DCS; Industrial control system
NameDescriptionContent
NEW CENTER
Current Location:

SHINKAWAVM-5 SERIES MONITOR MODEL VM-5K DUAL VIBRATION MONITOR INSTRUCTION MANUAL

From:SHINKAWA | Author:LIAO | Time :2025-08-25 | 256 Browse: | Share:

7-2 BASIC KEY OPERATIONS 

• (SET) key : Used to change the display mode of the LCD display and to 

finalize input. 

• (UP) key : Used to change parameters and increment set values. 

• (DOWN) key : Used to change parameters and decrement set values. 

• (RESET) key : Used to reset alarms set to self-holding. 

• Alarm reset is not possible until the output condition has been released. 

• An alarm lamp set flashing by the First-out Display function cannot be reset. 

(Reset by shorting between the RES and COM terminals.) 

• (CHECK) key : The CHECK key is used to adjust the gain while changing set 

values with the UP and DOWN keys. 

For example, if the CHECK key is pressed while the value 0.1 

appears on the MEAS 2 LED display, a value corresponding to the 

measurement range × 0.1 can be set. 

• Each operation of the CHECK key will multiply the multiplier by 10. 

 : When the CHECK key is pressed during normal monitoring, the 

monitor will go through self-diagnosis in the following sequence : 

(1) LCD, LED display test (all lamps light) 

(2) Self-diagnosis 

(3) Display of diagnosis result (Normal) (Abnormal) 

• The diagnosis result for CH1 is indicated on the MEAS 1 display and that for CH2 on 

the MEAS 2 display. 

• If an abnormality is found as a result of self-diagnosis, the error content is displayed 

after approx. 3 seconds. 

• In case of more than one abnormality, error contents are displayed at 3-second 

intervals. 

 Error content display 

Check items Display 

CH1 OK (input abnormal) alarm HIGH 

CH2 OK (input abnormal) alarm HIGH 

CH1 OK(input abnormal) alarm LOW 

CH2 OK(input abnormal) alarm LOW 

CH1 A/D input 5V side over 

CH2 A/D input 5V side over 

CH1 A/D input 0V side over 

CH2 A/D input 0V side over 

For safe operation..... 

Thank you for using our VM-5 Series Monitor. SHINKAWA Sensor Technology applies strict quality control 

and inspections to ensure the high reliability of its products. 

This instruction manual contains descriptive information, specifications, and operating, setting, and adjusting 

procedures. 

Please study the contents of this manual and related manuals thoroughly before installing or operating the 

equipment, and keep it handy for future reference. 

"Safety Conventions" 

Please thoroughly study the following section entitled "Safety Conventions" before operating the 

equipment. 

The safety symbols explained in this section are placed outside the left margin next to the text to which they 

apply. 

This unit is designed for use by specialists or persons thoroughly familiar with the field. 

Make sure that the end user receives the Instruction Manual delivered with this unit. 

Before use..... 

When the unit is received, inspect it for damage suffered in transport and check 

whether it is the item you ordered. In the unlikely event that it was damaged in transport 

or does not function according to specifications, please contact the SHINKAWA Office 

or dealer nearest you. 

Store the unit under the ambient conditions given in the specification. 

Avoid places where it is exposed to high humidity or corrosive gases. 

Make it a rule to follow the instructions given in this manual. 

This manual contains important information designed to prevent personal injury and property damage, and 

ensure safe operation of the equipment. 

Familiarize yourself with the signs and symbols explained below before proceeding to read the manual, and 

observe the instructions given. 

■ Explanation of signs

Symbols Explanation 

 WARNING Indicates a potentially hazardous situation which, if not avoided, could result in death 

or serious injury. 

 CAUTION Indicates a potentially hazardous situation which, if not avoided, may result in minor 

or moderate injury. It may also be used to permit for property-damage-only accidents. 

◊ "Serious injury" refers to such injuries as loss of eyesight, injuries, burns (due to heat or cold), electric 

shock, fractures, and poisoning, that have permanent aftereffects and require hospitalization or long-term 

outpatient treatment. 

◊ "Moderate or minor injury" refers to such injuries as burns and electric shock that do not require 

hospitalization or long-term outpatient treatment. "Property-damage-only accidents" refers to 

consequential damage related to destruction of property and damage to the equipment. 

