Isolation : >100 VDC
Communication interfaces – serial
Number : 2
Serial interfaces
• Network interface : RS-422 or RS-485 (half-duplex (2-wire) or full-duplex (4-wire))
• Data transfer rate : Up to 115.2 kBaud
• Distance between devices : According to the relevant standard
• Network topologies : Point-to-point for RS-232 links.
Point-to-point or linear (daisy-chained) for RS-422/ RS-485 networks.
• Protocols : Modbus RTU
• Function : Fieldbus Modbus RTU communications
• Connectors : A and B on IOCN card (see Connectors on page 10)
• RS-485 (fieldbus) isolation : 500 VDC
Notes
Jumpers on the CPUM and IOCN cards are used to configure the required operation of serial and Ethernet
interfaces and connectors. Refer to the VM600 machinery protection system (MPS) hardware manual for
further information.
System communications
Internal : VME bus interface (A24 / D16 master mode) for communication
with protection cards (MPC4 and AMC8) via VM600 rack
backplane
External : System communication interfaces (serial and Ethernet) for
communication with VM600 MPSx software running on an external
computer.
See Communication interfaces – serial on page 6 and
Communication interfaces – Ethernet on page 7.
External communication links/connections
• Connection to a computer/network : A serial communication interface (RS232 on CPUM card) can be
used for connections/communications between a CPUM/IOCN
card pair and a computer/network, using a standard serial cable.
See Communication interfaces – serial on page 6 and Connectors
on page 10.
An Ethernet communication interface (NET on CPUM card or 1 on
IOCN card) can be used for connections/communications
between a CPUM/IOCN card pair and a computer/network, using
standard cabling.
See Communication interfaces – Ethernet on page 7 and
Connectors on page 10.
• Connection to a fieldbus
(third-party system)
: A serial fieldbus communication interface (RS on IOCN card) can
be used for connections/communications between a CPUM/IOCN
card pair and serial-based fieldbuses (Modbus RTU).
See Communication interfaces – serial on page 6 and Connectors
on page 10.
An Ethernet fieldbus communication interface (NET on CPUM card
or 1 on IOCN card, or 2 on IOCN card) can be used for
connections/communications between a CPUM/IOCN
card pair and Ethernet-based fieldbuses (Modbus TCP).
See Communication interfaces – Ethernet on page 7 and
Connectors on page 10.
• VM600 MPSx software : Used for the configuration and operation of MPC4/IOC4T and
AMC8/IOC8T card pairs (using the CPUM/IOCN card pair as a
communications gateway)
• VibroSight® software : Used for the configuration of CPUM cards
Configuration
CPUM/IOCN card pair : Software configurable via Ethernet or serial, using a computer
running the VM600 MPSx and CPUM Configurator software.
Note: Serial (RS-232 / RS-422 / RS-485) line configuration and
Ethernet port to connector routing is determined by jumpers on the
CPUM and IOCN cards.
SPECIFICATIONS (continued)
Time synchronisation
Time reference for CPUM : Network time protocol (NTP) server or
CPUM’s internal real-time clock (RTC) with battery backup
Protocol used between VM600 cards
and host computer
: Network time protocol (NTP)
Note: When VM600 system event and/or measurement event logging is used, the time and date must be
configured for the CPUM in order for the timestamps in the event log files to be correct.
Environmental
Operating
• Temperature : −20 to 65°C (−4 to 149°F)
• Humidity : 0 to 90% relative humidity, non-condensing
Storage
• Temperature : −25 to 80°C (−13 to 176°F)
• Humidity : 0 to 90% relative humidity, non-condensing
Approvals
Conformity : CE marking, European Union (EU) declaration of conformity.
EAC marking, Eurasian Customs Union (EACU) certificate/
declaration of conformity.
Electromagnetic compatibility : TR CU 020/2011
Electrical safety : TR CU 004/2011
Environmental management : RoHS compliant
Russian federal agency for technical
regulation and metrology (Rosstandart)
: Pattern approval certificate CH.C.28.004.A N° 60224,
dated 11.11.2015
Power supply (to CPUM/IOCN)
Source : VM600 rack power supply
Voltage : 5 VDC
Power consumption
• CPUM : <10 W
• IOCN : <2 W
Total power consumption
(CPUM/IOCN card pair)
: ≤12 W
Control inputs (buttons)
CPUM
ALARM RESET : Used to reset all latched alarms (and associated relays) for all
protection cards in the VM600 rack (MPC4/IOC4T and AMC8/
IOC8T)
OUT+ and OUT− : Used to select a measurement channel for the currently selected
protection card (slot)
SLOT+ and SLOT− : Used to select a slot (protection card) in the VM600 rack
Note: OUT and SLOT button combinations are also used to enable
or disable VM600 rack (CPUM) security, that is, limit the VM600 MPSx
software to “read only” operations.
Status indicators (LEDs)
CPUM
DIAG : Green LED used to indicate the status of the CPUM card: off,
normal operation and status of VM600 MPS rack (CPUM) security
OK : Green LED used to indicate the status of the OK system check
(sensor OK link check) for the currently selected measurement