DCS; Industrial control system
NameDescriptionContent
NEW CENTER
Current Location:

SEWControl Cabinet Inverter MOVITRAC® B Functional Safety

From:SEW | Author:LIAO | Time :2025-08-25 | 500 Browse: | 🔊 Click to read aloud ❚❚ | Share:
 1 General Information

1.1 About this manual

The manual is part of the product and contains important information about installation,

startup, operation and service. The manual is written for everyone installing, starting up

or servicing this product.

The manual must be accessible and legible. Make sure that persons responsible for the

system and its operation, as well as persons who work independently on the unit, have

read through the manual carefully and understood it. If you are unclear about any of the

information in this documentation, or if you require further information, contact SEWEURODRIVE.

1.2 Structure of the safety notes

The safety notes in this manual are designed as follows:

1.3 Rights to claim under limited warranty

A requirement of fault-free operation and fulfillment of any rights to claim under limited

warranty is that you adhere to the information in the MOVITRAC® B documentation.

Therefore, read the operating instructions before you start working with the unit.

Make sure that the documentation is available to persons responsible for the system and

its operation as well as to persons who work independently on the unit. You must also

ensure that the documentation is legible.

1.4 Exclusion of liability

You must comply with the information contained in the MOVITRAC® B documentation

to ensure safe operation of MOVITRAC® B and to achieve the specified product characteristics and performance requirements. SEW-EURODRIVE assumes no liability for

injury to persons or damage to equipment or property resulting from non-observance of

the documentation. In such cases, any liability for defects is excluded.

1.5 Copyright notice

© 2009 – SEW-EURODRIVE. All rights reserved.

Unauthorized duplication, modification, distribution or any other use of the whole or any

part of this documentation is strictly prohibited.

1.6 Content of this publication

This publication contains conditions and amendments related to MOVITRAC® B in

safety-oriented applications.

The system comprises a frequency inverter with asynchronous motor and safety-tested

external disconnecting device.

1.7 Other applicable publications

This document supplements the MOVITRAC® B operating instructions and limits the

application notes according to the following information.

It can only be used in conjunction with the following publications: 

• The MOVITRAC® B operating instructions must always be observed.

For permitted connection variants, refer to chapter "Connection variants" (see page 17).

Safety Concept

• In case of danger, any potential risk related to a machine must be eliminated as

quickly as possible. Standstill with restart prevention is generally the safe condition

for preventing dangerous movements. 

• MOVITRAC® B is characterized by the optional connection of X17 to an external failsafe, prototype tested safety relay. The safety relay disconnects all active elements

(disconnection of the safety oriented 24 V power supply of the output stage control)

that generate the pulse trains to the power output stage (IGBT) when a connected

control device (E-STOP button with latching function) is activated. 

• Disconnecting the 24 V voltage supply at connector X17 ensures that the supply

voltages required for operating the frequency inverter and consequently for

generating a rotating field of pulse patterns (which allow the generation of a rotating

field) are safely interrupted, preventing automatic restart.

• Instead of separating the drive galvanically from the power supply using contactors

or switches, the disconnection procedure described here prevents the power

semiconductors in the frequency inverter from being activated, thus ensuring safe

disconnection. This process disconnects the rotating field generation for the

respective motor. The individual motor cannot develop any torque in this state even

though the mains voltage is still present.

• The requirements for the safety control are clearly defined in the following sections

and must be observed.

Using a suitable external circuit via a safety control

– with approval to at least EN 954-1 category 3

enables operation of the MOVITRAC® B frequency inverter with safe disconnection to stop category 0 or 1 according to EN 60204-1, fail-safe protection against

restart according to EN 1037 and fulfillment of safety category 3 to EN 954-1.

Using a suitable external circuit via a safety control

– with approval for EN ISO 13849-1, performance level "d"

enables operation of the MOVITRAC® B frequency inverter with safe disconnection according to stop category 0 or 1 to EN 60204-1, fail-safe protection against

restart according to EN 1037 and fulfillment of performance level "d" to EN ISO

13849-1.

