Multilin F650
Cost effective protection, automation and control of distribution feeders
The Multilin F650 has been designed for the protection, control and automation of feeders or related applications.
The Multilin F650 feeder protection relay provides high speed protection and control for feeder management and bay control applications, and comes with a large LCD and single line diagrams that can be built for bay monitoring and control for various feeder arrangements including ring-bus, double breaker or for breaker and half.

Key Benefits
Comprehensive and flexible protection and control device for feeder applications
Increased system uptime and improved stability with load shedding and transfer schemes
Advanced automation capabilities for customized protection and control solutions
Human machine interface (HMI) with graphical LCD, programmable buttons, and easy keys for selecting setting menus, and submenus
Reduced replacement time with modular draw-out construction
Reduced troubleshooting time and maintenance costs with IEEE 1588 (PTP), IRIG-B and SNTP time synchronization (configuration of two different SNTP masters), event reports, waveform capture, and data logger
Simplified system integration with communications supporting serial and Ethernet interfaces as well as multiple protocols
Embedded IEC® 61850 protocol (and support for edition 2), IEC 60870-5-103/104. IEC 62439/PRP/HSR, IEEE 802.1D/RSTP
Proven interoperability and KEMA 61850 Edition 2 certified
Applications
Primary or back-up protection and control for feeders on solidly grounded, high impedance grounded or resonant grounded systems
Bus blocking/Interlocking schemes
High-speed fault detection for arc flash
Throw over schemes (bus transfer scheme applications)
Load shedding schemes based on voltage and frequency elements
Distributed Generation (DG) interconnect protection, including active and passive anti-islanding
Key Features
Time, instantaneous & directional phase, neutral, ground and sensitive ground overcurrent
Manual close with cold load pickup control, Forward Power and Directional Power Units
Load encroachment supervision
Wattmetric ground fault detection
Positive and negative sequence based over/under voltage elements
2nd Harmonic restraint
CT Supervision
Four-shot autorecloser with synchronism check
Trip circuit supervision, breaker control and
breaker failure
Frequency protection (rate of change and six
stages of under and over frequency)
Broken conductor and locked rotor
Programmable digital inputs and outputs
6 Setting Groups

The F650 feeder protection relay provides high speed protection and control for feeder management and bay control applications, including:
25 Synchrocheck
27/27X Bus/Line Undervoltage
32 Sensitive Directional Power
32FP Forward Power
32N Wattmetric zero-sequence directional
46 Negative Sequence Time Overcurrent
47 Negative Sequence Voltage
48 Blocked Rotor
49 Thermal Image - overload protection
50 BF Breaker Failure
50PH/PL Phase Instantaneous Overcurrent (High/Low)
50N Neutral Instantaneous Overcurrent
50G Ground Instantaneous Overcurrent
50SG Sensitive Ground Instantaneous Overcurrent
50IG Isolated Ground Instantaneous Overcurrent
51N Neutral Time Overcurrent
51G Ground Time Overcurrent
51SG Sensitive Ground Time Overcurrent
51PH/V Voltage Restraint Phase Time Overcurrent
51PL/V
59/59X Bus/Line Overvoltage
59NH/NL Neutral Overvoltage - High/Low
67P Phase Directional Overcurrent
67N Neutral Directional Overcurrent
67G Ground Directional Overcurrent
67SG Sensitive Ground Directional Overcurrent
79 Autorecloser
81 U/O Under/Over Frequency Broken Conductor Detection
81R Frequency Rate of Change
VTFF VT Fuse Failure Detection
Load Encroachment
Key Features
Fault locator, fault and event recorder
Comprehensive breaker monitoring
High resolution oscillography and Data Logger, with programmable sampling rate
Metering: V, I, Hz, W, VA, PF
Demand: Ia, Ib, Ic, Ig, Isg, I2. MW, MVA
Breaker Arcing Current (I2t)
Fault Locator
Monitoring & Metering
The F650 provides advanced monitoring and metering that includes:
Current Transformer Failure
In event of abnormal behaviour of the CT or a loss of phase the F650 detects a change in zero sequence current to initiate a CT failure event and an output that can be used to block critical protection functions.
This feature can be inhibited either by zero sequence voltage, ground /sensitive ground current.
2nd harmonic inhibit
The F650 provides 2nd harmonic detection that can be used to block sensitive elements, especially during transformer energization.
The setting can be based on any phase, any two phases, all three phases or an average of the 3 phases.