ISCM DESIGN
ISCM modules support I/A Series and HART™
communications over the standard HDLC fieldbus.
They have a compact design, with a rugged exterior
for physical protection of the electronics in
environments with a minimum ingress protection of
IP 54. P+F-provided enclosures specially designed
for mounting of the P+F intrinsically safe I/O modules
provide the appropriate level of environmental
protection (for Zone 2/Div 2 or Zone 1 applications).
The ISCM and the supported P+F I/O modules can
be removed/replaced from the base or extension unit
without removing power. Light-emitting diodes (LEDs)
incorporated into the front of the ISCM and I/O
modules indicate module status.
HIGH RELIABILITY
In redundant ISCM configurations, the redundancy of
the module pair provides very high subsystem
availability time.
Either ISCM may be hot-swapped without upsetting
input or output communications to the other module,
or removing power from either module.
IS/IO SYSTEM CONFIGURATION
REQUIREMENTS
The requirements in Table 1 must be met to ensure
proper system operation:
Table 1. IS/IO System Configuration Requirements

Table 1. IS/IO System Configuration Requirements (Continued)

(a) Be aware that Zone 1 and Zone 2 installations have other special requirements for power consumption and dissipation. These are
observed automatically by P+F’s ATEX audited factories. Other panel builders would have to obtain their own certificates equivalent to
P+F’s PTB07ATEX1075 for Zone 1 and PF08CERT1234 for Zone 2.
(b) Windows XP and Windows Server 2003 workstation operating systems only.
PSS 21H-2Y6 B4
Page 6
MODULAR UNIT MOUNTING
The ISCM mounts on supported P+F-supplied LBstyle or FB-style base or extension units, which
accommodate different quantities of P+F I/O
modules, depending on the application.
The ISCM base unit includes signal connectors for
the ISCM and P+F I/O modules, redundant
independent power connections, and 2 Mbps HDLC
module Fieldbus connections for communications to
the I/A Series FCP270 or ZCP270
Redundant ISCMs must be located in the left-most
two slots in the LB-style base units. One each of the
FB-style ISCMs are located in the main and
redundancy units.
Table 2 lists the available ISCM modules and
available support equipment.
Table 2. ISCM Modules and Support Equipment

Zone 2 (LB-Style) P+F Intrinsically Safe Units and Support Equipment To Support the ISCM Table 3 lists the supported Zone 2 (LB-Style) I/O base, redundancy and extension units and their associated enclosures and power supplies.
Table 3. P+F Intrinsically Safe Units and Support Equipment To Support the ISCM (Zone 2, LB-Style)

Zone 1 (FB-Style) P+F Intrinsically Safe Units and Support Equipment To Support the ISCM
Table 4 lists the supported Zone 1 (FB-Style) I/O base, redundancy and extension units and their associated
enclosures and power supplies.
Table 4. P+F Intrinsically Safe Units and Support Equipment To Support the ISCM (Zone 1, FB-Style)

(a) Visit the IPS Portal (www.ips.invensys.pepperl-fuchs.com) to order this equipment as it does not have an Invensys part number.