psia and 600 psi
EN 1092-1 PN 16 1.3 kPa abs, 13 mbar abs, 0.2 psia and 13.5 bar
EN 1092-1 PN 40 1.3 kPa abs, 13 mbar abs, 0.2 psia and 33.8 bar
The pressure limit decreases with increasing temperature above 100°F
(38°C), according to ASME B16.5 standards or above 50°C according to
EN 1092-1 standards.
Proof pressure
The transmitter with threaded process connection can be
exposed without leaking to line pressure of up to
• 48 MPa, 480 bar, 6960 psi for standard static version
• up to two times the flange rating for the flange
mounted version.
Meet ANSI/ISA-S 82.03 hydrostatic test requirements.
Temperature limits °C ( °F)
Ambient
is the operating temperature
Models 266DSH Ambient temperature limits
Silicone oil for sensor F to S –40 and 85 °C (–40 and 185 °F)
Silicone oil for sensor A to E –40 and 85 °C (–40 and 185 °F)*
Inert (Galden) for sensor F to S –20 and 85 °C (–4 and 185 °F)
Inert (Galden) for sensor E –10 and 85 °C (14 and 185 °F)
Models 266DSH Ambient temperature limits
LCD integral display –40 and 85 °C (–40 and 185 °F)
LCD display may be affected in visibility below -20°C (-4°F) or above +70°C
(+185°F).
Transmitters with ambient temperature limit of -50°C (-58° F) are available
through special option.
This special option is not compatible with communication protocol option
“7”
IMPORTANT
For Hazardous Atmosphere applications see the
temperature range specified on the certificate/approval
relevant to the aimed type of protection
Process
Models 266DSH Process temperature limits
Silicone oil for sensor F to S –40 and 121 °C (–40 and 250 °F) *
Silicone oil for sensor A to E –25 and 121 °C (–13 and 250 °F) *
Inert (Galden) for sensor F to S –20 and 100 °C (–4 and 212 °F) **
Inert (Galden) for sensor E –10 and 100 °C (14 and 212 °F) **
* 100 °C (212 °F) for application below atmospheric pressure
** 65 °C (150 °F) for application below atmospheric pressure
Models 266DSH Process temperature limits
Viton gasket –20 and 121 °C (–4 and 250 °F)
Storage
Models 266DSH Storage temperature limits
Storage limits –50 and 85 °C (–58 and 185 °F)
LCD integral display –40 and 85 °C (–40 and 185 °F)
* between -40°C (-40° F) and -25°C (-13° F) device response
time might be influenced
Environmental limits
Electromagnetic compatibility (EMC)
Comply with 2014/30/UE to standards EN 61326-1:2013.
For IEC 61508 SIL certified transmitter to
EN 61326-3-1:2008.
For transmitter with option “YE” to NAMUR NE 021 (2004).
Surge immunity level (with surge protector): 4 kV
(according to IEC 61000-4–5 EN 61000–4–5)
Pressure equipment directive (PED)
Comply with 2014/68/UE to standards
ANSI/ISA 61010-1:2012
Category III Module H for PS ≥ than 20 MPa, 200 bar
Sound Engineering Practice (SEP) for PS < 20 MPa, 200 bar
Humidity
Relative humidity: up to 100 %
Condensing, icing: admissible
Vibration resistance
Accelerations up to 2 g at frequency up to 1000 Hz
(according to IEC 60068–2–6)
Shock resistance
Acceleration: 50 g
Duration: 11 ms
(according to IEC 60068–2–27)
Wet and dust-laden atmospheres
The transmitter is dust and sand tight and protected
against immersion effects as defined by IEC 60529 (2001)
to IP 67 (IP 68 on request) or by NEMA Type 4X.
IP65 with Harting Han connector.
Aluminium and AISI housings as barrel version also comply
to IP 66 as defined by IEC 60529 (2001).
IP66W/IP67W/IP68W as standard for Inmetro certification.
...Specification – operative limits
Hazardous atmospheres
(FOR ALL VERSIONS EXCEPT WirelessHART)
With or without integral display
INTRINSIC SAFETY Ex ia:
• ATEX Europe (code E1) approval
II 1 G Ex ia IIC T6...T4 Ga, II 1/2 G Ex ia IIC T6...T4 Ga/Gb,
II 1 D Ex ia IIIC T85 °C Da, II 1/2 D Ex ia IIIC T85 °C Da;
IP66, IP67.
• IECEx (code E8) approval
Ex ia IIC T6...T4 Ga/Gb, Ex ia IIIC T85 °C Da; IP66, IP67.
