DCS; Industrial control system
NameDescriptionContent
NEW CENTER
Current Location:

SEWControl Cabinet Inverter MOVITRAC® B Functional Safety

From:SEW | Author:LIAO | Time :2025-08-25 | 420 Browse: | Share:
 1 General Information

1.1 About this manual

The manual is part of the product and contains important information about installation,

startup, operation and service. The manual is written for everyone installing, starting up

or servicing this product.

The manual must be accessible and legible. Make sure that persons responsible for the

system and its operation, as well as persons who work independently on the unit, have

read through the manual carefully and understood it. If you are unclear about any of the

information in this documentation, or if you require further information, contact SEWEURODRIVE.

1.2 Structure of the safety notes

The safety notes in this manual are designed as follows:

1.3 Rights to claim under limited warranty

A requirement of fault-free operation and fulfillment of any rights to claim under limited

warranty is that you adhere to the information in the MOVITRAC® B documentation.

Therefore, read the operating instructions before you start working with the unit.

Make sure that the documentation is available to persons responsible for the system and

its operation as well as to persons who work independently on the unit. You must also

ensure that the documentation is legible.

1.4 Exclusion of liability

You must comply with the information contained in the MOVITRAC® B documentation

to ensure safe operation of MOVITRAC® B and to achieve the specified product characteristics and performance requirements. SEW-EURODRIVE assumes no liability for

injury to persons or damage to equipment or property resulting from non-observance of

the documentation. In such cases, any liability for defects is excluded.

1.5 Copyright notice

© 2009 – SEW-EURODRIVE. All rights reserved.

Unauthorized duplication, modification, distribution or any other use of the whole or any

part of this documentation is strictly prohibited.

1.6 Content of this publication

This publication contains conditions and amendments related to MOVITRAC® B in

safety-oriented applications.

The system comprises a frequency inverter with asynchronous motor and safety-tested

external disconnecting device.

1.7 Other applicable publications

This document supplements the MOVITRAC® B operating instructions and limits the

application notes according to the following information.

It can only be used in conjunction with the following publications: 

• The MOVITRAC® B operating instructions must always be observed.

For permitted connection variants, refer to chapter "Connection variants" (see page 17).

Safety Concept

• In case of danger, any potential risk related to a machine must be eliminated as

quickly as possible. Standstill with restart prevention is generally the safe condition

for preventing dangerous movements. 

• MOVITRAC® B is characterized by the optional connection of X17 to an external failsafe, prototype tested safety relay. The safety relay disconnects all active elements

(disconnection of the safety oriented 24 V power supply of the output stage control)

that generate the pulse trains to the power output stage (IGBT) when a connected

control device (E-STOP button with latching function) is activated. 

• Disconnecting the 24 V voltage supply at connector X17 ensures that the supply

voltages required for operating the frequency inverter and consequently for

generating a rotating field of pulse patterns (which allow the generation of a rotating

field) are safely interrupted, preventing automatic restart.

• Instead of separating the drive galvanically from the power supply using contactors

or switches, the disconnection procedure described here prevents the power

semiconductors in the frequency inverter from being activated, thus ensuring safe

disconnection. This process disconnects the rotating field generation for the

respective motor. The individual motor cannot develop any torque in this state even

though the mains voltage is still present.

• The requirements for the safety control are clearly defined in the following sections

and must be observed.

Using a suitable external circuit via a safety control

– with approval to at least EN 954-1 category 3

enables operation of the MOVITRAC® B frequency inverter with safe disconnection to stop category 0 or 1 according to EN 60204-1, fail-safe protection against

restart according to EN 1037 and fulfillment of safety category 3 to EN 954-1.

Using a suitable external circuit via a safety control

– with approval for EN ISO 13849-1, performance level "d"

enables operation of the MOVITRAC® B frequency inverter with safe disconnection according to stop category 0 or 1 to EN 60204-1, fail-safe protection against

restart according to EN 1037 and fulfillment of performance level "d" to EN ISO

13849-1.

Limitations

• Important: The safety concept is only suitable for performing mechanical work

on system/machine components.

