for ground fault location system. AUTO indicates location system is activated automatically when IRDH575 goes into alarm.
System may also be set manually on or off.
16 - Polarity of the test current pulse. Point = valid BMS traffic,
H = A new entry has been made in the history.
17 - Text indicating state of device
18 - Analog output: 0…20 mA or 4…20 mA (selectable)
19 - External test button (N/D contact)
20 - External reset button (N/E contact or wire jumper). When the
terminals are open, the device will reset automatically.
21 - STANDBY contacts. When the contacts are closed, the device
is forced into standby mode and will not send out a measurement signal.
22 - RS-485 termination (120 Ω) with micro switch S1 and connection
BMS bus; S1 = ON = BMS bus terminated, S2 = unassigned
23 - Alarm relay: Alarm 1 (A-ISOMETER®)
24 - Alarm relay: Alarm 2 (A-ISOMETER®)
25 - Alarm relay: System fault and EDS alarm (Adr.:1)
Example: IRDH575 with EDS460 (main circuits)
EDS460 system with IRDH575, EDS460 and measuring current
transformers W… in a three-phase AC system
1 - 3AC/3NAC/AC 20…575 V
2 - US
see ordering information, 6 A fuse recommended.
3 - Current transformers, W series
4 - Loads
5 - A-ISOMETER® IRDH575
6 - Ground fault location device EDS460
Example: IRDH575 with EDS461 (control circuits)
1 - DC 20 V…308 V
2 - US
see ordering information, 6 A fuse recommended.
3 - Current transformers, W…/8000 series
4 - Load PLC
5 - A-ISOMETER® IRDH575
6 - Ground fault location device EDS461
Design of an EDS461 system
The above example shows an EDS461 device being fed by a PLC
in a DC system. Using an EDS461 device is recommended for PLC
inputs due to the sensitivity required.