■ Explanation of symbols

Symbols Explanation 

 Indicates a prohibited action.

Details are given in the text next to the symbol. 

 Indicates a mandatory action.

Details are given in the text next to the symbol. 

To ensure safe use of this equipment, strictly observe the safety precautions provided in this manual, as well 

as installation methods and methods of use stipulated by laws and regulations. SHINKAWA Sensor 

Technology will not be liable for damage, etc. due to methods of use contravening to the instructions provided 

here. 

■ Safe use 

WARNING

Make sure to ground. 

May cause electric shock or malfunction.

Make sure to turn the power off before any wiring work.

Will cause electric shock. 

CAUTION

Connect the input signal within the voltage range described in the 

specification to the input terminals. 

Will cause damage and malfunction of the instrument. 

Install the monitor unit and its relay module unit in the same location in the 

instrument rack. 

Will cause damage to the instrument and malfunction of the turbine monitoring system. 

A printed circuit board and electronic products may receive damage with 

the static electricity of a human body. 

Touch the metal part once and discharge your static electricity before 

dealing with it. 

Will cause damage and malfunction of the instrument. 

Do not touch parts and soldered surfaces of the monitor unit. 

Will cause damage and malfunction of the instrument. 

The monitor unit is a precision instrument. 

Take care not to expose it to excessive shock or vibration. 

Do not change the parameter settings during operation. 

May cause unexpected alarm output. 

Do not pull out the face plate during operation. 

Will cause damage to the instrument and malfunction of the turbine monitoring system. 

Do not measure insulation resistance and dielectric strength other than 

those at places specified. 

Will cause damage to the instrument. 

Do not remodel this monitor unit without permission. 

Otherwise the guarantee can not be made.

■ EMC(Electro-magnetic compatibility) 

The EMC of each VM-5 Series monitor is evaluated by various noise tests. 

However, its characteristics may vary with on environmental conditions such as the magnitude of noise, 

ambient temperature, humidity and the arrangement of equipment. 

For the above reason, when operating the monitor, please observe the following CAUTION. 

 CAUTION

The monitor unit should be operated by specialists or personnel who have 

knowledge of it. 

When a shielded cable is used, the length of the unshielded cable section 

should be less than 100mm (3.937in REF.). 

For each relay used near this monitor unit, devices related to this monitor 

unit or signal cables connecting the monitor unit and these devices, install 

a surge killer.

Firmly tighten each screw used for mounting each unit. In additional, 

always close the face plate for the monitor unit, then fix it with knurled 

screws. 

In order to prevent the system from its malfunction when the monitor unit 

fails, provide the systematic interlock function.

Do not wire input signal cables in parallel with control and power cables. 

It is recommended that separated wire ducts be used for these cables.

Do not use any radio equipment near the monitor unit. 

■ Noise filter 

Noise transmitted through in each cable may be rejected to some extent by inserting a ferrite core in the cable 

(note 1). 

If the cable passes through noisy surroundings, it is recommended that such a noise prevention device is used.

GENERAL INFORMATION 

OVERVIEW 

This is a highly reliable dual channel vibration monitor which monitors the shaft vibration of 

rotating machinery. 

Both a 10-slot rack mounting type and a single-unit independent type with a built-in power supply 

are available so that it can respond flexibly to any system design from medium and small scale 

rotating machinery to TSI. The monitor accepts signals detected by a transducer and displays them 

on LCD. 

It is also possible to set ALERT and DANGER alarm levels independently to detect machine 

failures early on and inform the operator of these failures. It has a built-in self-diagnostic function 

to inform the operator of input transducer failures, thereby preventing rotating machinery from 

false shutdowns. 

FEATURES 

• Conforms to API St’d 670 

• The monitor is available as a single unit independent type or a rack mounting type. 

• Has a self-diagnostic function. 

• Allows the operator to change each setting even in the field. 

• Important information such as measured value, alarm set value and gap voltage is normally 

displayed. 

• Can isolate recorder output (option). 

• LED display / contact output (DANGER / ALERT alarm). 

• LED display / contact output (Input abnormal alarm). 

• For alarm output wiring proceed as described in the instruction manuals for the 

VM-5G Single Unit Instrument Rack and VM-5Y Relay Module Unit used in 

combination with this monitor unit. 