• Important: A system/machine-specific risk analysis must always be carried out

by the system/machine manufacturer and taken into account for the use of the

MOVITRAC® B frequency inverter.

• Danger of fatal injury: When the safety-oriented 24 V voltage supply is

disconnected, the mains supply voltage is still present at the frequency

inverter DC link.

• Danger of fatal injury: When the 24 V voltage supply is disconnected, the DC

link voltage is still present at the MOVITRAC® B frequency inverter.

• Important: If work is carried out on the electrical section of the drive system,

the DC link voltage must be disconnected.

Representation of the "Safety concept for MOVITRAC® B / control unit"

[1] Safety relay (external)

[2] Low-voltage switch-mode power supply

[3] Safety switched-mode power supply (SNT)

[4] Voltage supply for controlling the power transistors

[5] Feedback to the central processing unit: Voltage supply for output stage control OK (not in safety circuit)

[6] Pulse width modulated signals for output stage

[7] Power section

[8] Motor

[9] High-voltage switch-mode power supply

Representation of the "Safety concept for MOVITRAC® B / size 0"

Safety-Relevant Conditions

The following conditions are mandatory for the installation and operation of

MOVITRAC® B in applications with safe disconnection of the drive in accordance with

category 0 or 1 of EN 60204-1 and fail-safe protection against restart according to

EN 1037, and conformance with safety category 3 of EN 954-1 or performance level "d"

of EN ISO 13849-1. The conditions are divided into the following sections:

• Approved devices

• Installation requirements

• Requirements for external safety relays

• Startup requirements

• Operation requirements

3.1 Information on the stop categories

• Stop category 0 means that the safety 24 V voltage supply can be disconnected

independent of the setpoints.

• Observe the following procedure for stop category 1:

– Decelerate the drive using an appropriate brake ramp specified by the setpoint.

– Disconnect the safety-oriented 24 V voltage supply

3.2 Approved devices

The following frequency inverters are permitted for applications with safe disconnection

according to stop category 0 or 1 of EN 60204-1, fail-safe protection against restart

according to EN 1037 and compliance with safety category 3 according to EN 954-1 or

performance level "d" according to EN ISO 13489-1.

3.2.1 MOVITRAC® B for AC 3 × 380 – 500 V / 200 – 240 V supply voltage

3.2.2 Hazard caused by coasting drive

Note that if the drive does not have a mechanical brake, or if the brake is defective, the

drive may coast to a halt.

Note: If coasting to a halt results in application-dependent hazards, take

additional protective measures (e.g. movable covers with closure), which cover

the hazardeous area until persons are no longer in danger.

The additional protective covers must be designed and integrated in such a way that

they meet the safety category required for the machine. 

After activating the stop command, access to the machine must remain blocked until the

drive has reached standstill, or the access time has to be determined to ensure that an

adequate safety distance is maintained.

3.3 Installation requirements

Note the following instructions for applications of MOVITRAC® B with safe disconnection of the drive according to stop category 0 or 1 according to EN 60204-1 and fail-safe

protection against restart according to EN 954-1 safety category 3 or performance level

"d" according to EN ISO 13849-1. 

• The line between the safety control system (or the safety-oriented tripping device)

and MOVITRAC® B terminal X17 is designated as the safety-oriented 24 V voltage

supply.

• Power lines and the safety-oriented 24 V supply voltage must be installed in separate

cable ducts. 

• The safety-oriented 24 V supply voltage must be routed according to EMC guidelines

and as follows:

– Outside an electrical installation space: Shielded cables must be routed

permanently (fixed) and protected against external damage, or other equivalent

measures.

– Individual conductors can be routed inside an electrical installation space.

Observe the respective regulations governing the application.

• It must be ensured that parasitic voltages cannot be generated in the safety-oriented

24 V supply voltage.

• The total cable length between the safety control system (e.g. safety relay) and

MOVITRAC® B is limited to a maximum length of 100 m for EMC reasons.

• The switching capacity of the safety relay and the maximum permissible voltage drop

on the 24 V supply cable must be observed during disconnection of group drives.