• NEPSI China (code EY)
Ex ia IIC T4/T5/T6 Ga, Ex ia IIC T4/T5/T6 Ga/Gb,
Ex iaD 20 T85/T100/T135, Ex iaD 20/21 T85/T100/T135.
EXPLOSION PROOF:
• ATEX Europe (code E2) approval
II 1/2 G Ex db IIC T6 Ga/Gb Ta=–50 °C to +75 °C,
II 1/2 D Ex tb IIIC T85 °C Db Ta = –50 °C to +75 °C;
IP66, IP67.
• IECEx (code E9) approval
Ex db IIC T6 Ga/Gb Ta=–50 °C to +75 °C,
Ex tb IIIC T85 °C Db Ta = –50 °C to +75 °C; IP66, IP67.
• NEPSI China (code EZ)
Ex d IIC T6 Gb, Ex tD A21 IP67 T85 °C.
INTRINSIC SAFETY Ex ic:
• ATEX Europe (code E3 ) type examination
II 3 G Ex ic IIC T6...T4 Gc,
II 3 D Ex tc IIIC T85 °C Dc; IP66, IP67.
• IECEx (code ER) type examination
Ex ic IIC T6...T4 Gc, Ex tc IIIC T85 °C Dc; IP66, IP67.
• NEPSI China (code ES) type examination
Ex ic IIC T4~T6 Gc, Ex nA IIC T4~T6 Gc,
Ex tD A22 IP67 T85 °C.
FM Approvals US (code E6) and
FM Approvals Canada (code E4):
• Explosionproof (US): Class I, Division 1,
Groups A, B, C, D; T5
• Explosionproof (Canada): Class I, Division 1,
Groups B, C, D; T5
• Dust-ignitionproof: Class II, Division 1, Groups E, F, G;
Class III, Div. 1; T5
• Flameproof (US): Class I, Zone 1 AEx d IIC T4 Gb
• Flameproof (Canada): Class I, Zone 1 Ex d IIC T4 Gb
• Nonincendive: Class I, Division 2, Groups A, B, C, D T6...T4
• Energy limited (US): Class I, Zone 2 AEx nC IIC T6...T4
• Energy limited (Canada): Class I, Zone 2 Ex nC IIC T6...T4
• Intrinsically safe:Class I, II, III, Division 1,
Groups A, B, C, D, E, F, G T6...T4
Class I, Zone 0 AEx ia IIC T6...T4 (US)
Class I, Zone 0 Ex ia IIC T6...T4 (Canada)
Type 4X, IP66, IP67 for all above markings.
COMBINED FM Approvals US and Canada
• Intrinsically safe (code EA)
COMBINED ATEX, FM and IECEx Approvals (code EN)
Technical Regulations Customs Union EAC (Russia,
Kazakhstan, Belarus), Inmetro (Brazil), Kosha (Korea)
(ONLY FOR WirelessHART VERSION)
With or without integral display
INTRINSIC SAFETY Ex ia:
• ATEX Europe (code E1) approval
II 1 G Ex ia IIC T4 and II 1/2 G Ex ia IIC T4, IP67.
• IECEx (code E8) approval
Ex ia IIC T4
FM Approvals US and FM Approvals Canada:
• Intrinsically safe:Class I, Division 1, Groups A, B, C, D; T4
Class I, Zone 0 AEx ia IIC T4 Gb (US)
Class I, Zone 0 Ex ia IIC T4 Gb (Canada)
IP67 for all above markings.
IMPORTANT
REFER TO CERTIFICATES FOR AMBIENT TEMPERATURE
RANGES RELATED TO THE DIFFERENT TEMPERATURE
CLASSES.
Electrical Characteristics and Options
Optional indicators
Integrated digital display
(code LS; only with HART standard functionality)
Wide screen LCD, 128 x 64 pixel,
52.5 x 27.2 mm (2.06 x 1.07 in.) dot matrix.
Two keys for zero/span or without front
push buttons when ordered with R1
external pushbuttons option
Display may also indicate static pressure,
sensor temperature and diagnostic messages.
Integral display with integral keypad
(code L1; not with HART standard functionality)
Wide screen LCD, 128 x 64 pixel,
52.5 x 27.2 mm (2.06 x 1.07 in.) dot matrix.
Multilanguage. Four keys for configuration
and management of device.
Easy setup for quick commissioning.
User selectable application-specific
visualizations.
Totalized and instantaneous flow indication.
Display may also indicate static pressure, sensor
temperature and diagnostic messages and provides
configuration facilities.