• If megger test is made on the signal cable between transducer and monitor, 

disconnect the cable from transducer and monitor. 

Be sure to discharge the charged electric load before connecting the cable to the 

transducer and monitor. 

If this caution is not adhered to, the transducer and monitor could be damaged. 

FIRSTOUT DISPLAY 

• Installation in VM-5H3, 5W1 Instrument Rack 

Causes the alarm lamp of the channel that first output alarm to flash. 

• Installation in VM-5G Single Unit Instrument Rack 

Causes the lamp of the alarm first output to flash.

For details refer to 7. PARAMETER SETTING on page 19. 

• An alarm lamp set flashing by the First-out Display function cannot be reset by 

pressing the RES (RESET) key. 

Reset by shorting between the RES and COM terminals. 

• It is necessary to keep short circuit of the terminals for more than one (1) second to 

operate these functions. 

5-9 SEQUENCE FUNCTION 

To prevent alarm output due to excessive vibration generated during starting and stopping of the 

machine, this function expands the DANGER alarm and ALERT alarm set ranges by shorting 

between the SEQ. and COM terminals. 

• The machine is not protected if the alarm set value exceeds 110% of the monitor 

range due to operation of the sequence circuit. 

• It is necessary to keep short circuit of the terminals for more than one (1) second to 

operate these functions. 

5-10 BYPASS FUNCTION 

Used to disable alarm output while setting the alarm parameters, or during maintenance/inspection 

work. The alarm BYPASS lamp flashes or lights during this operation. Set by turning the BYPASS 

switch to ON. 

• While BYPASS FUNCTION is in operation, the machine is not protected. 

5-10-1 DANGER BYPASS 

Cuts off DANGER alarm. While cut off, the DANGER alarm and BYPASS lamps are flashing. 

This function is activated by means of the DANGER BYPASS switch. For details refer to 7. 

PARAMETER SETTING on page 19. 

• If mounted in the VM-5H3 or VM-5W1 Instrument Rack, all units in the instrument 

rack can be set collectively to DANGER BYPASS. 

For details refer to VM-5H3 or VM-5W1 Instrument Rack instruction manual. 

5-10-2 CH1 BYPASS 

DANGER alarm, ALERT alarm, OK alarm, display and recorder output of CH1 are cut off. 

While cut off, the OK lamp goes off and the BYPASS lamp lights. 

This function can be activated by means of the CH1 BYPASS switch. 

For details refer to 7. PARAMETER SETTING on page 19. 

5-10-3 CH2 BYPASS 

DANGER alarm, ALERT alarm, OK alarm, display and recorder output of CH2 are cut off. 

While cut off, the OK lamp goes off and the BYPASS lamp lights. 

This function can be activated by means of the CH2 BYPASS switch. 

For details refer to 7. PARAMETER SETTING on page 19. 

5-11 POWER ON TIMER MODE 

Operates for approx. 5sec. after the power is turned on. (for approx. 25 sec. in case of pk-pk 

detection). In this mode, all alarm functions are disabled and the BYPASS and OK lamps flash. 

5-12 ALARM RELAY MODE 

Each alarm contact can be set to either normally de-energized or normally energized. 

Alarm contact operation 

Monitor power Monitor power ON 

OFF Normal state Alarm state 

NO contact NORMALLY DE-ENERGIZED OPEN OPEN CLOSE 

NO contact NORMALLY ENERGIZED OPEN CLOSE OPEN 

NC contact NORMALLY DE-ENERGIZED CLOSE CLOSE OPEN 

NC contact NORMALLY ENERGIZED CLOSE OPEN CLOSE 

For details refer to 7. PARAMETER SETTING on page 19.

5-13 ALARM RESET MODE 

The automatic reset of all alarm output and alarm lamps can be set when the measured value or 

input signal return to normal. In addition to above, the self-holding function can be also set for 

each alarm output that holds the alarm condition until reset by setting RES key (inside of the front 

panel) or by shorting between RES and COM terminal. 

• Alarm reset is not possible until the output condition has been released. 

• It is necessary to keep short circuit of the terminals for more than one (1) second to 

operate these functions. 

For details refer to 7. PARAMETER SETTING on page 19.

