Note: 10 Hz DC filter (see DC filtering on page 6).
• Current measurement range : ±50 mAPEAK-PEAK (AC + DC input)
Input impedance
• Voltage : ≥100 kΩ, between the differential (high and low) inputs
• Current : 200 Ω ±0.2%
Dynamic input range : ≥72 dB
DC filtering
DC filter
• Cutoff frequency (−3 dB) : 10 Hz ±3.5 Hz
• Roll-off : −40 dB/decade (second order)
Note: The DC filter is used to extract the DC part of an auxiliary input when it is configured as a DC input.
Sensor/measurement chain OK check
Number of levels : Up to 16 configurable threshold levels (16 DC regions)
OK level range
• Voltage inputs : ±20 VDC
• Current inputs : 0 to 23 mA
Operating principle
• SIL safety sensors : Line-fault detection of conditions such as a problem with the sensor
and/or cabling, problem with the signal conditioner, and/or other
problem with the measurement chain or power supply.
Note: Requires a SIL safety sensor/measurement chain that
provides a suitable diagnostic signal (DC bias level), for example,
measurement chains using IPC707 or IQS900 signal conditioners.
• Standard sensors : Powered sensors – line-fault detection of conditions such as
open-circuit or short-circuit.
Unpowered sensors – line-fault detection of conditions such as
open-circuit.
Digital signal processing
Analogue to digital converter (ADC) : 24 bit
Dynamic range : ≥80 dB
Frequency bandwidth : 0 Hz to 20 kHz
Accuracy
• Amplitude : ≤1% of input full scale
• Phase : ≤1.5°
Digital filtering
• Notch filter : 50 or 60 Hz
• ISO 2954 filter : 10 Hz to 1 kHz (−3 dB), −24 dB/octave
• Band-pass filter : <0.1 dB ripple in pass band, >55 dB attenuation in stop band,
0.1 or 3 dB attenuation at cutoff, −24 to −60 dB/octave slope
• High-pass filter : 0.25 to 400 Hz
• Low-pass filter : 10 Hz to 20 kHz
Data acquisition : Fixed frequency or order tracking
Fixed frequency : Frequency span: 0.25 Hz to 20 kHz.
Note: The low-pass filter (LPF) cutoff frequency to high-pass filter
(HPF) cutoff frequency ratio must be less than 400 when the HPF
cutoff frequency is less than 3 Hz. See also Digital filtering above.
Order tracking : Digital resampling.
Tracking range: 300 to 6000 RPM (default).
Frequency span: DC to 3.125, 6.25, 12.5, 25, 50 or 100 orders.
Waveform averaging: 1 (default).
Note: Order tracking requires a reference speed (auxiliary input
configured as a tacho/speed channel).
Measurement resolution : 2 048, 4096, 8192 or 16384 point waveform /
800, 1600, 3200 or 6400 line spectrum
FFT window types : Blackman, Blackman-Harris, Flat top, Hamming, Hanning,
Kaiser α=1, Kaiser α=5, Kaiser α=10, Rectangular or Tukey α=0.5.
Note: Hanning is the default window type.
FFT resolution : 800, 1600, 3200 or 6400 spectral lines
Data sampling rate : 2.56 × frequency bandwidth
Extracted data (measurements) : Up to 10 processed outputs per channel/processing function.
See Processing functions on page 10.
Extracted data types : Time domain measurements: Scalar.
Frequency domain measurements: Scalar, Vector and Phasor.
Fixed-frequency measurements : Time domain or Frequency domain measurements.
Time domain measurements: Overall (Scalar).
Frequency domain measurements:
Single frequency – nX (Amplitude + Phase (Vector)),
Band – Band start to Band stop (Amplitude (Scalar)),
Highest peak – Band start to Band stop (Amplitude + Phase
+ Frequency (Phasor)).
Order-tracking measurements : Frequency domain measurements only.
Frequency domain measurements:
Single frequency – nX (Amplitude + Phase (Vector)),
Band – Band start to Band stop (Amplitude (Scalar)),
Highest peak – Band start to Band stop (Amplitude + Phase
+ Frequency (Phasor)).
Integration count : 0, 1 or 2 (Acceleration to Velocity or Displacement), as required
Measurement types : Time domain measurements: True RMS, True Peak, True Peak-peak,
True Average.
Frequency domain measurements: Amplitude + Phase (Vector).
Note: True RMS and True average measurements have a
configurable Response time (400 ms default). True Peak and
True Peak-peak measurements have a configurable Decay time
(4700 ms default).
Qualifiers (rectifiers) : Time domain measurements: True RMS, True Peak, True Peak-peak,
True Average, Scaled Peak, Scaled Peak-peak or Scaled Average.
Frequency domain measurements: RMS, Peak, Peak-peak or
Average.
Update rate – internal
(MPC4Mk2 module)
: 20 ms min. for time domain processing.
100 ms min. for frequency domain processing.
Note: MPC4Mk2 + IOC4Mk2 and RLC16Mk2 relays are also updated
every 20 ms.
Update rate – external
(VibroSight Capture condition
monitoring data update rate)
: Configurable as 100 ms, 200 ms, 500 ms, 1 s, 2 s or 5 s.
Note: 1 s is the default VibroSight Capture condition monitoring
update rate.
Update rate – external
(VibroSight Capture condition
monitoring data logging rule rate)
: Configurable between 100 ms and 99 days
Update rate – external
(VibroSight Vision live data
display interval)
: Configurable as 100 ms, 200 ms, 500 ms, 1 s, 2 s, 5 s, 10 s, 20 s, 50 s, …
Machinery protection system (MPS) functionality / processing
Measurement resolution
(fixed)
: 2048 point waveforms / 800 line spectra