Limitations

• Important: The safety concept is only suitable for performing mechanical work

on system/machine components.

• Important: A system/machine-specific risk analysis must always be carried out

by the system/machine manufacturer and taken into account for the use of the

MOVITRAC® B frequency inverter.

• Danger of fatal injury: When the safety-oriented 24 V voltage supply is

disconnected, the mains supply voltage is still present at the frequency

inverter DC link.

• Danger of fatal injury: When the 24 V voltage supply is disconnected, the DC

link voltage is still present at the MOVITRAC® B frequency inverter.

• Important: If work is carried out on the electrical section of the drive system,

the DC link voltage must be disconnected.

Representation of the "Safety concept for MOVITRAC® B / control unit"

[1] Safety relay (external)

[2] Low-voltage switch-mode power supply

[3] Safety switched-mode power supply (SNT)

[4] Voltage supply for controlling the power transistors

[5] Feedback to the central processing unit: Voltage supply for output stage control OK (not in safety circuit)

[6] Pulse width modulated signals for output stage

[7] Power section

[8] Motor

[9] High-voltage switch-mode power supply

Representation of the "Safety concept for MOVITRAC® B / size 0"

Safety-Relevant Conditions

The following conditions are mandatory for the installation and operation of

MOVITRAC® B in applications with safe disconnection of the drive in accordance with

category 0 or 1 of EN 60204-1 and fail-safe protection against restart according to

EN 1037, and conformance with safety category 3 of EN 954-1 or performance level "d"

of EN ISO 13849-1. The conditions are divided into the following sections:

• Approved devices

• Installation requirements

• Requirements for external safety relays

• Startup requirements

• Operation requirements

3.1 Information on the stop categories

• Stop category 0 means that the safety 24 V voltage supply can be disconnected

independent of the setpoints.

• Observe the following procedure for stop category 1:

– Decelerate the drive using an appropriate brake ramp specified by the setpoint.

– Disconnect the safety-oriented 24 V voltage supply

3.2 Approved devices

The following frequency inverters are permitted for applications with safe disconnection

according to stop category 0 or 1 of EN 60204-1, fail-safe protection against restart

according to EN 1037 and compliance with safety category 3 according to EN 954-1 or

performance level "d" according to EN ISO 13489-1.

3.2.1 MOVITRAC® B for AC 3 × 380 – 500 V / 200 – 240 V supply voltage

3.2.2 Hazard caused by coasting drive

Note that if the drive does not have a mechanical brake, or if the brake is defective, the

drive may coast to a halt.

Note: If coasting to a halt results in application-dependent hazards, take

additional protective measures (e.g. movable covers with closure), which cover

the hazardeous area until persons are no longer in danger.

The additional protective covers must be designed and integrated in such a way that

they meet the safety category required for the machine. 

After activating the stop command, access to the machine must remain blocked until the

drive has reached standstill, or the access time has to be determined to ensure that an

adequate safety distance is maintained.

3.3 Installation requirements

Note the following instructions for applications of MOVITRAC® B with safe disconnection of the drive according to stop category 0 or 1 according to EN 60204-1 and fail-safe

protection against restart according to EN 954-1 safety category 3 or performance level

"d" according to EN ISO 13849-1. 

• The line between the safety control system (or the safety-oriented tripping device)

and MOVITRAC® B terminal X17 is designated as the safety-oriented 24 V voltage

supply.

• Power lines and the safety-oriented 24 V supply voltage must be installed in separate

cable ducts. 

• The safety-oriented 24 V supply voltage must be routed according to EMC guidelines

and as follows:

– Outside an electrical installation space: Shielded cables must be routed

permanently (fixed) and protected against external damage, or other equivalent

measures.

– Individual conductors can be routed inside an electrical installation space.

Observe the respective regulations governing the application.

• It must be ensured that parasitic voltages cannot be generated in the safety-oriented

24 V supply voltage.

• The total cable length between the safety control system (e.g. safety relay) and

MOVITRAC® B is limited to a maximum length of 100 m for EMC reasons.