Integral display with Through-The-Glass (TTG) activated
keypad (code L5; not with HART standard functionality)
As above integral display but equipped
with the innovative TTG keypad allowing
the activation of the configuration and
management menus of the device without
the need of removing the transmitter
housing cover. TTG keypad is protected
against accidental activations.
Optional surge protection
Up to 4kV
• voltage 1.2 µs rise time / 50 µs delay time to half value
• current 8 µs rise time / 20 µs delay time to half value
Process diagnostics (PILD)
Plugged impulse line detection (PILD) generates a warning
via communication (HART, PA, FF). The device can be
configured to drive the output to “Alarm current” or set a
status “BAD”.
HART®
digital communication and 4 to 20 mA
output – Standard and Advanced functionality
Device type: 1a06hex (listed with HCF)
Power supply
The transmitter operates from 10.5 to 42 V DC with no
load and is protected against reverse polarity connection
(additional load allows operations over 42 V DC).
For Ex ia and other intrinsically safe approval power
supply must not exceed 30 V DC. Minimum operating
voltage increases to 12.3 V DC with optional surge
protector or to 10.8 V DC with optional conformity to
NAMUR NE 21 (2004).
Ripple
20 mV max on a 250 Ω load as per HART specifications.
Load limitations
4 to 20 mA and HART total loop resistance :
A minimum of 250 Ω is required for HART communication.
Output signal
Two–wire 4 to 20 mA, user-selectable for linear or square
root output, power of 3
/2 or 5
/2 , square root for
bidirectional flow, 22 points linearization table (i.e. for
horizontal or spherical tank level measurement). HART®
communication provides digital process variable
superimposed on 4 to 20 mA signal, with protocol based
on Bell 202 FSK standard.
HART revision 7 is the default HART output.
HART revision 5 is selectable on request.
Output current limits (to NAMUR NE 43 standard)
Overload condition
• Lower limit: 3.8 mA (configurable from 3.8 to 4 mA)
• Upper limit: 20.5 mA (configurable from 20 to 21 mA)
Alarm current
• Lower limit: 3.6 mA (configurable from 3.6 to 4 mA)
• Upper limit: 21 mA (configurable from 20 to 23 mA,
limited to 22 mA for HART Safety; apply for electronics
release 7.1.15 or later)
Factory setting: high alarm current.
...Specification – electrical characteristics and options
IEC 62591 WirelessHART®
output
Device type: 1a06hex (listed with HCF)
Network ID: ABBhex (2747 decimal)
Join keys: 57495245hex (1464422981) 4c455353hex (1279611731)
4649454chex (1179206988) 444b4559hex (1145783641).
Power Supply
1x D-cell size lithium-thionyl chloride battery.
Battery life: 10 years at 32 sec. update time, 8 years at 16
sec. update time or 5 years at 8 sec. update time.
(at reference conditions of 25 ± 2 °C ambient temperature,
data routed from 3 additional devices, LCD off).
THE BATTERY CAN BE REPLACED IN FIELD, ALSO IN
HAZARDOUS CLASSIFIED AREA.
Output signal
IEC 62591 WirelessHART Version 7.5 (IEEE 802.15.4-2006);
Frequency band: 2.4 GHz DSSS
Update rate: user selectable from 1 sec. to 60 min.
Integrated adjustable omnidirectional antenna
– Output radio frequency: maximum 10 mW (10 dBm) EIRP
– Range: up to 300 m. (328 yds.)
Minimum distance between antenna and person is 0.2 m.
(8 in.)
Telecommunications directive
Every wireless measuring device must be certified in
accordance with the telecommunications directive, in this
case the frequency range. This certification is countryspecific.
European directives
Radio Equipment & Telecommunications Terminal
Equipment Directive 2014/53/UE to standards EN 60950-
1:2013,
EN 62311:2008, EN 301 489-1 V1.9.2, EN 301 489-17 V2.2.1,
EN 300 328 v1.8.1.
In Europe, use of the 2400 - 2483.5 MHz frequency band is
not harmonized. Country-specific regulations must be
observed.
Restrictions for Norway
Operation not permitted within a radius of 20 km around
Ny-Alesund in Svalbard. For more information, see
www.npt.no Norway Posts and Telecommunications site
Extra-european radio frequency licences
USA to FCC Part 15.247:2009;
Canada to IC RSS-210 and ICES-003;
Argentina; United Arab Emirates (UAE); India; Mexico.
PROFIBUS®
PA output
Device type
Pressure transmitter compliant to Profiles 3.0.1
Identification number: 3450 (hex)
Power supply
The transmitter operates from 9 to 32 V DC , polarity
independent, with or without surge protector.
