• Target position outside position limits (bit 13)
Correct function:
The ZKL2 bits are set correctly.
V01-F07: Motor type (P-0-4036)
Error:
The last character of the motor type text (parameter P-0-4036) could be
incorrect.
Correct function:
The correct text is shown.
2.4 New Functions
V01-C01: P-0-4050, (RS485 turnaround delay)
New:
Sometimes a customer who utilized RS485 did not set the P-0-4050
parameter.
For most RS485 applications, a turnaround delay of 1 ms proves
sufficient. The minimum value and the default value of P-0-4050 are set
to 1 ms.
Before:
The minimum value and the default value of P-0-4050 were 0 ms.
V01-C02: S-0-269 storage mode
New:
S-0-269 integrated storage mode.
The storage mode parameter is 0 after the drive controller has been
switched on. All parameters that are contained in the list of operating data
that is to be stored are buffered after they have been written to.
If S-0-0269 (Parameter buffer mode) = 1, no parameter will be buffered
after it has been written to.
Before:
All parameters that are contained in the list of operating data that is to be
stored are buffered after they have been written to
V01-C03: Parameter conversion
New:
Various product-related parameters, that have been specified in SERCOS
in the meantime, are converted to SERCOS ident numbers.
P-0-0001 -> S-0-0390 Diagnostic Message Number
P-0-0005 -> S-0-0265 Language Selection
P-0-0013 -> S-0-0393 Command value mode for modulo format
P-0-0020 -> S-0-0298 Reference cam shift by ...
P-0-0050 -> S-0-0348 Acceleration Feedforward prop. Gain
P-0-0120 -> S-0-0391 Monitoring Window ext. Feedback
P-0-1003 -> S-0-0392 Velocity Feedback Filter time constant
P-0-4025 -> S-0-0267 Password
Before:
P-0-0001 Diagnostic Message Number
P-0-0005 Language Selection
P-0-0013 Command value mode for modulo format
P-0-0020 Reference cam shift by ...
P-0-0050 Acceleration Feedforward prop. Gain
P-0-0120 Monitoring Window ext. Feedback
P-0-1003 Velocity Feedback Filter time constant
P-0-4025 Password
V01-C04: Position limit value monitoring
New:
The diagnosis distinguishes whether the positive (S-0-0049) or the
negative (S-0-0050) position limit value is exceeded.
Warnings:
E829 Positive Position Limit Value exceeded
E830 Negative Position Limit Value exceeded
Error messages:
F629 Positive Travel Limit Value is exceeded
F630 Negative Travel Limit Value is exceeded
Before:
If the positive (S-0-0049) or the negative (S-0-0050) position limit value is
exceeded, a warning E830 Negative Position Limit Value exceeded or
an error F630 Negative Travel Limit Value is exceeded is issued.
V01-C05: Limit switch monitoring
New:
The diagnosis distinguishes whether the positive or the negative position
limit switch is actuated.
Warnings:
E843 Positive Limit Switch activated
E844 Negative Limit Switch activated
Error messages:
F643 Positive Travel Limit Switch Detected
F644 Negative Travel Limit Switch Detected
Before:
If the positive or the negative travel limit switch is actuated, a warning
E844 Negative Limit Switch activated or an error F644 Negative
Travel Limit Switch Detected is issued.
V01-C06: Absolute encoder monitoring
New:
Absolute encoder monitoring can be de-activated by entering 0 in the
parameter P-0-0097, Monitoring Window abs. Encoder.
Before:
The monitoring function could not be de-activated.
V01-C07: Length MDT, AT
New:
The maximum MDT length is limited to 16 bytes.
The maximum AT length is limited to 16 bytes.
Before:
The length of 24 bytes in the AT and 32 bytes in the MDT could not
always be covered by the available computing time.
V01-C08: Same scaling for feed constant (S-0-0123) and position data
New:
Unit and number of fractional part digits of the parameter S-0-0123, Feed
constant depend on the scaling of the position data.
Before:
The parameter S-0-0123, Feed constant had 5 fractional part digits and
the unit mm/rev.
V01-C09: Resolution external encoder
New:
For rotary and for linear encoders, the resolution of the external encoder
is selected via the parameter S-0-0117, Resolution of rotational
feedback. Unit and fractional part digits are switched over.
S-0-118 (Resolution of linear feedback) is obsolete.
Before:
S-0-117 was used for rotary encoders, and S-0-118 was used for linear
encoders.
V01-C10: Continuous current limitation
New:
The maximum continuous current is limited to 2.2 * motor standstill
current (S-0-0111).
Thus, the maximum overload factor (P-0-0006) is 220%.
Before:
Provided that the motor peak current (S-0-0109) was not smaller, the
maximum selectable continuous current was identical to amplifier nominal
current 2 (P-0-0518).
The maximum overload factor (P-0-0006) was 500%.