• The switching capacity of the safety relay and the maximum permissible voltage drop

on the 24 V supply cable must be observed during disconnection of group drives.

• Only use terminal connections (terminal blocks) that meet EN 60204-1 and prevent

short-circuits.

• Observe the notes in the "MOVITRAC® B" operating instructions on EMC compliant

cabling. It is essential that you apply the shielding at both ends on the housing.

• Only use power supplies with safe isolation (SELV/PELV) according to VDE010.

According to EN 60950-1, the voltage between the outputs or between any output

and a ground part must not exceed DC 60 V voltage for longer than 0.2 s after only

one fault. The maximum DC voltage must be 120 V.

• You must remove the jumpers at X17:1 to X17:4 (see following figure) for use in

applications with safe disconnection of the drive according to stop category 0 or 1 in

accordance with EN 60204-1 and fail-safe protection against restart according to

EN 954-1 safety category 3 or performance level "d" according to EN ISO 13849-1.

• The shielded lines of the safety-oriented 24 V voltage supply (terminal X17) must be

clamped under the signaling electronics shield clamp.

• You must observe the technical data of MOVITRAC® B (see MOVITRAC® B

operating instructions).

Removing jumpers

Requirements on external safety relays

• If the requirements of the standard EN 954-1 are to be met, at least one approval for

safety category 3 according to EN 954-1 must be available.

• If the requirements of the standard EN ISO 13849-1 are to be met, at least one

approval for performance level "d" according to EN ISO 13849-1 must be available.

• If the DC 24 V voltage supply is safely disconnected at the positive pole only, no test

pulses must be applied to this pole in disconnected condition.

• Bipolar disconnection of the DC 24 V supply is permitted.

• The values specified for the safety relays must be adhered to when designing the

circuit.

• The switching capacity of the safety relays must correspond at least to the maximum

permitted limited output current of the DC 24 V voltage supply. Observe the

manufacturer's instructions for the safety relays concerning the permitted

contact loads and fusing that may be required for the safety contacts. Unless

specified otherwise, the contacts must be protected with 0.6 times the nominal

value of the maximum contact rating specified by the manufacturer.

• The controller must be designed and connected in such a way that resetting the

control device itself will not lead to a restart. A restart may only be carried out after

an additional reset of the controller.

3.4.1 "Safety relay" sample circuit

The following figure shows the basic connection of an external safety relay (according

to the before mentioned requirements) to MOVITRAC® B.

The information in the respective manufacturer's data sheets must be observed for

connection. 

1-pole disconnection of the 24 V supply voltage:

3.5 Startup requirements

• Startup must be documented and the functionality of the safety functions must be

demonstrated.

• Startup checks of the disconnecting device and the correct wiring must be performed

and documented for MOVITRAC® B with safe disconnection of the drive according

to stop category 0 or 1 of EN 60204-1, fail-safe protection against restart according

to EN 1037 and compliance with safety category 3 according to EN 954-1 or

performance level "d" according to EN ISO 13849-1. 

• At startup, the safety-related 24 V control voltage must be included in the functional

test. 

3.6 Operation requirements

• Operation is only allowed within the limits specified in the data sheets. This applies

both to the external safety relay as well as MOVITRAC® B.

• The safety functions must be checked at regular intervals to ensure proper

functioning. The period of time between the tests should be specified in accordance

with the risk analysis.

Connection Variants

Refer to the publication "Safe Disconnection for MOVITRAC® B - Applications" for

examples of approved connection variants of units listed in the section "Approved Units"

for safe disconnection of the drive according to stop category 0 or 1 of EN 60204-1 and

fail-safe protection against restart according to EN 1037 and fulfillment of the safety

category according to EN 954-1 or performance level "d" of EN ISO 13849-1. The

publication "Safe Disconnection for MOVITRAC® B - Applications" is constantly being

supplemented by possible applications. The publication includes checklists, which offer

additional assistance in project planning and installation as well as operating

MOVITRAC® B drives in safety-oriented applications. It is essential that you comply with

the publications listed in the section "Safety and warning instructions" for all the

connection variants listed in the publication "Safe Disconnection for MOVITRAC® B -

Applications".