5-14 MONITOR OUTPUT 

For vibration analysis, the vibration waveform signal is output from the BNC connector on the 

monitor front panel and buffer output terminal on the rear panel (VM-5G Single Unit Instrument 

Rack, VM-5Y Relay Module Unit) via a buffer amplifier. 

5-15 RECORDER OUTPUT 

An analog signal proportional to the vibration value is output from the terminal block. 

5-16 SELF-DIAGNOSTIC FUNCTION 

Any failures in the input system, such as sensor short-circuit or imperfect connections, are detected, 

then an OK alarm is contact-output and (simultaneously), the OK lamp flashes. 

5-17 POWER SEQUENCE 

If mounted in the VM-5G Single Unit Instrument Rack, the secondary power supply can be cut off 

by shorting between the P-S (POWER SEQUENCE) and COM terminals. 

• This function can be used for pulling out or pulling in the monitor unit at the 

emergency time. However, do not use for long time shorting of more than one (1) 

minute or turning on and off repeatedly. 

Also, the parallel connection for the two (2) or more monitors should not be allowed. 

5-18 TIMED OK CHANNEL DEFEAT 

When on setting, when OK alarm is output, DANGER alarm, ALERT alarm, display, and recorder 

output are disabled. DANGER ALERT, display and recorder output are not disabled, in case of 

excessive signal input from sensor. 

For details refer to 7. PARAMETER SETTING on page 19. 

5-19 SUPPRESSION FUNCTION 

This function can suppress the measurement around zero measurement point of the monitor by the 

effect of the piping vibration or electric noise, etc. during the machine stopping. 

The suppression can be set at 0.0 to 10.0 % (0.1% step) of the monitor range. 

ex.) If the suppression is set at 2.0%, monitor measurement less than 2.0% shall be output as 0.0%

2 DESCRIPTION OF PARTS 1 LCD display This LCD display serves for display of measured values, alarm set values, sensor set gap voltage value and other set values. 2 DANGER alarm lamp Lit when DANGER alarm is output. 3 ALERT alarm lamp Lit when ALERT alarm is output. 4 OK lamp Flashes (steady light in normal condition) when OK (input abnormal) alarm is output. 5 BYPASS lamp Flashes during DANGER bypass and lights during CHANNEL bypass. 6 Monitor output connector This is a BNC output connector for connection of an oscilloscope to observe the waveform, or for output to other devices such as an analyzer. The input signals from the transducers are output through a buffer amplifier. • Make sure to insulate the monitor output against earth. If not insulated, a 2-point earth system results, which may cause noise interference. 7 Name plate 8 Tag, Ser. No. plate The TAG NO. and SER.NO. are entered on this plate. 9 LCD board 10 Slide frame 11 Main board frame 12 Main board 13 DIN connector (64pin) Connector for connection to the VM-5G Single Unit Instrument Rack or VM-5H3 or VM-5W1 Instrument Rack.

1) 1BY (CH1 BYPASS) Switch 

"ON" To select CH1 BYPASS function. 

"OFF" Normal monitoring 

2) 2BY (CH2 BYPASS) Switch 

"ON" To select CH2 BYPASS function. 

"OFF" Normal monitoring 

3) DBY (DANGER BYPASS) Switch 

"ON" To select DANGER BYPASS function. 

"OFF" Normal monitoring 

4) MS1 (MODE-SELECT1) Switch (normally OFF) 

• Set normally to “OFF”. Parameter setting mode is disabled. 

5) MS2 (MODE-SELECT2) Switch 

“ON” 

For setting the alarm reset mode, alarm delay time, alarm relay mode, first-out display, 

and timed OK channel defeat. 

Also enables setting the address when used in combination with the VM-5H3 or 5W1 

Instrument Rack and VM-5P1,2 Communication/Phase Marker Unit or VM-53 Dual 

Communication Unit. To PARAMETER SETTING 1. 

“OFF” 

For changing the set values for DANGER alarm and ALERT alarm, and GAP ALARM, 

and adjusting measured value and recorder output zero span. 

To PARAMETER SETTING 2.