• Only use terminal connections (terminal blocks) that meet EN 60204-1 and prevent

short-circuits.

• Observe the notes in the "MOVITRAC® B" operating instructions on EMC compliant

cabling. It is essential that you apply the shielding at both ends on the housing.

• Only use power supplies with safe isolation (SELV/PELV) according to VDE010.

According to EN 60950-1, the voltage between the outputs or between any output

and a ground part must not exceed DC 60 V voltage for longer than 0.2 s after only

one fault. The maximum DC voltage must be 120 V.

• You must remove the jumpers at X17:1 to X17:4 (see following figure) for use in

applications with safe disconnection of the drive according to stop category 0 or 1 in

accordance with EN 60204-1 and fail-safe protection against restart according to

EN 954-1 safety category 3 or performance level "d" according to EN ISO 13849-1.

• The shielded lines of the safety-oriented 24 V voltage supply (terminal X17) must be

clamped under the signaling electronics shield clamp.

• You must observe the technical data of MOVITRAC® B (see MOVITRAC® B

operating instructions).

Removing jumpers

Requirements on external safety relays

• If the requirements of the standard EN 954-1 are to be met, at least one approval for

safety category 3 according to EN 954-1 must be available.

• If the requirements of the standard EN ISO 13849-1 are to be met, at least one

approval for performance level "d" according to EN ISO 13849-1 must be available.

• If the DC 24 V voltage supply is safely disconnected at the positive pole only, no test

pulses must be applied to this pole in disconnected condition.

• Bipolar disconnection of the DC 24 V supply is permitted.

• The values specified for the safety relays must be adhered to when designing the

circuit.

• The switching capacity of the safety relays must correspond at least to the maximum

permitted limited output current of the DC 24 V voltage supply. Observe the

manufacturer's instructions for the safety relays concerning the permitted

contact loads and fusing that may be required for the safety contacts. Unless

specified otherwise, the contacts must be protected with 0.6 times the nominal

value of the maximum contact rating specified by the manufacturer.

• The controller must be designed and connected in such a way that resetting the

control device itself will not lead to a restart. A restart may only be carried out after

an additional reset of the controller.

3.4.1 "Safety relay" sample circuit

The following figure shows the basic connection of an external safety relay (according

to the before mentioned requirements) to MOVITRAC® B.

The information in the respective manufacturer's data sheets must be observed for

connection. 

1-pole disconnection of the 24 V supply voltage:

3.5 Startup requirements

• Startup must be documented and the functionality of the safety functions must be

demonstrated.

• Startup checks of the disconnecting device and the correct wiring must be performed

and documented for MOVITRAC® B with safe disconnection of the drive according

to stop category 0 or 1 of EN 60204-1, fail-safe protection against restart according

to EN 1037 and compliance with safety category 3 according to EN 954-1 or

performance level "d" according to EN ISO 13849-1. 

• At startup, the safety-related 24 V control voltage must be included in the functional

test. 

3.6 Operation requirements

• Operation is only allowed within the limits specified in the data sheets. This applies

both to the external safety relay as well as MOVITRAC® B.

• The safety functions must be checked at regular intervals to ensure proper

functioning. The period of time between the tests should be specified in accordance

with the risk analysis.

Connection Variants

Refer to the publication "Safe Disconnection for MOVITRAC® B - Applications" for

examples of approved connection variants of units listed in the section "Approved Units"

for safe disconnection of the drive according to stop category 0 or 1 of EN 60204-1 and

fail-safe protection against restart according to EN 1037 and fulfillment of the safety

category according to EN 954-1 or performance level "d" of EN ISO 13849-1. The

publication "Safe Disconnection for MOVITRAC® B - Applications" is constantly being

supplemented by possible applications. The publication includes checklists, which offer

additional assistance in project planning and installation as well as operating

MOVITRAC® B drives in safety-oriented applications. It is essential that you comply with

the publications listed in the section "Safety and warning instructions" for all the

connection variants listed in the publication "Safe Disconnection for MOVITRAC® B -

Applications".