4.1 Disconnection of single drives

4.1.1 Requirements

The requirements of the manufacturers of safety relays (such as protecting the output

contacts against welding) or other safety components must be strictly observed. In

addition, the basic requirements described in the manual "Safe Disconnection for

MOVITRAC® B - Conditions" apply for cable routing.

For reasons of EMC, the length of the cable between connection X17 on

MOVITRAC® B and the safety components (e.g. safety relay) is limited to a maximum

of 100 m. Other instructions by the manufacturer on the use of safety relays for specific

applications must also be observed.

4.1.2 Internal 24 V supply, stop category 0

4.2 Disconnection of group drives

4.2.1 Requirements

For group drives, the 24 V supply of several MOVITRAC® B units can be made available

by a single safety relay. The maximum possible number of units (n units) results from

the maximum permitted contact load of the safety relay and the maximum permitted

voltage drop of the DC supply for MOVITRAC® B units.

Other requirements of the safety relay manufacturer (such as protecting the output

contacts against welding) must be strictly observed. In addition, the basic requirements

described in the manual "Safe Disconnection for MOVITRAC® B - Conditions" apply for

cable routing.

For reasons of EMC, the length of the cable between connection X17 (MOVITRAC® B)

and the safety components (e.g. safety relay) is limited to a maximum of 100 m.

Other instructions by the manufacturer on the safety relay used in the specific

application must also be observed.

Determining the maximum number of MOVITRAC® B drives for disconnection of group drives

The number (n units) of MOVITRAC® B units that can be connected to a group drive with

safe disconnection is limited by the following points:

1. Switching capacity of the safety relay.

A fuse must be connected in front of the safety contacts according to the

specifications of the safety relay manufacturer to prevent the contacts from sticking

or welding.

The project planner is responsible for ensuring that the specifications on the

switching capacity according to EN 60947-4-1, 02/1 and EN 60947-5-1, 11/97 as well

as on contact fuse protection given in the operating instructions of the safety relay

manufacturer are strictly observed.

2. Maximum permitted voltage drop in the 24 V power supply cable.

Values concerning cable lengths and permitted voltage drops must be observed

during project planning for group drives.