  • EMERSON P188.R2 Industrial interface module
  • EMERSON VE3008 CE3008 KJ2005X1-MQ1 12P6381X042 MQ Controller
  • EMERSON TPMC917 4MB SRAM with Battery Backup and 4 Channel RS232
  • EMERSON P152.R4 Multifunctional module
  • EMERSON DA7281520 P152 Processor board
  • EMERSON PR6423/008-110 8mm Eddy Current Sensor
  • EMERSON PR6423/000-131 8mm Eddy Current Sensor
  • EMERSON MVME61006E-0163R VMEbus Single-Board Computer
  • EMERSON Ovation 5X00453G01 Remote I/O Node Controller Module
  • EMERSON 5X00070G04 Analog input
  • EMERSON Ovation 5X00070G01 Analog Input Module
  • EMERSON Ovation 5X00790G01 Compact Controller Module
  • EMERSON 5X00846G01 HART analog output module
  • EMERSON 1C31113G01 Digital output module (5-60VDC)
  • EMERSON KJ4110X1-BA1 I/O terminal module
  • EMERSON CSI3125 A3125/022-020 Shaft-Vibration Monitor
  • EMERSON 5X00273G01 Digital output module
  • EMERSON KJ4001X1-NB1 12P3368X012 REV:E 1-Wide I/O Carrier Extender Left
  • EMERSON KJ4001X1-NA1 12P3373X012 REV:C 1-Wide I/O Carrier Extender Right
  • EMERSON A6312/06 Speed and Key Monitor
  • EMERSON KJ4001X1-BE1 8-Wide I/O Carrier
  • EMERSON KJ2005X1-MQ1 KJ2005X1-MQ2 13P0072X082 MQ Controller
  • EMERSON 5X00226G03 - Ovation™ I/O Interface Controller, Electronics Module
  • EMERSON PR6423/00R-010+CON031 Vibration sensor
  • EMERSON 9199-00002 A6120 Control Module
  • Emerson Ovation 1C31234G01 - Ovation™ 16 Channel Compact Digital Input
  • Emerson Ovation KJ3002X1-BF1 12P1732X042 Controller module
  • Emerson Ovation 5X00226G01 I/O Interface Module
  • Emerson Ovation™ Controller Model OCR1100(5X00481G04/5X00226G04)
  • Emerson Ovation 5X00499G01 Digital Input 24Vdc Single 32CH
  • Emerson Ovation 5X00500G01 32-Channel Digital Output Module
  • Emerson ovation VE4001S2T2B4 Analog output card
  • Emerson ovation 5X00501G01 5X00502G01 Ethernet link controller
  • EMERSON A6824R 9199-00098-13 Module
  • EMERSON A6140 9199-00058 Industrial Control Module
  • EMERSON 1C31194G03 Industrial Control Module
  • EMERSON DB1-1 Industrial Control Module
  • EMERSON PMC-IO-ADAPTER I/O module
  • EMERSON L0115012 L0115032 Control module
  • EMERSON PMC-IO-PROZESSOR Process control module
  • EMERSON PMC PROFINET Manage Gigabit Ethernet switches
  • EMERSON A3120022-000 CSI3120 Bearing-Vibration Monitor
  • EMERSON SE3008 KJ2005X1-SQ1 12P6383X032 Controller
  • EMERSON 1000554 Printed circuit board
  • EMERSON PR6423/002-041 Sensor module
  • EMERSON 1C31232G02 Westinghouse control module
  • Abaco TRRM940 Switch
  • Abaco SWE440A Switch
  • Abaco NETernity™ RM984RC Ethernet Switch
  • Abaco NETernity™ GBX411 Ethernet Switch
  • Abaco NETernity™ GBX25
  • Abaco NETernity SWE540A
  • Abaco CP3-GESW8-TM8 Ethernet switch
  • Abaco SWE440S Ethernet switch
  • Abaco SWE450S 100GbE 3U VPX Switch Aligned to SOSA™ Standard
  • Abaco SWE550S 100GbE 6U VPX Switch Aligned to SOSA™ Standard
  • Abaco SPR870A Wideband Digital Receiver/Exciter
  • Abaco SPR507B Serial FPDP XMC/PMC
  • Abaco ICS-1572A Transceiver Module
  • Abaco daq8580 FMV Compression System
  • Abaco VP868 FPGA Card
  • Abaco HPC2812 Rugged 6U VPX High Performance Computer with Dual Intel
  • Abaco VSR347D 3U VPX Rugged Virtual Secure Router
