The measurements include:
□ Input signal
□ Valve position with contactless sensor
□ Actuator pressures, 2 independent measurements
□ Supply pressure
□ Spool valve position
□ Device temperature
Advanced self-diagnostics guarantees that all measurements
operate correctly. After connections of electric signal and pneumatic supply, the micro controller (μC) reads the input signal,
position sensor (α), pressure sensors (Ps, P1, P2) and spool position sensor (SPS). A difference between input signal and position
sensor (α) measurement is detected by control algorithm inside
the μC. The μC calculates a new value for prestage (PR) coil current based on the information from the input signal and from the
sensors. The changed current to the PR changes the pilot pressure to the spool valve. Reduced pilot pressure moves the spool
and the actuator pressures change accordingly. The spool opens
the flow to the driving side of the double diaphragm actuator and
opens the flow out from the other side of the actuator. The
increasing pressure will move the diaphragm piston. The actuator
and feedback shaft rotate. The position sensor (α) measures the
rotation for the μC. The μC using control algorithm modulates the
PR-current from the steady state value until the new position of
the actuator, according to the input signal, is reached.

TECHNICAL SPECIFICATIONS
ND9000 INTELLIGENT VALVE CONTROLLER
General
Loop powered, no external power supply required.
Suitable for rotary and linear valves.
Actuator connections in accordance with VDI/VDE 3845 and IEC
60534-6 standards.
Flush mounting on selected actuators
Action: Double or single acting
Travel range: Linear; 10–120 mm / 0.4-4.7 in
rotary; 45–95 degrees. Measurement
range 110° with freely rotating
feedback shaft.
Environmental influence
Standard temperature range:
-40° – +85 °C / -40° – +185 °F
Arctic temperature range: -53° – +85 °C / -64° – +185 °
Influence of temperature on valve position:
0.5 % /10 °K
Influence of vibration on valve position:
< 1 % under 2g 5–150 Hz,
1g 150–300 Hz, 0.5g 300–2000 Hz
Enclosure
Material: ND9100: Anodized aluminum alloy
and polymer composite
ND9200: Anodised aluminum alloy
and tempered glass
ND9400: Stainless steel and polymer
composite
ND9300: Stainless steel
Protection class: IP66, Nema 4x
Pneumatic ports: G 1/4 (ND9100)
1/4 NPT (ND9200, ND9300 & ND9400)
Cable gland thread: M20x1.5 (ND9000 )
1/2 NPT (ND9000E2, ND9000U)
Weight: 1.8 kg / 4.0 lbs (ND9100)
3.4 kg / 7.5 lbs (ND9200)
5.6 kg / 12.4 lbs (ND9400)
8.6 kg / 19.0 lbs (ND9300)
Mechanical and digital position indicator visible through main
cover, not applicable to ND9200E2 and ND9300.
Special corrosion resistant design or stainless steel housing available as an option for demanding environment.
Pneumatics
Supply pressure: 1.4–8 bar / 20–115 psi
Effect of supply pressure on valve position:
< 0.1 % at 10 % difference in inlet
pressure
Air quality: Acc. to ISO 8573-1
Solid particles: Class 5 (3 – 5 μm
filtration is recommended)
Humidity: Class 1 (dew point 10 °C/
18 °F below minimum temperature
is recommended)
Oil class: 3 ( or < 1 ppm)
Capacity with 4 bar / 60 psi supply:
5.5 Nm3/h / 3.3 scfm (spool valve 2)
12 Nm3/h / 7.1 scfm (spool valve 3)
38 Nm3 /h /22,4 scfm (spool valve 6)
Consumtion with 4 bar / 60 psi supply in steady state position:
< 0.6 Nm3/h /0.35 scfm
(spool valve 2 & 3)
< 1.0 Nm3/h / 0.6 scfm (spool valve 6)
Electronics
HART
Supply power: Loop powered, 4–20 mA
Minimum signal: 3.6 mA
Current max : 120 mA
Load voltage: up to 9.7 VDC/20 mA
(corresponding 485 Ω)
Voltage: max. 30 VDC
Polarity protection: -30 VDC
Over current protection: active over 35 mA
Profibus PA and FOUNDATION fieldbus
Supply power: voltage 9–32 VDC, reverse polarity
protection
Max basic current: 17.2 mA
Quiescent Current Draw: 16 mA
Fault current (FDE): 3.9 mA
FOUNDATION fieldbus function block
execution times
AO 20 ms
AI 20 ms
PID 20 ms
DO 20 ms
DI 15 ms
IS 15 ms
OS 15 ms
Performance with moderate constant-load actuators
Dead band: ≤ 0.1 %
Hysteresis: < 0.5 %
Local User Interface (LUI) functions □ Local control of the valve
□ Monitoring of valve position, target position, input signal, temperature, supply and actuator pressure difference
□ Guided-startup function
□ LUI may be locked remotely to prevent unauthorised access
□ Calibration: Automatic / Manual linearization
□ 1-point calibration
□ Control configuration: aggressive, fast, optimum, stable, maximum stability
□ HART version configuration: HART 6 or HART 7
□ Configuration of the control valve
□ Rotation: valve rotation clockwise or counter-clockwise to close
□ Dead Angle
□ Low cut-off, cut-off safety range (default 2 %)
□ Positioner fail action, open/close
□ Signal direction: Direct/reverse acting
□ Actuator type, double/single acting
□ Valve type, rotary/linear
□ Language selection: English, German and French
Position transmitter (optional)
Output signal: 4–20 mA (galvanic isolation;
600 VDC)
Supply voltage: 12–30 VDC
Resolution: 16 bit / 0.244 μA
Linearity: < 0.05 % FS
Temperature effect: < 0.35 % FS
External load: max 0–780 Ω
max 0–690 Ω for intrinsically safe
Ex ia IIC T6 Ui ≤ 28 V