• Configurable inputs : Outputs from level 1 (basic) logic functions.
Note: Level 1 (basic) and level 2 (advanced) logic functions can
be combined to generate more complex logic function.
Alarm update rate (internal) : 100 ms max.
Note: This is the time required for MPC4Mk2 + IOC4Mk2 modules to
detect and initiate an alarm, including output relay (RL1 to RL4)
activation.
Discrete signal interface (DSI) inputs
Control signal
• Alarm bypass (AB) : A closed contact between the DSI AB and RET inputs inhibits the
activation of alarms and relays on MPC4Mk2 + IOC4Mk2 modules.
Note: The common circuit-fault relay (FAULT) is activated when
Alarm bypass (AB) is enabled.
• Alarm reset (AR) : A closed contact between the DSI AR and RET inputs resets (clears)
the alarms and relays latched by MPC4Mk2 + IOC4Mk2 modules.
Note: The Alarm reset (AR) input is edge-sensitive and a high-to-low
transition is required to activate the reset. The Alarm reset (AR) input
should not be held low and must transition low-to-high before
another reset (high-to-low) can activate the reset.
• Trip multiply (TM) : A closed contact between the DSI TM and RET inputs multiplies the
configured alarm levels for MPC4Mk2 + IOC4Mk2 modules by a scale
factor (software configurable)
Operating principle : Detection of an open circuit or a closed circuit on the input
Buffered outputs – dynamic channels
Number : 4
Type : Buffered outputs (buffered “raw” analog signal).
Buffered analog signals corresponding to dynamic channel input
channels (CH1 to CH4) are available on BNC connectors on the
MPC4Mk2 module (front of rack) and on the J2 screw-terminal
connector on the IOC4Mk2 module (rear of rack).
See Connectors on page 17.
Frequency bandwidth : DC to 60 kHz
Output impedance : <5 Ω
Accuracy
• Amplitude : ± 0.1 dB up to 20 kHz.
± 3 dB from 20 to 60 kHz.
• Phase : <1° from 10 Hz to 2 kHz.
<15° from 2 to 20 kHz.
Transfer ratios
• Voltage input : 1 V/V
• Current input : 0.2 V/mA
Admissible load on output
• Resistance : ≥50 kΩ
• Capacitance : Able to drive up to 3 m of cable with a typical capacitance
of 100 pF/m
• Impedance : >50 kΩ with a load capacitance <5 nF
Buffered outputs – auxiliary channels
Number : 2
Type : Buffered outputs (buffered “raw” analog signal or TTL-level signal).
Buffered analog signals corresponding to auxiliary input
channels (AX1 and AX2) are available on BNC connectors on the
MPC4Mk2 module (front of rack) and on the J2 connector on the
IOC4Mk2 module (rear of rack).
See Connectors on page 17.
Note: When an auxiliary input is configured as a tachometer input,
a buffered TTL-level signal corresponding to the auxiliary input
channel (AX1 or AX2) is available on the J2 connector on the
IOC4Mk2 module (rear of rack). When an auxiliary input is
configured as a DC input, no digital TTL-level signal is available.
Frequency bandwidth : DC to 60 kHz
Output impedance
• Buffered TTL-level signal
(tachometer input)
: <300 Ω
• Buffered “raw” analog signal
(DC input)
: <5 Ω
Signal levels : 0 to 5 V TTL-compatible signal (non-inverting)
Admissible load on output
• Resistance : >50 kΩ
• Capacitance : Able to drive up to 3 m of cable with a typical capacitance
of 100 pF/m
• Impedance : >50 kΩ with a load capacitance <5 nF
Analog outputs
Number of local outputs : 4 single-ended outputs.
Used to output quasi-static measurement signals (DC).
Individually configurable as either current or voltage output signals.
Current outputs
• Range : 4 to 20 mA.
Two modes of operation are supported, as follows:
• Mode 1, measured value with quality checks – the analog output
is driven in the 4 to 20 mA signal range during normal operation,
and the analog output is driven to 2 mA to indicate a problem.
• Mode 2, measured value without quality checks – the analog
output is driven in the 2 to 23 mA signal range.
Note: Current outputs are 0 mA ± 0.5 mA when disabled.
• Resolution : 10 µA
• Accuracy : ≤1% of full scale
• Admissible load on output : >360 Ω
Voltage outputs
• Range : 0 to 10 V.
Note: Voltage outputs are 0 V ± 10 mV when disabled.
• Resolution : 2.5 mV
• Accuracy : ≤1% of full scale
• Admissible load on output : >50 kΩ with a load capacitance <5 nF
Update rate / frequency bandwidth : 100 ms / 10 Hz max.
Short-circuit protection : Yes
Discrete outputs
Relays
• Number : 5.
4 × output relays (RL1 to RL4) – suitable for alarm and/or
status outputs.
1 × common circuit-fault relay (FAULT) – for fault indication.
See Relay characteristics on page 14.
• Configurable functions : Normally energized (NE) or normally de-energized (NDE).
Latched or unlatched.
• Configurable inputs : From the sensor OK checks, the measurement alarms (Danger+,
Alert+, Alert−, Danger−) and/or the logic functions of the MPC4Mk2
module
Communication interfaces
External (Ethernet)
• Number : 1.
Available on LAN connector of the MPC4Mk2 module.
See Connectors on page 17.
• Network interface : 10/100BASE-TX
• Data transfer rate : Up to 100 Mbps
• Maximum distances : System Ethernet communications can support distances up to