module pair, the termination assembly is connected to the baseplate using a
redundant adapter (RH926ZY).
The cables are available in a variety of lengths, up to 30 meters (98 feet), allowing the
termination assemblies to be mounted in either the enclosure or in an adjacent
enclosure. See Functional Specifications - Termination Assemblies, page 14 for
termination cable part numbers and specifications.
Migration Use of Termination Assemblies
When an FBM217 is used to replace 100 Series FBMs, its associated termination
assembly is determined based on which 100 Series FBM is being replaced. Typically,
the 100 Series FBM being replaced was a main FBM and may have been used in
conjunction with an expansion FBM.
A single FBM217 provides the I/O communications for both the 100 Series equivalent
main and expansion TAs. To provide enough terminals for the field input wiring, two
termination assemblies are used with the FBM217 - one for the field input wiring for
the replaced main FBM, and one for the field input wiring for the replaced expansion
FBM.
The “expansion” termination assembly is daisy-chained to the “main” termination
assembly via the expansion cables listed in Table 3, page 20.
See Functional Specifications - Termination Assemblies, page 14 for a list of the
termination assemblies needed to replace both the 100 Series main FBMs and the
expansion FBMs.
Alternatively, the FBM217 can accept field wiring through a Termination Assembly
Adapter (TAA) instead of the termination assemblies when upgrading 100 Series
FBMs. This is discussed in Termination Assembly Adapter Modules for 100 Series
Upgrade (PSS 41H-2W4)
Discrete Inputs
Various termination assemblies are available to support the interfacing of field signals
to the low level FBM input circuits. Active termination assemblies support input signal
conditioning for the FBM as well as channel isolation.
Be aware that for configurations which use main and expansion TAs, the I/O signal
conditioning circuits are designed to emulate the 100 Series FBM I/O subsystem. This
provides for functional I/O equivalence during upgrades from 100 Series to 200 Series
hardware.
The signal conditioning circuits are located on daughter boards that are mounted
under the component covers of the termination assemblies. To condition signals,
these termination assemblies provide optical isolation, current limiting, voltage
attenuation and optional terminal blocks to connect externally supplied excitation
voltage.
Low Voltage Discrete Inputs
The low voltage inputs (less than 60 VDC) use passive termination assemblies. Inputs
are voltage monitor or contact sense types. Voltage monitor inputs require an external
field voltage source. Contact sense inputs use the FBM auxiliary +24 VDCpower
supply to wet field contacts.
A load may be required for proper operation of the input channels.
High Voltage Discrete Inputs
The high voltage input circuits support 125 VDC, 120 VAC, or 240 VAC. Voltage
monitor inputs require a field voltage source.
Some versions of the termination assembly have a pair of external excitation voltage
terminals, which distribute customer-supplied wetting voltage to all input channels on
the assembly. These terminals allow the field power to be daisy chained between
terminal assemblies.
Functional Specifications - Termination Assemblies
FBM Type Input Signal TA Part
Number
PA(a)
Termination
Type(b)
BP to TA
Cable
Type(c)
TA Cert.
Type(d)
FBM217 32 channel, voltage monitor 30
VDC
Logic Zero – 0 to 5 VDC
Logic One – 15 to 30 VDC
Passive feedthrough with FBM217
group isolation
RH916CA C 4 1, 2, 4
FBM217 32 channel, contact sense
24 VDC contact wetting from FBM
Passive feedthrough with FBM217
group isolation
RH916XZ(e) C 4 1, 2, 4
FBM217 32 channel, voltage monitor 132
VAC or 150 VDC maximum
Logic Zero - 0 to 20 VAC; 0 to 20
VDC
Logic One - 80 to 132 VAC; 75 to
150 VDC
Input Current for Logic One; 2.6 mA
maximum
Channel isolation provided by
termination assembly
RH916YA(e) C 4 1, 4
FBM217 32 channel, contact sense inputs,
132 VAC or 150 VDC maximum
with external excitation
Logic Zero - 0 to 20 VAC; 0 to 20
VDC
Logic One - 80 to 132 VAC; 75 to
150 VDC
Input Current for Logic One; 2.6 mA
maximum
Group isolation provided by
termination assembly
RH916YB(e) C 4 1, 4
FBM217 32 channel, voltage monitor 240
VAC
Logic Zero: 0 to 40 VAC
Logic One: 164 to 264 VAC
Input Current for Logic One; 2.8 mA
maximum
Channel isolation provided by
termination assembly
RH916PU C 4 1
FBM Type Input Signal TA Part
Number
PA(a)
Termination
Type(b)
BP to TA
Cable
Type(c)
TA Cert.
Type(d)
FBM217 32 channel, contact sense inputs,
240 VAC with external excitation
Logic Zero: 0 to 40 VAC
Logic One: 164 to 264 VAC
Input Current for Logic One; 2.8 mA
maximum
Group isolation provided by
termination assembly
RH916QA C 4 1
FBM217 When replacing a main FBM07A:
Voltage monitor, external source,
130 VDC maximum voltage
Logic Zero: 0 to 5 VDC
Logic One: 15 to 130 VDC
2.2 mA typical 5 to 130 VDC
1 kΩ Maximum On-state resistance
100 kΩ Minimum Off-state
resistance
When replacing a main FBM07B:
Contact Sense, internal source 24
VDC ±10% Open circuit voltage
2.5 mA maximum short circuit
current
1 kΩ Maximum On-state resistance
100 kΩ Minimum Off-state
resistance
Pairs isolation provided by