For Ex ia approval power supply must not exceed 17.5 V DC.
Intrinsic safety installation according to FISCO model.
Current consumption
operating (quiescent): 15 mA
fault current limiting: 20 mA max.
Output signal
Physical layer in compliance to IEC 1158–2/EN 61158–2
with transmission to Manchester II modulation, at 31.25
kbit/s.
Output interface
PROFIBUS PA communication according to Profibus
DP50170 Part 2/DIN 19245 part 1–3.
Output update time
25 ms
Data blocks
3 analog input, 1 physical.
Additional blocks
1 Pressure with calibration transducer block
1 Advanced Diagnostics transducer block including
Plugged Input Line Detection
1 Local Display transducer block
Transmitter failure mode
On gross transmitter failure condition, detected by selfdiagnostics, the output signal can be driven to defined
conditions, selectable by the user as safe, last valid or
calculated value.
If electronic failure or short circuit occur the transmitter
consumption is electronically limited at a defined value
(20 mA approx), for safety of the network.
FOUNDATION FieldbusTM output
Device type
LINK MASTER DEVICE
Link Active Scheduler (LAS) capability implemented.
Manufacturer code: 000320hex
Device type code: 0007hex
Power supply
The transmitter operates from 9 to 32 V DC, polarity
independent, with or without surge protector.
For Ex ia approval power supply must not exceed 24 V DC
(FF–816 certification) or 17.5 V DC (FISCO certification).
Current consumption
operating (quiescent): 15 mA
fault current limiting: 20 mA max.
Output signal
Physical layer in compliance to IEC 61158–2/EN 61158–2.
Transmission to Manchester II modulation, at 31.25 kbit/s.
Function blocks/execution period
3 enhanced Analog Input blocks/25 ms max (each)
1 enhanced PID block/40 ms max.
1 standard ARitmetic block/25 ms
1 standard Input Selector block/25 ms
1 standard Control Selector block/25 ms
1 standard Signal Characterization block/25 ms
1 standard Integrator/Totalizer block/25 ms
Additional blocks
1 enhanced Resource block,
1 custom Pressure with calibration transducer block
1 custom Advanced Diagnostics transducer block
including Plugged Input Line Detection
1 custom Local Display transducer block
Number of link objects
35
Number of VCRs
35
Output interface
FOUNDATION fieldbus digital communication protocol to
standard H1, compliant to specification V. 1.7.
Transmitter failure mode
The output signal is “frozen” to the last valid value on
gross transmitter failure condition, detected by selfdiagnostics which also indicate a BAD conditions. If
electronic failure or short circuit occur the transmitter
consumption is electronically limited at a defined value
(20 mA approx), for safety of the network.
Specification – performance
Stated at reference condition to IEC 60770 ambient
temperature of 20 °C (68 °F), relative humidity of 65 %,
atmospheric pressure of 1013 hPa (1013 mbar), mounting
position with vertical diaphragm and zero based range for
transmitter with isolating diaphragms in AISI 316 L ss or
Hastelloy and silicone oil fill and HART digital trim values
equal to 4 mA and to 20 mA span end points, in linear
mode.
Unless otherwise specified, errors are quoted as % of
span.
Some performance referring to the Upper Range Limit are
affected by the actual turndown (TD) as ratio between
Upper Range Limit (URL) and calibrated span.
IT IS RECOMMENDED TO SELECT THE TRANSMITTER
SENSOR CODE PROVIDING THE TURNDOWN VALUE AS
LOWEST AS POSSIBLE TO OPTIMIZE PERFORMANCE
CHARACTERISTICS.
Dynamic performance (according to IEC 61298–1
definition)
Sensors Total response time
Sensor M to S ≤ 100 ms
Sensor F to H ≤ 100 ms*
Total response time for sensor E ≤ 130 ms*, for sensor B ≤ 310 ms*
Total response time includes dead time of 30 ms (for all sensors) with
time constant @ 63.2 % of total step change.
See “Update Rate” for WirelessHART version.
Accuracy rating (Elin)
% of calibrated span, including combined effects of
terminal based linearity, hysteresis and repeatability.
