mode until the terminal is de-energized.
If this input remains energized for at least 1 s, the faults detected in monitoring
level 2 are reset. This means that the relays will be de-energized and the text display
will be deleted from the screen as long as the monitored currents are not exceeding
the configured threshold level.
When this input is energized, the differential protection is disabled.This means that
the differential current is not monitored, no relay can be enabled and no text is dis
played.
This relay becomes enabled when the unit detects threshold limit 2 (main stage) has
been exceeded. The configured differential current characteristics and delay time will
determine how relay 1 functions.
This relay becomes enabled when the unit detects threshold limit 2 (main stage) has
been exceeded. The configured differential current characteristics and delay time will
determine how relay 2 functions.
This relay becomes enabled when the unit detects threshold limit 1 has been ex
ceeded. The configured differential current characteristics and delay time will deter
mine how relay 4 functions.
This relay is enabled when the unit is operational and the differential current is being
monitored. The relay becomes disabled if the monitoring is deactivated through any
of the following reasons:
• the internal self-monitoring has detected a malfunction of the unit. A correct func
tioning of the unit cannot be guaranteed and corrective action may be necessary.
• the set values for parameter "CT-ratio" or parameter "Generator Current" are out
side the permissible limits (see page 19).
• the digital input "Blocking" is energized.
• the parameter "Monitoring" is configured to "Off".

When in configuration mode (simultaneous pressing of "Digit↑" and "Cursor→"), the configuration screen can
be advanced by pressing the "Select" button. Should there be no entry, parameter change or other action for 60
seconds, the unit will automatically revert into Automatic mode.
During the configuration mode, the monitoring function is still active. This means inevitably, that while adjusting
parameters during operation, it is possible to cause a tripping of the relay.
adjust settings
[press "SELECT"]
Configuration mode "Select" button
Pressing the "Select" key activates the configuration mode, and the following pa
rameters can be enabled or changed within the given limits. Please you note that as
you advance through the configuration screens, by configuring some parameters as
"ON", additional screens must be configured relating to that parameter. If the pa
rameter is configured as "OFF", the additional screens will be disabled and not dis
played.
Software version
Software version
Displays the software version.
SPRACHE/LANGUAGE ----------------
Language selection english/german
The screens can be displayed in German or English.
curr. transform.
ratio 0000/x
CT-Ratio Selection 10 to 6.000/{x} A
The Ratio of the CTs being used is entered here. The CTs should be selected so that
in fault-free operation at generator rated current, at least 60 % of nominal current
flows in the CT-secondary. Failure to use properly a sized CT-Ratio leads to loss of
resolution and inaccuracies in the monitoring functions.
generator nomin.
current 0000A
Generator rated current 5 to 6.000 A
This value is used as reference value for the calculation and display of restraint cur
rent and differential current. The entered value of generator current must be at least
60% of the nominal current of the CT and must not exceed the entered value of CT
nominal current.
Example CT-Ratio 500/5 A
Range of Generator rated current 300 A to 500 A.
If the nominal value is less than 50% of the transformer ratio, the message "Wrong
Entry" will be displayed on the screen in Automatic mode and the unit will de
activate monitoring functions (the Monitoring LED goes out).
automatic reset
relay ON
Automatic reset of the relay ON/OFF
Applies only to monitoring level 2 (tripping).
Monitoring level 1 (warning) always Auto-resets.
ON................The relays de-energize automatically when the fault is no longer pre
sent. The screen input "Automatic reset of error text" determines
what happens to the Alarm-text in the display.
OFF..............The relays remain energized until they are reset.
monitoring
ON
Monitoring ON/OFF
ON................Monitoring of the differential current is active and the follow
ingscreens of this option are displayed.
OFF..............The monitoring is de-activated and the following screens are not dis
played.
release limit
Is/In X=000%
Trigger Value IS/IN (X12) 50 to 300 %
Definition of the threshold characteristic for the monitoring of levels 1 and 2.
This value determines the horizontal position (X12-coordinates of points
P [X12/Y1] and P [X2/Y2]) of the corner points of the Warning and Tripping char
acteristics.
release limit
Id/In Y=000%
Limit valueId
This value determines the vertical position (Y2-coordinate) of the corner point
P [X12/Y2] of the tripping characteristic (monitoring level2).