3. Maximum cable cross section of 1x1.5 mm2 or 2x0.75 mm2.

A calculation based on the technical data of MOVITRAC® B must be performed

separately for each group drive application


  • AMAT 0190-12695 SBS CL7 3U CompactPCI Single Board Computer
  • AMAT 0190-11817 CP3-SER16-TTL 16-Port Serial Interface Card
  • AMAT 0190-11524 CDN500-25 Interlock Module
  • AMAT 0190-07450 CompactPCI 48-Channel Digital I/O Interface Board
  • AMAT 0190-05990-001 Maglev Rotation System Controller (300mm)
  • AMAT 0190-05647 LK3710 Serial Module Transition Card
  • AMAT 0190-04457 High-Performance Integrated Circuit Control Module
  • Applied Materials (AMAT) 0190-04098 | 5.X Factory Interface I/O Distribution Board
  • Applied Materials (AMAT) 0190-03705 | MF Producer SE/E Interlock Module
  • Applied Materials (AMAT) 0190-02748 | Flex Scanner Transition Module
  • Applied Materials (AMAT) 0190-02362 | Mainframe Interlock 1 Relay Module
  • Applied Materials (AMAT) 0190-01227 | Intelligent Motor Control OMS Board
  • Applied Materials (AMAT) 0190-00318 | VME 486 Video Controller
  • Applied Materials (AMAT) 0130-14007 | Advanced RF Signal Assembly
  • Applied Materials (AMAT) 0130-14005 | RF Cable/Interface Assembly
  • Applied Materials (AMAT) 0130-01218 | High-Efficiency RF Interface Controller
  • Applied Materials (AMAT) 0110-77040 | Head Pneumatic Controller
  • Applied Materials (AMAT) 0110-00077 | Precision Control Module
  • AMAT 0101-57015 high-performance Next-Generation Deflection Amplifier Board
  • AMAT 0100-77040 critical Head Pneumatic Controller Board
  • AMAT 0100-76291 Data Buffer / Memory Expansion Interface
  • AMAT 0100-76290 Advanced I/O Interface Board
  • AMAT 0100-76269 Control Board / Interface Module
  • AMAT 0100-71462-01 high-performance Process Controller PCB
  • AMAT 0100-71171 Chamber Interlock Control PCB
  • AMAT 0100-71154 Semiconductor Circuit Board / Electronic Group Card
  • AMAT 0100-70034 PCB Assembly (PCBA) for Endpoint VGA I/O Interconnect.
  • AMAT 0100-38032 ESC (Electrostatic Chuck) Controller PCB
  • AMAT 0100-36035 DPS Source Match / Seriplex I/O Distribution PCB
  • AMAT 0100-35231 Seriplex I/O Distribution Module
  • AMAT 0100-35217 TC Amp Interlock PCB Module
  • AMAT 0100-35065 High-Precision Serial Isolator PCB
  • AMAT 0100-35054 Advanced Chamber Interface Module
  • AMAT 0100-20453 DeviceNet Digital I/O Interface Board
  • AMAT 0100-20100 High-Performance Semiconductor Component
  • AMAT 0100-20068 Precision CCD Image Control Board
  • AMAT 0100-20064 Advanced Semiconductor Control Module
  • Applied Materials (AMAT) 0100-20018 Advanced Communication Interface Module
  • Applied Materials (AMAT) 0100-20016 High-Performance Interface and Control Module
  • Applied Materials (AMAT) 0100-20003 Digital I/O (DI/DO) Interface Board
  • Applied Materials (AMAT) 0100-20001 System Electronics Interface (SEI) / PCB Assembly
  • Applied Materials (AMAT) 0100-11030 Chamber Hardware / Gas Distribution Component
  • Applied Materials (AMAT) 0100-11022 Semiconductor Board Card
  • Applied Materials (AMAT) 0100-11018 Advanced Interface Control Module
  • Applied Materials (AMAT) 0100-11001 Precision Analog Output Board
  • ​Applied Materials (AMAT) 0100-11000 High-Precision Analog Input Board
  • Applied Materials (AMAT) 0100-09237 Advanced Signal Interface Module
  • Applied Materials (AMAT) 0100-09204 Advanced Digital Interface Control Board
  • Applied Materials (AMAT) 0100-09172 High-Density Digital I/O Control Board
  • Applied Materials (AMAT) 0100-09137 High-Performance VME Control Module
  • Applied Materials (AMAT) 0100-09054 Precision Analog Input Board
  • Applied Materials (AMAT) 0100-09029 Turbo Interconnect Interface Module
  • AMAT 0100-03391 Precision Semiconductor Control
  • AMAT 0100-01984 | VME System Interface & Logic Controller Board