For fieldbus versions SPAN refer to analog input function
block outscale range
Model Sensor for TD
266DSH F to P from 1:1 to 10:1 ± 0.06 %
F to P from 10:1 to 100:1 ± (0.006 x TD) %
E, Q, S from 1:1 to 10:1 ± 0.075 %
Q and S from 10:1 to 100:1 ± (0.0075 x TD) %
E from 10:1 to 30:1 ± (0.0075 x TD) %
B from 1:1 to 10:1 ± 0.10 %
B from 10:1 to 20:1 ± (0.01 x TD) %
A from 1:1 to 4:1 ± 0.10 %
A from 4:1 to 20:1 ± (0.025 x TD) %
266DSH
(option D2)
F to Q from 1:1 to 5:1 ± 0.04 %
F to P from 5:1 to 100:1 ± (0.0105 + 0.0059 x TD) %
Q from 5:1 to 100:1 ± (0.003 + 0.0074 x TD) %
(*) Availability subject to special request and not applicable
for explosionproof and flameproof
Ambient temperature (E∆Tz + E∆Ts)
per 20K change between the limits of –40 °C to +85 °C
(per 36 °F change between the limits of –40 to +185 °F):
Model Sensor for TD up to
266DSH F to Q 10:1 ± (0.03 % URL + 0.045 % span)
E and S 10:1 ± (0.04 % URL + 0.065 % span)
B 10:1 ± (0.06 % URL + 0.10 % span)
A 4:1 ± (0.10 % URL + 0.10 % span)
for an ambient temperature change from –10 °C to +60 °C
(+14 to +140 °F):
Model Sensor for TD up to
266DSH F to Q 10:1 ± (0.055 % URL + 0.08 % span)
E and S 10:1 ± (0.075 % URL + 0.11 % span)
B 10:1 ± (0.11 % URL + 0.18 % span)
A 4:1 ± (0.18 % URL + 0.18 % span)
per 10K change between the limits of –40 °C to –10 °C or
+60° to +85 °C (per 18 °F change between the limits of –40
to +14 °F or +140° to +185 °F):
Model Sensor for TD up to
266DSH F to Q 10:1 ± (0.03 % URL + 0.04 % span)
E and S 10:1 ± (0.04 % URL + 0.055 % span)
B 10:1 ± (0.055 % URL + 0.09 % span)
A 4:1 ± (0.09 % URL + 0.09 % span)
Static pressure (E∆Ps)
(zero errors can be calibrated out at line pressure)
per 0.5 MPa, 5 bar or 72.5 psi (sensor A)
per 2 MPa, 20 bar or 290 psi (sensor B)
per 3.5 MPa, 35 bar or 500 psi (sensor E)
per 7 MPa, 70 bar or 1015 psi (sensor F to S)
Model 266DSH standard static
• zero error: ±0.05 % of URL for sensor F to S
±0.08 % of URL for sensor A, B and E
• span error: ±0.08 % of reading.
Model 266DSH flange mounted
per 2 MPa, 20 bar or 290 psi
• zero error: ±0.05 % of URL for sensor F to P
±0.08 % of URL for sensor E
span error: ±0.08 % of reading.
Supply voltage
Within voltage/load specified limits the total effect is less
than 0.005 % of URL per volt.
Load
Within load/voltage specified limits the total effect is
negligible.
Electromagnetic field
Meets all the requirements of EN 61326 for surge
immunity level (of NAMUR NE 21 on request).
Common mode interference
No effect from 100Vrms @ 50Hz, or 50 V DC
Mounting position
Rotations in the plane of the diaphragm have a negligible
effect. A tilt from the vertical of up to 90° causes a zero
point shift of up to 0.5 kPa (5 mbar, 2 inH2O), which can be
corrected by making an appropriate zero position
adjustment. There is no effect on the measuring span.
In applications where a dynamic inclined installation is
required (e.g. naval applications with maximum vessel
inclination of +/-22.5°), the maximum error can be up to 3
mbar for 266DSH
Such error might be resulting in a deviation from the
standard accuracy with percentual magnitude depending
on the range of the selected device.
In case of non-dynamic inclined installations, this effect
can be eliminated by performing a zero calibration in the
field.
