(see fig. above) must be closed.
In the case of electrically connected systems (e.g. PC), this jumper represents a high-resistance
bridge (1k ) and may generate a hum loop!
3.2 Module Pin Assignment
The pin assignment on the right shows the top view of the module
backplane (see chapter 3).
The pin assignment corresponds to the 5B modules of Analog
Devices®, BURR BROWN® etc. However, an additional 0EX pin has
been introduced, which is particularly suitable for ungrounded
shielding. This is a specific assignment of BMC Messsysteme
GmbH. The 0EX pin is not connected in modules of other
manufacturers.
3.3 Fuse
The fusing of the AMS backplane is effected on the backplane (see chapter 3) with one reversible
semi-conductor fuse. In case of overload, it turns off. To make the fuse work effectively again, first
remove the cause for overload before disconnecting the power supply of the AMS42/84.
3.4 Connection for AMS Cassettes
The cassettes are connected to the AMS backplane via 7-way pin connectors,
leading the input signals connected at the cassette panel to the backplane. The
assignment of the 7-way female connector on the board is illustrated in the figure on
the right-hand side.
4 Supplementary Products for AMS42/84

4.1 5B Modules (MA Line)
The 5B measuring amplifiers from bmcm allow for the professional
signal adjustment to a data acquisition system.
The amplifier output is 5V or 0..5V. Most of the modules are
electrically isolating and provide sensor supply.
The following 5B modules from bmcm are available:
4.2 Plug-in Cassettes (AMS-K Line)
The amplifier system can be individually equipped with 8
(AMS42-USB) or 16 (AMS84) plug-in cassettes.
Each cassette is equipped with the relevant 5B module and
suitable input connector.
The suitable input connector on the front panel guarantees for
the relevant connection to be available when exchanging the
cassette.
The following cassettes are available:
Product
Description
AMS-K-BIN5
cassette with panel and 5-pin Binder female connector (712 series)
AMS-K-BLANK blank panel
AMS-K-BNC
AMS-K-CO5
cassette with front panel and BNC female connector
cassette with front panel and 5-pin terminal connector
AMS-K-THK
cassette with front panel and thermocouple socket (type K)
4.3 AMS-HANDLE2. AMS-FOOT
For mobile use, the AMS42/84 can be equipped with two stable
metal handles at the housing frame (AMS-HANDLE2).
If the AMS84 is not installed in a 19'' rack, a set of tip-up feet
(AMS-FOOT) can optionally be ordered.
4.4 AMS-EXT8
With the add-on option AMS-EXT8. 8 additional analog channels are
available at the back of the AMS42. In this case the device features max. 16
channels.
The analog outputs are accessible at a second D-Sub37 female with the
same assignment as the standard D-Sub37 female of the AMS device (see
chapter 2.3).
5 Important Notes for Using the AMS42/84
AMS42/84
• The device is only suitable for extra-low voltages - please observe the relevant regulations! For reasons
relating to EMC, it must only be used in closed PC housings.
• Only use an electrical isolated power supply unit (with CE).
• Only use non-solvent detergents for cleaning. The product is designed to be maintenance-free.
• For calibration purposes, the device must be returned to BMC Messsysteme GmbH.
• Use shielded cables for reasons relating to CE. Connect the shield to ground at one end only. Close open
inputs if possible.
• When mounting the cassettes, a connection between power supply ground and chassis of the device is made
via the module screw.
• The device must not be used for safety-relevant tasks. With the use of the product, the customer becomes
manufacturer by law and is therefore fully responsible for the proper installation and use of the product. In the
case of improper use and/or unauthorized interference, our warranty ceases and any warranty claim is
excluded.