fashion as desired. Insert the appropriate CHARM into each
terminal block to complete the field circuit and the signal
is ready to be used by any, up to four controllers.
For each Migration CIOC installation you will need to
determine the quantity and connector cable length as
well as the appropriate quantity of top and/or bottom
baseplate terminators.
The Migration CIOC assembly has a height of 6 EIA units
(10.5 inches) and is designed to be mounted at the top
of the migration cabinet and connected to the CHARM
baseplate assemblies through the cables and cable extenders.
It should be noted that the CIOC can be mounted on vertical
DIN-rail anywhere in the cabinet (front, back, side, top,
middle, bottom) and connected to the CHARM baseplate
assembly the same way. NOTE: the CIOC cannot be mounted
on a horizontal DIN-rail.
The Migration CHARM baseplate assembly has a height of
3 EIA units (5.25 inches) which allows for each installation
to determine the mounting location within each cabinet.
The user can decide to reuse existing wire way / cable tray,
mount each assembly adjacent to each other, or mount with
spacing between each assembly. DeltaV CHARMs allow for
installation flexibility by allowing each assembly to be mounted
as needed to achieve the best result for each customer-specific
termination installation.
Each CHARM acts as a circuit protection device and field wiring
disconnects. Signals are current limited or fused to protect
against wiring faults to ground. Each CHARM provides surge
protection to meet industry standards in the area of EMC, and is
designed to fail during overvoltage conditions due to incorrect
field wiring. Signal faults are isolated to the single CHARM.
CHARMs can be partially ejected to a locked position that
disconnects the field wiring from the system to perform field
maintenance actions or to remove power to a field device.
Activating the CHARM latch ejects the CHARM to the detent
position. Closing the latch locks the CHARM in place and
isolates the field wiring for field work.
The CIOC communicates over Ethernet with up to four
controllers, allowing great flexibility and ease of system
expansion. Additional controllers can be added to
accommodate increased control scope and I/O can be
reassigned without changing the physical wiring. This allows
you the flexibility required in migrations where over time
I/O has been landed on one controller only to be used in
another because of space and or available I/O.
CHARM Types
All CHARM types function on the migration panel. See DeltaV
Electronic Marshalling PDS and DeltaV IS Electronic Marshalling
PDS for a complete listing of CHARMs and IS CHARMs.
I/O Terminal Block Options
All IS and non IS I/O Terminal Block types function on the
migration panel by choosing the right baseplate assembly.
CHARM Keying Posts
Keying Posts function the same.
CHARM I/O Card Hardware
See DeltaV Electronic Marshalling PDS and DeltaV IS Electronic
Marshalling for a complete description of CIOC Hardware.
CHARM I/O Card Carrier
See DeltaV Electronic Marshalling PDS and DeltaV IS
Electronic Marshalling PDS for a complete description
of CIOC Carrier Hardware.
Hardware Specifications
CHARM I/O Migration Panel
Environmental Specifications
Operating Temperature* -40 to 70°C (-40 to 158°F)**
Storage Temperature -40 to 85°C (-40 to 185°F)
Relative Humidity 5 to 95% , non-condensing
Protection Rating IP 20
Airborne Contaminants ISA-S71.04-1985 Airborne Contaminants Class G3
Conformal coating
Shock 10 g ½-sine wave for 11 ms
Vibration 1 mm peak-to-peak from 5 to 13.2 Hz;
0.7 g from 13.2 to 150 Hz
Dimensions
Height 10.5 in (26.7 cm)
Depth 6.68 in (17.4 cm)
Width 19 in (48.3 cm)
Mounting 19 in (48.3 cm) EIA rails
6 Rack Units (U) high