Please contact ABB to assess more in details on the
installation effects
Stability
±0.15 % of URL over a ten years period
(±0.25 % of URL over a ten years period for sensor A or B)
Maximum total performance
For temperature change of 28 °C (50 °F), static pressure
change of 5,1 MPa, 51 bar, 740 psi, for model 266DSH with
accuracy option code D2 (± 0.04 %)
Sensor Span Maximum total performance
F 35 kPa, 350 mbar, 140 inH2O ≤± 0.125 % of calibrated span
H 150 kPa, 1,5 bar, 600 inH2O
M 550 kPa, 5,5 bar, 80 psi
EMperf = √ (E∆Tz + E∆Ts)2
+ E∆Ps 2
+ Elin 2
EMperf = Maximum total performance
E∆Tz = Effect of the ambient temperature on zero
E∆Ts = Effect of the ambient temperature on span
E∆Ps = Effect of the static pressure on span
Elin = Accuracy rating (for terminal-based linearity 0.04 %)
Total performance
similar to DIN 16086
Temperature change in the range from –10 to 60 °C (14 to 140 °F),
static pressure change (266DSH) 10 MPa, 100 bar, 1450 psi
Model Sensor TD Total performance
266DSH std. static, D2 option F to Q 1:1 ≤± 0.16 % of calibrated span
Eperf = √ (E∆Tz + E∆Ts)2
+ E∆Ps 2
+ Elin 2
Eperf = Total Performance
E∆Tz = Effect of the ambient temperature on zero
E∆Ts = Effect of the ambient temperature on span
E∆Ps = Effect of the static pressure on span
Elin = Accuracy rating (for terminal-based linearity 0.04 %
or 0.075% as per model/sensor accuracy)
Maximum total performance and Total performance
includes the measuring errors of
• non-linearity including hysteresis and nonreproducibility,
• thermal change of the ambient temperature as regards
the zero signal and the calibrated span,
• effect of static pressure change on the calibrated span,
with transmitter re-zeroed at line pressure.
Specification – physical
(Refer to ordering information sheets for variant availability related to specific model or versions code)
Materials
Process isolating diaphragms (*)
AISI 316 L ss; AISI 316 L ss gold plated; Tantalum;
Hastelloy®
C-276; Hastelloy®
C-276 on AISI 316L ss gasket
seat.
Process flanges, adapters, plugs and drain/vent valves (*)
AISI 316 L ss (1); Hastelloy®
C-276 (2);
Kynar®
(PVDF insert in AISI 316 ss flange).
AISI 316 L ss with flushing connections for high side of
flange mounted version.
Sensor fill fluid
Silicone oil; Inert fill (Galden®
).
Mounting bracket (**)
Zinc plated carbon steel with chrome passivation; AISI 316
ss; AISI 316 L ss.
Gaskets (*)
Viton®
; PTFE.
Sensor housing
AISI 316 L ss.
Bolts and nuts
AISI 316 ss bolts Class A4–80 and nuts Class A4–70
per ISO 3506;
AISI 316 ss bolts and nuts Class A4–50 per ISO 3506, in
compliance with NACE MR0175 Class II (std. static only).
Plated alloy steel bolts per ASTM-A-193-77a grade B7M and
nuts per ASTM A194/A 194 M-90 grade 2HM, in compliance
with NACE MR0175 Class II.
Electronic housing and covers
Aluminium alloy (copper content ≤ 0.3 %) with baked
epoxy finish (colour RAL9002); AISI 316 L ss.
Covers O-ring
Buna N.
Local adjustments (zero, span and write protect)
For Standard HART version:
• Internal for zero and span (on connection board)
• External non-intrusive for zero, span and write protect
in glass filled polyphenylene oxyde, removable (code
R1).
For all other versions:
• External non-intrusive for zero, span and write protect
in glass filled polyphenylene oxyde, removable.
Plates
Transmitter nameplate: AISI 316 ss screwed to the
electronics housing.
Certification plate and optional tag/calibration plate: selfadhesive attached to the electronics housing or AISI 316 ss
fastened to the electronics housing with rivets or screws.
Optional wired-on customer data plate: AISI 316 ss.
Laser printing on metal or thermal printing on selfadhesive.
For AISI 316 L ss housing it is mandatory to select option
I2 or I3 for plates in AISI 316 ss.
Optional wired-on customer data plate can be populated
with customized data (4 lines of 32 characters 4 mm/0.16
in high).
Customized data have to be provided separately: in case
of no data, the wired-on plate will be delivered blank.
Calibration
Standard: at maximum span, zero based range, ambient
temperature and pressure;
Optional: at specified range and ambient conditions.
Device is delivered with a standard 4-point calibration
record
(*) Wetted parts of the transmitter.
(**)U-bolt material: high-strength alloy steel or AISI 316 L ss;
bolts/nuts material: high-strength alloy steel or AISI 316 ss.
(1) Supplied as AISI 316 L or as ASTM A351 Grade CF-3M
(2) Supplied as Hastelloy C-276 or as ASTM A494 alloy
CW-12MW
Optional extras
Mounting brackets (code Bx)
For vertical and horizontal 60mm. (2in) pipes or wall
mounting. (EXCEPT U-BOLT ASSEMBLY WHICH IS NOT
SUPPLIED FOR WALL MOUNTING, PARTS ARE THE SAME
FOR PIPE AND WALL BRACKET OPTIONS, AS PER
RELEVANT MATERIALS).
