shield clamps comprises:
– 2 shield clamps for power cable (2 contact clips each)
– 1 shield clamp for signal cable (1 contact clip) for MDX60B
– 1 shield clamp for signal cable (2 contact clips) for MDX61B
– 6 contact clips
– 6 screws for attaching the contact clips
– 3 screws for attaching the contact clips to the unit
Sizes 1-6 • 1 set of shield clamps for signal cable, not installed. The set of shield clamps comprises:
– 1 shield clamp for signal cable (1 contact clip)
– 2 contact clips
– 2 screws for attaching the contact clips
– 1 screw for attaching the shield clamp to the unit
• Only for size 6: Carrying bar and 2 split pins
Size 2S • Accessories set, not installed. The accessories set (→ Following illustration) comprises:
– 2 mounting feet [1] to be plugged into the heat sink
– 2 touch guards [2] to be fastened to terminals X4: -Uz/+Uz and X3:-R(8)/+R(9).
Once the touch guards [2] have been installed, the enclosure is IP20. Otherwise
it is IP10 (→ Section "Touch guards").

Optional scope of delivery
All sizes • Option DBM60B: Door installation for separate mounting of the DBG60B keypad
(e.g. in the control cabinet).
Part number 824,853 2.
The DBM60B option consists of the housing with enclosure IP65 and a 5 m extension cable (→ Following illustration). Das Bediengerät DBG60B ist in dieser Option
nicht enthalten und muss separat bestellt werden.

• Option DKG60B: 5 m Verlängerungskabel für Bediengerät DBG60B.
Part number 817 583 7.
5 m extension cables are available for mounting the keypad separately in customer
housing (→ Following illustration).

Size 2 S • DMP11B mounting panel (→ following figure), not installed.
Part number 818 398 8.
If a MOVIDRIVE® MD_60A size 2 unit is to be replaced by MOVIDRIVE® MDX61B
size 2S, the MDX61B size 2S can be fitted on the existing mounting plate with the
DMP11B mounting panel. New retaining holes do not have to be drilled.
54588AXX
DMP11B

Connector adapter
for replacing
MOVIDRIVE® A
with
MOVIDRIVE® B
The following adapters are available for rapid replacement of a MOVIDRIVE® A unit with
a MOVIDRIVE® B unit.
• DAT11B: Terminal adapter, part number 824 671 8
X10 can be rearranged directly when using MOVIDRIVE® MDF, MDV or MDS. Three
plugs have to be rewired. You can avoid such rewiring work by using the DAT11B
terminal adapter. Using this adapter will prevent incorrect connection and save time.
The terminal adapter is required for terminals X11 (analog input), X12 (SBus) and
X13 (binary inputs).

• DAE14B: Encoder adapter X14, part number 817 630 2
If a synchronous encoder is operated at X14 on MOVIDRIVE® MDV, MDS, MCV or
MCS, connection takes place via a 9-pin connector. Since the DEH11B and DER11B
options for MOVIDRIVE® MDX61B come equipped with a 15-pin plug, you will either
have to rework the encoder cable or use the encoder adapter. The encoder adapter
can be plugged directly between the existing encoder cable with 9-pin socket and the
15-pin connector on DEH11B/DER11B. This step makes for fail-safe and fast connection of existing drives

• DWE11B: Interface adapter (adapter cable), part number 188 187 6
The interface adapter DWE11B (HTL→TTL) in the form of an adapter cable is used
to connect single-ended HTL encoders to the HIPERFACE®encoder card
DEH11B. Only the A, B and C tracks are connected. The interface adapter is suitable
for all HTL encoders that were operated on MOVIDRIVE® A, MDV and MCV and can
be connected without any rewiring effort

[1] X1: Power supply connection 1/L1, 2/L2, 3/L3, separable
[2] X4: Connection for DC link connection –UZ +UZ, separable
[3] Fieldbus slot
[4] Expansion slot
[5] Encoder slot
[6] X3: Braking resistor connection 8/+R, 9/–R and PE connection, separable
[7] Electronics shield clamp and PE connection
[8] X2: Motor connection 4/U, 5/V, 6/W and PE connection, separable
[9] X17: Electronics terminal strip for safety contacts for safe stop
[10] X10: Electronics terminal strip for binary outputs and TF/TH input
[11] X16: Electronics terminal strip for binary inputs and outputs
[12] X13: Electronics terminal strip for binary inputs and RS485 interface
[13] X11: Electronics terminal strip for setpoint input AI1 and 10 V reference voltage
[14] X12: Electronics terminal strip for system bus (SBus)
[15] DIP switches S11 ... S14
[16] XT: Slot for DBG60B keypad or UWS21B serial interface
[17] 7-segment display
[18] Memory card

[1] X1: Power supply connection 1/L1, 2/L2, 3/L3
[2] X4: Connection for DC link connection –UZ +UZ and PE connection
[3] Memory card
[4] Fieldbus slot
[5] Expansion slot
[6] Encoder slot
[7] X3: Braking resistor connection 8/+R, 9/–R and PE connection
[8] Electronics shield clamp and PE connection
[9] X2: Motor connection 4/U, 5/V, 6/W
[10] X17: Electronics terminal strip for safety contacts for safe stop
[11] X10: Electronics terminal strip for binary outputs and TF/TH input
[12] X16: Electronics terminal strip for binary inputs and outputs
[13] X13: Electronics terminal strip for binary inputs and RS485 interface
[14] X11: Electronics terminal strip for setpoint input AI1 and 10 V reference voltage
[15] X12: Electronics terminal strip for system bus (SBus)
[16] DIP switches S11 ... S14