  • Abaco VSR8000 Fully Rugged, COTS System Secure Router
  • Abaco RES3000 Compact, Rugged Ethernet Switches
  • Abaco PMC238 Expansion Card
  • Abaco EXP238 PMC/XMC Expansion Card for XVB603 VME Single Board Computer
  • Abaco VME-REPEAT-A-L VMEbus Repeater Link
  • Abaco VME-4514A VME Analog I/O Input/Output Board
  • Abaco VME-3128A Analog I/O
  • Abaco VME-3125A analog-to-digital Conversion board
  • Abaco VME-3123A VME Analog I/O Input Boards
  • Abaco PMC239/F Analog input/output board
  • Abaco PEX431 Multi-fabric Switch
  • Abaco CPCI-100A-BP 2-slot IndustryPack carrier for 3U CompactPCI
  • Abaco PMC522 Serial Controller
  • Abaco PMC522/FP Serial Controller
  • Abaco VME-2170A Digital Output 32-bit optically isolated
  • Abaco VME-1129 Digital Input Board 128-bit high voltage
  • Abaco IP-OCTALPLUS232 Eight EIA-232 asynchronous serial ports
  • Abaco IP-DIGITAL482 Digital I/O with 48 TTL Channels
  • Abaco PMC523 16-Port Serial Controller
  • EMERSON CE4003S2B1 M-series Traditional I/O
  • EMERSON SE3008 DeltaV™ SQ Controller
  • EMERSON 1C31227G01 - Ovation™ 8 Channel Analog Input
  • EMERSON 1C31224G01 - Ovation™ 8 Channel Analog Input
  • ABB UNS0119A-P,V101 3BHE029154P3 3BHE029153R0101 Digital input
  • ABB 3BDH000050R1 AM811F Battery Module
  • ABB 3ASC25H705-7 Digital output board
  • ABB UDD406A 3BHE041465P201 control board
  • ABB 3BHE014967R0002 UNS 2880B-P,V2: COB PCB Assembled
  • ABB PPC380AE02 HIEE300885R0102 module
  • ABB NU8976A99 HIER466665R0099 Processor Module
  • ABB DIS0006 2RAA005802A0003G Digital Input Module
  • ABB Bailey IMDS003 infi 90 Digital Output Slave Module
  • ABB XO08R1-B4.0 Expand the output relay module
  • ABB VA-MC15-05 Controller module
  • ABB VA-3180-10 Controller module
  • ABB 72395-4-0399123 Excitation module
  • ABB PU516A 3BSE032402R1 Engineering Board - PCI
  • ABB 3BHE044481R0101 3BHE044477P3 PPE091A101 Module
  • ABB UCD224A102 Control unit
  • ABB SNAT603CNT SNAT 603 CNT Motor Control Board
  • ABB SNAT634PAC Drive board
  • ABB UAD149A0011 Servo controller
  • ABB UCD224A103 Industrial controller module
  • ABB 3BHE029154P3/3BHE029153R0101 UNS0119A-P,V101 Processor Module
  • ABB ARCOL 0338 ARCOL 0346 Solid-state motor starter
  • ABB ARCOL 0339 Solid-state motor controller
  • ABB KUC720AE01 3BHB003431R0001 3BHB000652R0001 power control drive board card
  • ABB UFC718AE01 HIEE300936R0101 Main Circuit Interface Board
  • ABB 216DB61 HESG324063R100 Input/output and trip unit module
  • ABB 3HAC17973-1 DSQC332A I/O Unit
  • ABB DSQC509 Circuit board connection unit
  • ABB DSQC346B Control module
  • ABB 3HAB9271-1 Dummy Module Drive System
  • ABB 3HAC5566-1 Robot drive system cable
  • ABB 3HAC9710-1 Heat exchanger unit
  • ABB SPBLK01 Blank Faceplate
  • ABB IMFECI2 Multifunctional control board
  • ABB IMDSO14 ,Digital Slave Output Module
  • ABB 3HAC031683-004 Cable Teach Pendant 30m
  • ABB Millmate Strip Scanner Edge Sensor PMSG12x
  • ABB Millmate Controller 400 PFXA401SF
  • ABB UAC318AE Controller module
  • ABB UNS2980c-ZV4 Medium-voltage control mainboard
  • ABB 3ASC25H204 DAPU100 Control board, I/O
  • ABB 3HAB8101-19 DSQC545A Modules Drive System