4.1 Disconnection of single drives

4.1.1 Requirements

The requirements of the manufacturers of safety relays (such as protecting the output

contacts against welding) or other safety components must be strictly observed. In

addition, the basic requirements described in the manual "Safe Disconnection for

MOVITRAC® B - Conditions" apply for cable routing.

For reasons of EMC, the length of the cable between connection X17 on

MOVITRAC® B and the safety components (e.g. safety relay) is limited to a maximum

of 100 m. Other instructions by the manufacturer on the use of safety relays for specific

applications must also be observed.

4.1.2 Internal 24 V supply, stop category 0

4.2 Disconnection of group drives

4.2.1 Requirements

For group drives, the 24 V supply of several MOVITRAC® B units can be made available

by a single safety relay. The maximum possible number of units (n units) results from

the maximum permitted contact load of the safety relay and the maximum permitted

voltage drop of the DC supply for MOVITRAC® B units.

Other requirements of the safety relay manufacturer (such as protecting the output

contacts against welding) must be strictly observed. In addition, the basic requirements

described in the manual "Safe Disconnection for MOVITRAC® B - Conditions" apply for

cable routing.

For reasons of EMC, the length of the cable between connection X17 (MOVITRAC® B)

and the safety components (e.g. safety relay) is limited to a maximum of 100 m.

Other instructions by the manufacturer on the safety relay used in the specific

application must also be observed.

Determining the maximum number of MOVITRAC® B drives for disconnection of group drives

The number (n units) of MOVITRAC® B units that can be connected to a group drive with

safe disconnection is limited by the following points:

1. Switching capacity of the safety relay.

A fuse must be connected in front of the safety contacts according to the

specifications of the safety relay manufacturer to prevent the contacts from sticking

or welding.

The project planner is responsible for ensuring that the specifications on the

switching capacity according to EN 60947-4-1, 02/1 and EN 60947-5-1, 11/97 as well

as on contact fuse protection given in the operating instructions of the safety relay

manufacturer are strictly observed.

2. Maximum permitted voltage drop in the 24 V power supply cable.

Values concerning cable lengths and permitted voltage drops must be observed

during project planning for group drives.

