5 to 95% (noncondensing)
ALTITUDE-300 to +12.000 m (-1.000 to +40.000 ft)
Contamination
Suitable for use in Class G3 (Harsh) environments as
defined in ISA Standard S71.04. based on exposure
testing according to EIA Standard 364-65. Class III.
Vibration
0.75 m/S2 (0.75g) from 5 to 500 Hz
Mounting
MODULE
FBM239 mounts on a baseplate. The baseplate
can be mounted on a DIN rail (horizontally or
vertically), or horizontally on a 19-inch rack using
a mounting kit. Alternatively, FBM239 mounts on
a 100 Series conversion mounting structure.
Refer to Standard 200 Series Baseplates
(PSS 31H-2SBASPLT) or 100 Series Conversion
Mounting Structures (PSS 31H-2W8) for details.
TERMINATION ASSEMBLY
The TA mounts on a DIN rail and accommodates
multiple DIN rail styles including 32 mm (1.26 in)
and 35 mm 1.38 in)
Weight
MODULE
284 g (10 oz) approximate
TERMINATION ASSEMBLY - COMPRESSION
Dimensions - Module
HEIGHT
102 mm (4 in),114 mm (4.5 in) including mounting
lugs
WIDTH
45 mm (1.75 in)
DEPTH
104 mm (4.11 in)
Dimensions - Termination Assembly
Compression Screw - Refer to page 26
Part Numbers
FBM239 MODULE
RH927AG (supersedes P0927AG)
TERMINATION ASSEMBLIES
Refer to “FUNCTIONAL SPECIFICATIONS -
Standard TERMINATION ASSEMBLIES” on
page 8. “FUNCTIONAL SPECIFICATIONS - Main
TERMINATION ASSEMBLIES” on page 9 and
“FUNCTIONAL SPECIFICATIONS - Expansion
TERMINATION ASSEMBLIES” on page 15.
Termination Cables
CABLE LENGTHS
Up to 30 m (98 ft)
CABLE MATERIALS
Polyurethane or Low Smoke Zero Halogen
(LSZH)
TERMINATION CABLE TYPE
Baseplate to Main TA
Type 4 - Refer to Table 2
Main TA to Expansion TA
Type 6 - Refer to Table 3
BASEPLATE TO MAIN TA CABLE CONNECTION
FBM Baseplate End
37-pin D-subminiature
Termination Assembly End
37-pin D-subminiature
MAIN TA TO EXPANSION TA CABLE
CONNECTION
Main TA End
25-pin D-subminiature
Expansion TA End
37-pin D-subminiature
Construction - Termination Assembly
MATERIAL
Polyamide (PA), compression
Field Termination Connections
COMPRESSION - ACCEPTED WIRING SIZES
Solid/Stranded/AWG
0.2 to 4 mm2/0.2 to 2.5 mm2/24 to 12 AWG
Stranded with Ferrules
0.2 to 2.5 mm2 with or without plastic collar
TERMINATION ASSEMBLIES AND CABLES
General Description
Field I/O signals connect to the FBM subsystem via
DIN rail mounted termination assemblies (TAs).
Multiple types of TAs are available with FBM239 to
provide I/O signal connections, signal conditioning,
optical isolation from signal surges, and external
power connections for field devices as required by
the particular FBM. Since these features are built into
the termination assemblies (where required), in most
applications there is no need for additional
termination equipment for field circuit functions such
as circuit protection or signal conditioning (including
fusing and power distribution).
The DIN rail mounted termination assemblies
connect to the FBM subsystem baseplate by means
of removable termination cables. The cables are
available in a variety of lengths, up to 30 meters
(98 feet), allowing the termination assemblies to be
mounted in either the enclosure or in an adjacent
enclosure. Refer to “Cable Types and Part Numbers”
on page 22 and “Cable Types (Main TA to Expansion
TA Cables) and Part Numbers” on page 23 for
termination cable part numbers and specifications.
Use of Termination Assemblies in 100 Series
Upgrade
When an FBM239 is used to replace 100 Series
FBMs, its associated termination assembly is
determined based on which 100 Series FBM is being
replaced. Typically, the 100 Series FBM being
replaced is a main FBM and may be used in
conjunction with an expansion FBM.
A single FBM239 provides the I/O communications
for both the 100 Series equivalent main and
expansion TAs. To provide enough terminals for the
field I/O wiring, two termination assemblies are used
with the FBM239 - one for the field I/O wiring for the
replaced main FBM, and one for the field I/O wiring
for the replaced expansion FBM.
The “expansion” termination assembly is daisy
chained to the “main” termination assembly via the
expansion cables listed in Table 3 on page 25.
The table “FUNCTIONAL SPECIFICATIONS - Main
TERMINATION ASSEMBLIES” on page 9 lists the
termination assemblies needed to replace the
100 Series main FBMs. “FUNCTIONAL
SPECIFICATIONS - Expansion TERMINATION
ASSEMBLIES” on page 15 lists the termination
assemblies needed to replace the 100 Series
expansion FBMs.
Alternatively, the FBM239 can accept field wiring
through a Termination Assembly Adapter (TAA)
instead of the termination assemblies when replacing
100 Series FBMs. This is discussed in Termination
Assembly Adapter Modules for 100 Series Upgrade
(PSS 31H-2W4).
Discrete Inpu