Power Requirements • Input Voltage Range:
24 VDC +5%, -10%
• Consumption:
3 W (maximum) at 24 VDC
• Heat Dissipation:
5 W (maximum) at 24 VDC (including contribution from field power
supply)
Calibration Requirements Calibration of the module and termination assembly is not required
Regulatory Compliance:
Electromagnetic Compatibility
(EMC)
• European EMC Directive 2004/108/EC (Prior to April 20, 2016) and
2014/30/EU (Beginning April 20, 2016):
Meets: EN61326-1:2013 Class A Emissions and Industrial Immunity
Levels
Regulatory Compliance: Product
Safety • Underwriters Laboratories (UL) for U.S. and Canada:
UL/UL-C listed as suitable for use in UL/UL-C listed Class I, Groups AD; Division 2; temperature code T4 enclosure based systems when
connected to specified Foxboro DCS processor modules.
Communications circuits also meet the requirements for Class 2 as
defined in Article 725 of the National Electrical Code (NFPA No.70) and
Section 16 of the Canadian Electrical Code (CSA C22.1).For more
information, see Standard and Compact 200 Series Subsystem User's
Guide (B0400FA).
• European Low Voltage Directive 2006/95/EC (Prior to April 20, 2016)
and 2014/35/EU (Beginning April 20, 2016) and Explosive
Atmospheres (ATEX) directive 94/9/EC (Prior to April 20, 2016) and
2014/34/EU (Beginning April 20, 2016):
DEMKO certified as Ex nA IIC T4 for use in certified Zone 2 enclosure
when connected to specified processor modules as described in the
Standard and Compact 200 Series Subsystem User's Guide
(B0400FA). For use in an enclosure suited for an ATEX Zone 2
classified area.
RoHS Compliance Complies with European RoHS Directive 2011/65/EU, including amending
Directives 2015/863 and 2017/2102
IECEx Certification IECEx Certified
(1) Digital filtering available for 200 Series FBM or competitive migration modules with version 1.25H or later
firmware.
Environmental Specifications
Operating Storage
Temperature • FBM217 :
-20 to +70°C (-4 to +158°F)
• Termination Assembly - PA (Polyamide):
-20 to +70°C (-4 to +158°F)
-40 to +70°C (-40 to +158°F)
Relative
Humidity
5 to 95% (noncondensing) 5 to 95% (noncondensing)
Altitude -300 to +3,000 m (-1,000 to +10,000 ft) -300 to +12,000 m (-1,000 to +40,000 ft)
Contamination Suitable for use in Class G3 (Harsh) environments as defined in ISA Standard S71.04, based
on exposure testing according to EIA Standard 364-65, Class III.
Vibration 0.75g from (5 to 500 Hz)
Physical Specifications
FBM217 Termination Assembly
Mounting The FBM217 mounts on a modular
baseplate. The baseplate can be mounted
on a DIN rail (horizontally or vertically), or
horizontally on a 19-inch rack using a
mounting kit. Redundant modules must be
located in odd and even adjacent positions
on the baseplate (positions 1 and 2, 3 and 4,
5 and 6, or 7 and 8) along with the
appropriate redundancy adapter.
See Standard 200 Series Baseplates (PSS
41H-2SBASPLT) for details. Alternatively, a
non-redundant FBM217 mounts on a 100
Series conversion mounting structure. See
100 Series Conversion Mounting Structures
(PSS 41H-2W8) for details.
The TA mounts on a DIN rail and
accommodates multiple DIN rail styles
including 32 mm (1.26 in) and 35 mm (1.38
in)
Weight 284 g (10 oz) approximate Compression:
• 216 mm (8.51 in) – 420 g (0.93 lb,
approximate)
• 233 mm (9.15 in) – 454 g (1.0 lb,
approximate)
Dimensions • Height:
102 mm (4 in),114 mm (4.5 in) including
mounting lugs
• Width:
45 mm (1.75 in)
• Depth:
104 mm (4.11 in)
Compression Screw:
• See Dimensions - Nominal, page 21
Part Numbers • FBM217 Module:
RH914TR
• Redundant Adapter:
RH926ZY
See Functional Specifications - Termination
Assemblies, page 14
Termination Cables • Cable Lengths:
Up to 30 m (98 ft)
• Cable Materials:
Polyurethane or Low Smoke Zero Halogen
• Termination Cable Type:
◦ Baseplate to Main TA:
Type 4 - See Table 2, page 20
◦ Main TA to Expansion TA:
Type 6 - See Table 3, page 20
Cable Connection Type 4:
• FBM Baseplate End:
37-pin D-subminiature plug
• Termination Assembly End:
37-pin D-subminiature receptacle
Type 6:
• Main TA End:
25-pin D-subminiature receptacle
• Expansion TA End:
37-pin D-subminiature receptacle
Construction -
Termination
Assembly
• Material:
Polyamide (PA), compression
Field Termination
Connections
Compression — Accepted Wiring Sizes:
• Solid/Stranded/AWG:
0.2 to 4 mm2/0.2 to 2.5 mm2/24 to 12 AWG
• Stranded with Ferrules:
0.2 to 2.5 mm2 with or without plastic collar
Termination Assemblies and Cables
Field I/O signals connect to the FBM subsystem via DIN rail mounted termination
assemblies (TAs). Multiple types of TAs are available with FBM217 to provide input
signal connections, signal conditioning, optical isolation from signal surges and
external power connections for field devices. Since these features are built into the
termination assemblies (where required), in most applications there is no need for
additional termination equipment for field circuit functions such as circuit protection or
signal conditioning (including fusing and power distribution).
The termination assembly can be used with a single FBM217 or with a redundant pair
(two FBM217s).
The DIN rail mounted termination assemblies connect to the FBM subsystem
baseplate by means of removable termination cables. When used with a redundant