  • AMAT 0100-01363 | VME Intelligent System Control & I/O Board
  • AMAT 0100-01321 | VME DeviceNet Scanner / Interface Board
  • AMAT 0100-00793 | VME Multi-Channel Interface & Logic Board
  • AMAT 0100-00689 | VME PCB Power Module
  • AMAT 0100-00580 | VME Intelligent System Controller Board
  • AMAT 0100-00523 | VME Multi-Channel Analog-to-Digital (A/D) Board
  • AMAT 0100-00493 | VME Multi-Function System Controller Board
  • AMAT 0100-00398 | VME Interface System Control Board
  • AMAT 0100-00369 | VME 12-Channel High-Speed Stepper Motor Controller
  • ​AMAT 0100-00196 | VME System Mainframe CPU Controller Board
  • AMAT 0100-00169 | VME 12-Channel Stepper Motor Controller Board
  • AMAT 0100-00162 | VME Dual Channel Serial Communication Board
  • AMAT 0100-00137 | VME Stepper Motor Controller Interface Board
  • AMAT 0100-00075 | VME Digital Input/Output (DI/O) Interface Board
  • AMAT 0100-00007 VME Analog Input/Output Interface Board
  • AMAT 0100-00002 | VME Slave I/O Interface PCB
  • AMAT 0090-05596 High-Voltage DC Power Cable Assembly
  • AMAT 0090-01809 | High-Performance RF Power Cable Assembly
  • AMAT 0010-29958 | CCM HART 3 Mainframe Control Assembly
  • AMAT 0010-20003 System Controller Card Cage Assembly
  • AMAT 0010-11239 PVD High-Voltage Power Interface Assembly
  • AMAT 0010-09416 RF Matching Network Assembly
  • AMAT 0010-00019 Analog Power Supply Assembly
  • AMAT AS00009-02 (31-000-00940) | Precision Semiconductor Component
  • AMAT 0010-00028 Power Supply Module
  • AMAT 0330-1586A Serial Communication PCB
  • AMAT 0190-09690 Seriplex SENSORbus SPX-MUXADIO-001
  • AMAT 0190-04397 DeviceNet I/O Interface Board
  • AMAT 0190-02506 DeviceNet I/O Interface Card
  • AMAT 0090-00475 Seriplex 210 MUXADIO
  • AMAT 410-0198-1 Multi-Output Switching Power Supply
  • AMAT 0100-20458 high-reliability Configurable Interlock Personality Board
  • AMAT VAS104350-0415 Gasline Heater Control Unit
  • AMAT VME6U1V2 VMEbus Backplane Interface Module
  • AMAT 0920-01070 high-performance RF Power Generator
  • AMAT 0090-76133A VME Single Board Computer (SBC)
  • AMAT 0190-24115 DeviceNet I/O Interface Card
  • AMAT 0190-37607 Backplane / Base Board Assembly
  • AMAT 0190-32372 Analog Input/Output (I/O) Board
  • AMAT 0190-09956 Loadlock Interface PCB Base Assembly
  • AMAT 0190-07908 four-channel DeviceNet Interface Card
  • AMAT 0190-07905 (UPS) control board
  • AMAT 0190-07502 Precision Controller / Interface Board
  • AMAT 0190-03680 I/O Backplane
  • AMAT 0190-02200 Water Leak Detection Control Board
  • AMAT 0100-76124 Digital I/O Board Assembly
  • AMAT 0100-35563 Leak Detector Configuration PCB
  • AMAT 0100-35250 Chamber Interface DPS Centura PCB
  • AMAT 0100-35124 Seriplex I/O Distribution Board
  • AMAT 0100-35058 Loadlock Interlocks PCB
  • AMAT 0100-20213 RF Match Detector PCB
  • AMAT 0100-20063 Interface PCB Assembly
  • AMAT 0100-09225 TC AMP/INTERLOCK PCB
  • AMAT 0100-09153 Gas Panel Interface PCB
  • AMAT 0100-09127 Loader Interconnect Board
  • AMAT 0100-09009 Buffer I/O PCB Card
  • AMAT 0100-02813 Signal Conditioning Board
  • AMAT 0100-01911 AC Gas Heater Control Board
  • AMAT 0100-01708 Pedestal Integration PCB
  • AMAT 0100-00658 300mm RTP Controller Distribution PCB
  • AMAT 0100-00582 Gas Panel Controller Backplane
  • AMAT 0100-00049 Analog Signal Conditioner
  • AMAT 0100-00008 Control Interface Module
  • AMAT 0090-03402 DC Power Supply / Power Module
  • AMAT 0090-01248 DC Power Supply / Power Module
  • AMAT 0090-76109 RF Matching / Capacitor Assembly
  • AMAT 0101-57106 Substrate Voltage Board
  • AMAT 0101-57014 Deflection-Amplifier PCB
  • AMAT 0101-57012 AKT Column Control PCB (COL-C 50-10)
  • AMAT AKT 0241-58482 PCB
  • AMAT 0241-58255 REV05 PCB
  • AMAT 0161-57042 AKT framework
  • AMAT 0101-57196 electronic control board
  • AMAT 0101-57178 Digital Input / Interface PCB