Distributed Control Interface (DCI) block types:

The DCI blocks are configured just like other Foxboro DCS control blocks. The DCI
blocks address and read/write data from/to the addressed field device.
Standard, Rugged Design
The FBM232 has a rugged extruded aluminum exterior for physical and electrical
protection of the circuits. Enclosures, specially designed for mounting the FBMs,
provide various levels of environmental protection, up to Class G3 harsh
environments per ISA Standard S71.04.
Modular Baseplate Mounting
The module mounts on a Modular Baseplate, which accommodates up to four or eight
FBMs. The Modular Baseplate is either DIN rail mounted or rack mounted. The
Modular Baseplate includes signal connectors for the FBMs, provides connections for
independent dc power supplies, I/O cable connections, and 2 Mbps Module Fieldbus
connections.
Easy Removal/Replacement
The module can be removed or replaced without removing power.
Regulatory Compliance,
Product Safety
• Underwriters Laboratories (UL) for U.S. and Canada
UL/UL-C listed as suitable for use in UL/UL-C listed Class I, Groups A-D; Division
2; temperature code T4 enclosure based systems when connected to specified
Foxboro DCS processor modules as described in the Standard and Compact 200
Series Subsystem User's Guide (B0400FA).
Communications circuits also meet the requirements for Class 2 as defined in
Article 725 of the National Electrical Code (NFPA No.70) and Section 16 of the
Canadian Electrical Code (CSA C22.1). Conditions for use are as specified in the
Standard and Compact 200 Series Subsystem User's Guide (B0400FA).
• European Low Voltage Directive 2014/35/EU and Explosive Atmospheres (ATEX)
Directive 2014/34/EU
DEMKO certified as Ex nA IIC T4 for use in certified Zone 2 enclosure when
connected to specified processor modules as described in the Standard and
Compact 200 Series Subsystem User's Guide (B0400FA).
• Marine Certification
ABS Type Approved and Bureau Veritas Marine certified for Environmental
Category EC31.
Calibration
Requirements
Calibration of the module is not required.
Environmental Specifications