3. Maximum cable cross section of 1x1.5 mm2 or 2x0.75 mm2.

A calculation based on the technical data of MOVITRAC® B must be performed

separately for each group drive application


  • UNIOP MKDR-04-0021 Monochrome LCD (with Contrast Control)
  • UNIOP eTOP03-0046 Monochrome LCD (STN)
  • UNIOP MKDR-16-TA-0045 HMI TOUCH SCREEN
  • UNIOP Operator Interface Display MD02R-04-0042
  • UniOP Display Screen eTOP20C-0050 eTOP20C
  • UniOp eTOP05-0045 eTOP05. eTOP05P Operator Interface Touch Panel
  • UNIOP ETOP11-0050 HMI 5.6Color Operator Interface Touch Panel
  • UniOp eTOP306 Panel
  • UniOP CP04F-04-0045 Human Machine Interface
  • UniOP eTOP308 ETOP308U301 HMI Panel
  • UniOP MD00R-02-0045 Ultra-Compact Industrial Operator Terminal
  • UniOP ePALM10-0061 Handheld Robot Trainer
  • ​UniOP CP05R-04-0045 High-Value Character Operator Terminal
  • UniOP CP01R-04. CP05R-04 and CP01F-02
  • Uniop MD02R-04 - MD02R-04-0045 Industrial PLC Workstation
  • Uniop Cp02r-04-0021 Operating Interface
  • UniOP CP04F-04-1945 Rugged VFD Operator Interface
  • UniOP ECT-16-0045 High-Performance Color Touchscreen HMI
  • UniOP ERT-16-0042 High-Durability Industrial Operator Interface
  • UniOP ePAD04-0046 Compact Industrial Interface
  • UniOP BKDR-16 High-Reliability Monochrome Operator Interface
  • UniOP MKDR-04-004 Control Unit Panel
  • UniOP eTOP515 Series 500 HMI
  • Woodward 8200-1300 High-Precision 505D Steam Turbine Controller
  • ABB PFSK138 3BSE016323R3 High-Performance Digital Board Connection Unit
  • ABB PFSK163 3BSE000435R1 High-Performance Interface Module
  • UniOP ETT-VGA Human-Machine Interface (HMI) terminal
  • ABB PFSK165 3BSE027778R1 VP74201-933CW07 Signal Processing and Communication Unit
  • ABB PFSK164 3BSE021180R1 Tension sensor module and processing board
  • ABB 3BSE006505R1 PFSK 142 Control board
  • ABB PFSK160A 3BSE009514R1 Regulated High-Capacity 24V DC
  • ABB PFSK162 3BSE015088R1 High-performance signal conditioning and processing board
  • ABB PFSK152 3BSE018877R1 Signal concentrator board
  • ALSTOM PIB1201A 3BEC0067 Power Interface Board (PIB)
  • ALSTOM PIB310 3BHB0190 Adapter Module / Printed Circuit Board (PCB)
  • ALSTOM PIB102A 3BEB0180 Communication Card / PCB Module
  • ALSTOM BGTR8HE 24491276A1004 High-Frequency Power Controller / Rack Module
  • ALSTOM AM164 Analog Output / Remote I/O
  • ALSTOM UT150-1 PID temperature controller / process control board
  • ALSTOM AL132 AL132A STO0982E01 Control Motherboard / CPU Card
  • ALSTOM AS111-1 Analog Output (AO) Module
  • ALSTOM AH116-2 Servo Drive / Control Module
  • ALSTOM V4555724-0100 Electromechanical Contactor /Power Switch
  • WATLOW 999D,999A Digital/Analog Dual-Channel Base Unit
  • WATLOW 998D 998A Digital/Analog Dual-Channel Base Unit
  • WATLOW 999D-11FF-AARG Dual-channel digital unit with universal process outputs
  • WATLOW Wattlo 998D-22KK-ARRG is a high-performance dual-channel digital controller.
  • WATLOW 996A Single-loop controller
  • WATLOW 996D-11CC-CUGR Single-loop digital controller
  • WATLOW 996D Single-Channel Digital Temperature/Process Controller
  • WATLOW 997D Digital Dual-Channel Base Unit
  • WATLOW 997A Analog Dual-Channel Variant
  • WATLOW DAC / SDAC,Digital-to-Analog / Serial-to-Analog Modules
  • WATLOW MLS300-OIT Operator Interface Terminal (Keypad/Display),Discontinued
  • WATLOW CIM300 Communication Interface Module (EIA-232/485),Discontinued
  • WATLOW MLS300-CIM Control Interface Module (Comm Bridge),Discontinued
  • WATLOW MLS300-AIM,Analog Input Module (16-channel expansion),Discontinued
  • WATLOW MLS300-PM Processor Module (Central CPU),Discontinued
  • Watlow MLS332 32-Loop Processor Base Unit,Discontinued
  • Watlow MLS316 Multi-loop thermal controller
  • Watlow CLS208 C10000CP high-performance, 8-loop PID temperature controller
  • Watlow CAS 16CLS/CAS Multi-loop temperature controller
