Step 3: Check MV-53 (Control State)
a) Should be ì32î (Run).
b) If not, check Run, R-Stop and F-Stop wiring.
Step 4: Check MV-41 (External Reference Frequency).
a) Should display the lead sensor frequency.
b) If not, check signal at External Reference Frequency input, and the configuration jumpers per Chapter 2
of the ìM-Drive User Manualî.
Step 5: Check MV-45 (Scaled Reference).
a) Should not be zero.
b) If zero, press ìSETSPEEDî and enter a non-zero ratio setpoint.
c) Check CP-11 (Maximum Limit) and enter a value greater than CP-37 (RPM Fdbk Secondary Max).