Display (code Lx)
L1/L5: 4 position (90° steps) user orientable
LS: fixed position
Optional plates (code Ix)
Code I1: AISI 316 ss wired-on plate with laser printed
customized data (4 lines of 32 characters with 4 mm/0.16
in. height).
Code I2: AISI 316 ss plate with laser printed tag (up to 32
characters - long) and calibration details (up to 32
characters: lower and upper range values and engineering
unit) fixed onto transmitter housing.
Code I3: complete set of AISI 316 ss plates (see I1 and I2).
Surge protection (code S2)
Cleaning procedure for oxygen service (code P1)
Test Certificates (test, design, calibration, material
traceability) (codes Cx and Hx)
Tag and manual language (codes Tx and Mx)
Manifold mounting (code A1)
Factory mounting and pressure test of ABB M26
manifolds.
Process connections
on flanges: 1/4 in. – 18 NPT on process axis
on adapters: 1/2 in. – 14 NPT on process axis
centre distance (266DSH): 54 mm. (2.13 in.) on flange;
51, 54 or 57 mm. (2.01, 2.13 or 2.24 in.) as per adapters
fittings
fixing threads: 7/16 in. – 20 UNF at 41.3 mm centre
distance
High pressure side of flange mounted version (*):
2 in. or 3 in., ASME Class 150 or Class 300 RF;
DN 50 or DN 80, PN 16 or PN 40 to EN 1092-1 Type B1
(*) Bolts and nuts, gasket and mating flange supplied by customer.
Electrical connections
Two 1/2 in. – 14 NPT or M20x1.5 threaded conduit entries,
direct on housing. Only M20x1.5 for WirelessHART with
one port used for antenna.
One certified stainless steel plug (supplied loose with
thread according to housing entries) available as option.
Terminal block
HART version: three terminals for signal/external meter
wiring up to 2.5 mm2
(14 AWG), also connection points for
test and communication purposes.
WirelessHART version: connection points for test and
communication purposes; additional fast connection for
external harvesting unit.
Fieldbus versions: two terminals for signal wiring (bus
connection) up to 2.5 mm2
(14 AWG)
Grounding
Internal and external 6 mm2 (10 AWG) ground termination
points are provided.
Mounting position
Transmitter can be mounted in any position.
Electronics housing may be rotated to any position. A
positive stop prevents over travel.
Mass (without options)
4 kg approx (8.8 lb) for standard static and gauge
versions;
7 to 11 kg approx (16 to 24 lb) for flange mounted version;
add 1.5 kg (3.3 lb) for AISI housing.
Add 650 g (1.5 lb) for packing.
Packing
Carton 27 x 24 x 20 cm approx (11 x 10 x 8 in.);
Carton 35 x 33 x 35 cm approx (14 x 13 x 14 in) for flange
mounted version
Specification – configuration
Transmitter with HART communication
and 4 to 20 mA
Standard configuration
Transmitters are factory calibrated to customer's
specified range. Calibrated range and tag number are
stamped on the tag plate. If a calibration range and tag
data are not specified, the transmitter will be supplied
with the plate left blank and configured as follows:
Engineering Unit kPa
4 mA Zero
20 mA Upper Range Limit (URL)
Output Linear
Damping 1 s
Transmitter failure mode Upscale
Tag Blank (up to 32 alphanumeric
characters - long;
only 8 visible on display - short)
Optional LCD display PV in kPa; output in mA and
in percentage on bargraph
Any or all the above configurable parameters, including
Lower range–value and Upper range-value which must be
the same unit of measure, can be easily changed using the
HART hand–held communicator or by a PC running the
configuration software with DTM for 266 models. The
transmitter database is customized with specified flange
type and material, O–ring and drain/vent materials and
meter code option.
Tag and Calibration
Tag and/or specific calibrated span can be requested
when configuring the device.
Two tag types are available: Short Tag and Long Tag.
See below table for details about tag type applicability /
presence:
Type Max Length On Display On CertificationOn Device Label
Short Tag 8 digits YES YES NO
Long Tag 32 digits NO YES YES
In case no specific indication will be given about the tag
type, data will be considered as Long Tag by default.
In case tag is required on the optional wired-on customer
data plate (optional digits I1, I3) specific indication needs
to be given.
