Application
Digital controller to automate industrial and process plants for general and more complex control tasks.
Fig. 1: TROVIS 6495-2 Industrial Controller
The TROVIS 6495-2 Industrial Controller is suitable for control
of continuous, on/off or pulsing final control elements (pneumatic actuators with i/p positioners, additional electric actuators, electric heating systems, refrigerating machines etc.)
Special features
• Simple menu structure with plain text display
• 4 analog inputs with filter, root extraction, function generation and measuring range monitoring
• 4 digital inputs for set point switchover, constant output
value, reversal of operating action, output tracking (DDC
backup), ramps etc
• 3 analog outputs
• 4 relay outputs for two on/off or three-step outputs or four
limit alarms
• 2 transistor outputs for fault alarms
• 1 transistor output for fault alarms
• Optional RS-232/USB and RS-485/USB interface boards
for SSP and Modbus RTU
• Degree of protection (front) IP 65
• Plug-on screw terminals
• Fixed set point control, one or two channels, internal/external switchover
• Follow-up control, one or two channels, internal/external
switchover
• Ratio control
• Cascade control, consisting of master and slave controller
• Limiting or override control
• Mixing control
• Linking of input variables (addition, subtraction, multiplication, division, mean value, minimum and maximum selection) for feedforward control or control with 1 to 4 input
variables (multi-component control)
• Operation with up to four internal set points and one external set point, either analog or via interface (SPC mode)
• Set point ramp and output ramp
• Split-range operation
• Control mode selection P/PI or PD/PID
• KP and TN adapted using the controlled variable, reference variable, manipulated variable or error signal
• Adjustable limitation of integral-action component
• Operating point preset by set point or digital input
• Control signal limitation (fixed or floating according to an
input variable)
• Operation with code number or key locking by a digital
inpu
Design and principle of operation
The TROVIS 6495-2 Industrial Controller has two independently working controllers with shared input and output
sections.
By setting the functions and parameters, the controller can be
adapted to a control task quickly. Preset basic configurations
for each control type minimize setup work for standard applications. The controller can be set up using the keys on the
housing or with the optional TROVIS-VIEW software without
requiring any additional accessories.
The controller settings are saved in a non-volatile memory,
even when the power supply fails. The two internal controllers
can be operated directly without switching. The plain-text display in English, German and French facilitates configuration
and parameterization.
Control modes
− Fixed set point control, one or two channels, internal/
external switchover
− Follow-up control, one or two channels, internal/external
switchover
− Ratio control (mixing control)
− Cascade control, consisting of master and slave controller
− Limiting or override control
Control
− Linking of input variables (addition, subtraction, multiplication, division, mean value, minimum and maximum selection) for feedforward control or control with one to four
input variables (multi-component control)
− Operation with up to four internal set points and one external set point, either analog or via interface (SPC mode)
− Set point ramp and output ramp
− Split-range operation
− Control mode selection P/PI or PD/PID
− KP and TN adapted using the controlled variable, reference variable, manipulated variable or error signal
− Adjustable limitation of integral-action component
− Operating point preset by set point or digital input
− Control signal limitation (fixed or floating according to an
input variable)
− Operation with code number or key locking by a digital
input
Inputs
− 4 analog inputs (AI1 to AI4)
DIP switches at the side of the housing to select current or
resistance inputs. The signal type is set depending on the
configuration:
− 0/4 to 20 mA
− 0/2 to 10 V
− Pt 100 or Pt 1000 resistance thermometer
− Filter, root extraction, function generation and measuring range monitoring
− Input 2 additionally for potentiometers
− 4 digital inputs (DI1 to DI4)
The digital inputs are controlled either by a 24 V DC voltage signal or by the transmitter supply using a floating
contact. The digital outputs can only be controlled in
groups, with DI1 and DI2 being the first group and DI3
and DI4 being the second group.
Example: internal supply for digital inputs DI1 and DI2
and external supply for digital inputs DI3 and DI4.
− Set point switchover, constant output value, reversal of operating action, output tracking (DDC backup), ramps etc
The following functions that have been defined over the C
Controller, O Output and A General settings menus
can be assigned to a digital input (see the 'Start-up and configuration' section):
− Invert digital input