  • HIMA K9212 Module Overview
  • ABB CP555 1SBP260179R1001 Product Overview
  • Watlow MLS300 Multi-Loop Control System
  • Watlow 997D-11CC-JURG SERIES 997 Vertical Limit Control
  • Watlow CLS216 | Multi-Loop PID Temperature Controller
  • Watlow NLS300-CIM316 Multi-Loop Control Interface Module
  • Watlow PPC-TB50 (30280-00) Precision Power Controller
  • ABB PPD113-B03-23-111615 high-performance Processor / Controller Module
  • ABB MB510 3BSE002540R1 Control System Accessory
  • ABB 3BSE000863R1 SR511 Power Supply
  • ABB 3BSE014227R1 RF533 Central Unit
  • ABB PDD500A101 high-performance Drive Board / Processor Module
  • ABB PPD512A10-150000 high-performance Controller/Processor Module
  • ABB 500BIO01 1MRB150005R0001 1MRB200060/E Binary Input/Output (Combined)
  • ABB 500BIM01-1MRB160024R0002 Binary (Digital) Input Module
  • ABB 500PSM03 1MRB150038R1 894-030375D 136-011100H Power Supply Module
  • ABB 500PSM02 1MRB150015R1 AD-272.100.20-01 AZ:C Power Supply Module
  • ABB 500AIM02 1MRB150022R001 1HDF 930412 X010 Analog Input Module (AIM)
  • ABB 500MTM02 1MRB150020R0712 1HDF 930512 X010 Multivariable Transmitter Module
  • ABB 500SCM01 1MRB150004R0001 1MRB200059/C Signal Regulation and Monitoring Module
  • ABB 500TRM02 1MRB150011R0001 Terminal/Input-Output Board
  • ABB 500CPU03 1HDF700003R5122 Central Processing Unit module
  • ABB 500PB101 1MRB178009R0001 1MRB200064/C Communication Module
  • ABB 500CSP04 HE401314/0002 1MRB150051R2 Control and System Processing Module
  • ABB 500CMP04 HE401314/0001 1MRB150051R1 Communication motherboard
  • ABB 500TTM02 1MB150021R01161HF930712X010 Temperature / Logic Interface Module
  • ABB DSAO110 57120001-AT/1 Analog Output 4 Channels
  • ABB UNS4684A-P,V.1 HIEE305114R00R0001 Overvoltage protection (OVP) and pulse coupling panel (PCP) module
  • ABB PVD164A2059 3BHE014340R2059 high-performance Excitation Processor Module
  • ABB PFCL201CE 10KN 3BSX105983-100 Pressductor® Curved Plate Force Sensor
  • ABB 500SCM01 1MRB200059/C 1MRB15004R0001 Control Module
  • ABB 500CPU05 1MRB150081R1/E Central Processing Unit module
  • ABB 500CIM05 1MRB150077R1/B Communication Interface Module
  • ABB 500BIO01 1MRB150005R1/J high-performance Binary Input/Output (BIO) module
  • Metso D201379L ACN RT Controller / Processor
  • Metso D201505 (ACN C20 Controller)
  • Metso D201463 high-performance Network Controller / Processor Module
  • Metso D201505R (ACN C20 Series)
  • Metso D201380 CPU / Processor Module
  • Metso D202275 ACN Communication / Gateway Node
  • Metso D201376 ACN RT (Real-Time) Controller Node
  • METSO D200175 Application Control Node (ACN) Proc
  • METSO D200137 high-performance controller module
  • METSO IOP111 Analog Input Module
  • METSO IOP353 Digital Output Module
  • METSO IOP304 high-performance Thermocouple (TC) / Millivolt (mV) Input Module
  • METSO PDP601 high-performance Distributed Processing Unit
  • METSO IOP345 Digital Input/Output Module
  • METSO DPU-MR high-performance Distributed Processing Unit
  • METSO IOP114 high-precision Analog Input Module
  • METSO IOT300A Terminal substrate / Interface module
  • Metso R/I-TB 9139041 nput/output (I/O) interface module
  • YOKOGAWA YS1700-100/A06/A31 Programmable Logic Controller
  • YOKOGAWA PW482-10 AC Input Power Module
  • YOKOGAWA SCP451-11 CPU
  • YOKOGAWA SR1030B62 high-precision Power Supply Unit (PSU)
  • YOKOGAWA AAI143-H50 high-density Analog Input Module
  • YOKOGAWA AMM42 high-density Analog Input/Output Module
  • YOKOGAWA SDV144-S63 Digital input module
  • YOKOGAWA AIP830-111 Operating keyboard
  • YOKOGAWA S9361DH-00 High-performance terminal board module
  • YOKOGAWA ATK4A-00 S1 Terminal block adapter
  • YOKOGAWA PW701 Power Supply Module
  • YOKOGAWA AVR10D-A22010 Bus Converter
  • YOKOGAWA PROFIBUS-DP communication module
  • YOKOGAWA AIP578 AIP591 Optical link transceiver module