Custom configuration (option N6)
The following data may be specified in addition to the
standard configuration parameters:
Descriptor 16 alphanumeric characters
Message 32 alphanumeric characters
Date Day, month, year
For HART protocol available engineering units of pressure
measure are :
Pa, kPa, MPa
inH2O@4 °C, mmH2O@4 °C, psi
inH2O@68 °F, ftH2O@68 °F, mmH2O@68 °F
inHg, mmHg, Torr
g/cm2
, kg/cm2
, atm
mbar, bar
These and others are available for PROFIBUS and
FOUNDATION Fieldbus.
Transmitter with WirelessHART
communication
Standard configuration
Transmitters are factory calibrated to customer's
specified range. Calibrated range and tag number are
stamped on the tag plate. If a calibration range and tag
data are not specified, the transmitter will be supplied
with the plate left blank and configured as follows:
Engineering Unit kPa
Output scale 0 % Lower Range Limit (LRL)
Output scale 100 % Upper Range Limit (URL)
Output Linear
Update time 16 s
Tag Blank (up to 32 alphanumeric
characters - long;
only 8 visible on display - short)
Optional LCD display PV in kPa; output in
percentage on bargraph
Any or all the above configurable parameters, including
Lower range–value and Upper range-value which must be
the same unit of measure, can be easily changed using the
HART hand–held communicator or by a PC running the
configuration software with DTM for 266 models. The
transmitter database is customized with specified flange
type and material, O–ring and drain/vent materials and
meter code option.
Custom configuration (option N6)
The following data may be specified in addition to the
standard configuration parameters:
Descriptor 16 alphanumeric characters
Message 32 alphanumeric characters
Date Day, month, year
Transmitter with PROFIBUS PA
communication
Standard configuration
Transmitters are factory calibrated to customer’s
specified range. Calibrated range and tag number are
stamped on the tag plate. If a calibration range and tag
data are not specified, the transmitter will be supplied
with the plate left blank and configured as follows:
Measure Profile Pressure
Engineering Unit kPa
Output scale 0 % Lower Range Limit (LRL)
Output scale 100 % Upper Range Limit (URL)
Output Linear
Hi-Hi Limit Upper Range Limit (URL)
Hi Limit Upper Range Limit (URL)
Low Limit Lower Range Limit (LRL)
Low-Low Limit Lower Range Limit (LRL)
Limits hysteresis 0.5 % of output scale
PV filter 0 s
Address (set by local key) 126
Tag PI000 (up to 32 alphanumeric
characters; only 8 visible on
display)
Optional LCD display PV in kPa; output in percentage
on bargraph
Any or all the above configurable parameters, including
the range values which must be the same unit of measure,
can be easily changed by a PC running the configuration
software with DTM for 266 models.The transmitter
database is customized with specified flange type and
material, O–ring and drain/vent materials and meter code
option.
Custom configuration (option N6)
The following data may be specified in addition to the
standard configuration parameters:
Descriptor 32 alphanumeric characters
Message 32 alphanumeric characters
Date Day, month, year
...Specification – configuration
Transmitter with FOUNDATION Fieldbus
communication
Standard configuration
Transmitters are factory calibrated to customer’s
specified range. Calibrated range and tag number are
stamped on the tag plate. If a calibration range and tag
data are not specified, the transmitter will be supplied
with the plate left blank and the analog input function
block FB1 is configured as follows:
Measure Profile Pressure
Engineering Unit kPa
Output scale 0 % Lower Range Limit (LRL)
Output scale 100 % Upper Range Limit (URL)
Output Linear
Hi-Hi Limit Upper Range Limit (URL)
Hi Limit : Upper Range Limit (URL)
Low Limit Lower Range Limit (LRL)
Low-Low Limit Lower Range Limit (LRL)
Limits hysteresis 0.5 % of output scale
PV filter time 0 s
Tag PI000 (up to 32 alphanumeric
characters; only 8 visible on
display)
Optional LCD display PV in kPa; output in percentage
on bargraph
The analog input function block FB2 and FB3 are
configured respectively for the sensor temperature
measured in °C and for the static pressure measured in
MPa.
Any or all the above configurable parameters, including
the range values, can be changed using any host
compliant to FOUNDATION fieldbus. The transmitter
database is customized with specified flange type and
material, O–ring and drain/vent materials and meter code
option.
Custom configuration (option N6)
The following data may be specified in addition to the
standard configuration parameters:
Descriptor 32 alphanumeric characters
Message 32 alphanumeric characters
Date Day, month, year
Dimensions
(not for construction unless certified) – dimensions in mm. (in.)
